Unless explicitly specified otherwise, the following technical specifications are valid for all SINAMICS G120C compact converters. General technical specifications |
---|
Mechanical specifications | Vibratory load | | - Transport acc. to EN 60721‑3‑2 1)
| Class 1M2 | - Operation acc. to EN 60721‑3‑3
| Class 3M1 | Shock load | | - Transport acc. to EN 60721‑3‑2 1)
| Class 1M2 | - Operation acc. to EN 60721‑3‑3
| Class 3M2 | Degree of protection | IP20/ UL open type | Permissible mounting position | Vertical wall mounting | Ambient conditions | Protection class According to EN 61800‑5‑1 | Class III (PELV1) | Touch protection According to EN 61800‑5‑1 | Class I (with protective conductor system) | Humidity, max. | 95 % at 40 °C (104 °F), condensation and icing not permissible | Ambient temperature | | - Storage 1) acc. to EN 60068‑2‑1
| -40 ... +70 °C (-40 ... +158 °F) | - Transport 1) acc. to EN 60068‑2‑1
| -40 ... +70 °C (-40 ... +158 °F) | - Operation acc. to EN 60068‑2‑2
| -10 ... +40 °C (14 ... 104 °F) without derating >40 ... 60 °C (104 ... 140 °F) see derating characteristics | Environmental class in operation | | - Harmful chemical substances
| Class 3C2 to EN 60721‑3‑3 | - Organic/biological pollutants
| Class 3B1 to EN 60721‑3‑3 | | 2 acc. to EN 61800 | Standards | Compliance with standards | CE, UL, cUL, C-Tick (RCM) | Fail-safe certification | Function: Safe Torque Off (STO) | | SIL 2 | - According to EN ISO 13849‑1
| PL d and Category 3 | CE marking, according to | EMC Directive 2004/108/EC Low-Voltage Directive 2006/95/EC | EMC Directive 2) According to EN 61800‑3 | | Interference immunity | The SINAMICS G120C compact inverters are tested according to the interference immunity requirements for environments according to Category C3. | Interference emissions | | - Frame sizes FSAA to FSC
without integrated line filter
| 3) | - Frame sizes FSAA to FSC
with integrated line filter class A
| The inverters comply with the limit values according to Category C3. The inverters comply with the limit values for conducted interference and field-conducted interference emissions according to Category C2. 4) 5) | | Note: The EMC product standard EN 61800-3 does not apply directly to a frequency converter but to a PDS (Power Drive System), which comprises the complete circuitry, motor and cables in addition to the converter. The frequency inverters on their own do not generally require identification according to the EMC Directive. |
1) In transport packaging. 2) For further general information, see also chapter SINAMICS G120, section Technical specifications, Compliance with standards. 3) Non-filtered devices are designed for operation in IT systems or in conjunction with an RCD. The customer must provide suitable RI suppression equipment to ensure that these devices comply with the limits defined for Category C3 or C2. 4) Max. permissible motor cable length of 25 m (82 ft) (shielded) as standard - with low-capacitance CY cable for frame sizes FSA and FSB 50 m (164 ft) (shielded), for FSC 100 m (328 ft) (shielded). 5) SINAMICS G120C compact inverters, frame size FSB, with PROFINET interface (Article No.: 6SL3210-1KE21-.AF1) additionally require a line reactor. SINAMICS G120C compact inverter | USS, Modbus RTU version | PROFIBUS DP version | PROFINET, EtherNet/IP version |
---|
| 6SL3210-1KE..-..B1 6SL3210-1KE..-..B2 | 6SL3210-1KE..-..P1 6SL3210-1KE..-..P2 | 6SL3210-1KE..-..F1 6SL3210-1KE..-..F2 |
---|
Integrated bus interface | Fieldbus protocols | - USS
- Modbus RTU
(switchable using a parameter)
| PROFIBUS DP | - ODVA AC/DC drive
- SINAMICS profiles
| Profile | – | - PROFIdrive Profile V4.1
- PROFIsafe
| - PROFIdrive Profile V4.1
- PROFIsafe
- PROFIenergy
| Hardware | Plug-in terminal, insulated, USS: max. 187.5 kBaud Modbus RTU: 19.2 kBaud, Bus terminating resistor that can be switched in | 9-pin SUB-D socket, insulated, max. 12 Mbit/s Slave address can be set using DIP switches | 2 × RJ45, max. 100 Mbit/s (full duplex), device name can be stored on the device | I/O interfaces | Signal cable cross-section | 0.15 ... 1.5 mm2 (28 ... 16 AWG) | Digital inputs – Standard | 6 isolated inputs Optically isolated; Free reference potential (own potential group) NPN/PNP logic can be selected using the wiring | | 11 V | | 5 V | | 15 mA | Digital inputs, fail-safe | 1 When using the standard digital inputs (DI4+DI5) Safety function: Safe Torque Off (STO) | Digital outputs | 1 relay changeover contact 30 V DC, 0.5 A (ohmic load) 1 transistor 30 V DC, 0.5 A (ohmic load) | Analog inputs | 1 analog input Differential input Switchable between voltage (-10 ... +10 V) and current (0/4 ... 20 mA) using a DIP switch 10‑bit resolution Can be used as additional digital input Analog inputs are protected in a voltage range of ± 30 V and have a common-mode voltage in the ± 15 V range. | - Switching threshold: 0 → 1
| 4 V | - Switching threshold: 1 → 0
| 1.6 V | Analog outputs | 1 analog output Non-isolated output Switchable between voltage (0 ... 10 V) and current (0/4 ... 20 mA) using a parameter Voltage mode: 10 V, min. burden 10 kΩ Current mode: 20 mA, max. burden 500 Ω The analog outputs have short-circuit protection | PTC/KTY interface | 1 motor temperature sensor input Connectable sensors PTC, KTY and bimetal, Accuracy ±5 °C (41 °F) | Voltage supply for the integrated Control Unit | 24 V DC via the Power Module or by connecting to an external 20.4 ... 28.8 V DC power supply Typical input current: 500 mA at 24 V DC | Tool interfaces | Memory card | Optional SINAMICS SD card | Operator panels | Optional Basic Operator Panel BOP‑2 or Intelligent Operator Panel IOP | PC interface | USB |
SINAMICS G120C compact inverter |
---|
Open-loop/closed-loop control techniques | U/f linear/quadratic/parameterizable | ✓ | U/f with flux current control (FCC) | ✓ | U/f ECO; linear/quadratic | ✓ | Vector control, sensorless | ✓ | Vector control, with sensor | – | Torque control, sensorless | – | Torque control, with sensor | – | Software functions | Setpoint input | ✓ | Fixed frequencies | 16, parameterizable | JOG | ✓ | Digital motorized potentiometer (MOP) | ✓ | Ramp smoothing | ✓ | Extended ramp-function generator (with ramp smoothing Off3) | ✓ | Positioning down ramp | – | Slip compensation | ✓ | Signal interconnection with BICO technology | ✓ | Free function blocks (FFB) for logical and arithmetic operations | – | Switchable drive data sets (DDS) | ✓ (2) | Switchable command data sets (CDS) | ✓ (2) | Flying restart | ✓ | Automatic restart after line supply failure or operating fault (AR) | ✓ | Technology controller (internal PID) | ✓ | Energy consumption counter | ✓ | Energy saving computer | ✓ | Thermal motor protection | ✓ (I2t, sensor: PTC, KTY and bimetal) | Thermal inverter protection | ✓ | Motor identification | ✓ | Motor holding brake | ✓ | Auto-ramping (Vdcmax controller) | ✓ | Kinetic buffering (Vdcmin controller) | ✓ | Braking functions | | | ✓ | | ✓ | - Dynamic braking with integrated braking chopper
| ✓ |
General technical specifications of the power electronics |
---|
System operating voltage | 380 ... 480 V 3 AC +10 % -20 % | Grid requirement Short-circuit power RSC | No restriction | Input frequency | 47 ... 63 Hz | Output frequency | | | 0 ... 550 Hz | | 0 ... 240 Hz | Pulse frequency | 4 kHz for higher pulse frequencies up to 16 kHz, see derating data | Power factor λ | 0.7 ... 0.85 | Offset factor cos φ | ≥0.95 | Output voltage, max. as % of input voltage | 95 % | Overload capability | | - Low overload LO
Note: No reduction in base-load current IL for use of overload.
| 1.5 × base-load current IL (i. e. 150 % overload) for 3 s plus 1.1 × base-load current IL (i. e. 110 % overload) for 57 s within a cycle time of 300 s | - High overload HO
Note: No reduction in base-load current IH for use of overload.
| 2 × base-load current IH (i. e. 200 % overload) for 3 s plus 1.5 × base-load current IH (i. e. 150 % overload) for 57 s within a cycle time of 300 s | Electromagnetic compatibility | - Devices without line filter 1)
- Devices with integrated line filter class A according to EN 55011
| Cooling | Air cooling using an integrated fan | Installation altitude | Up to 1000 m (3281 ft) above sea level without derating, > 1000 m (3281 ft) see derating characteristics | Short Circuit Current Rating (SCCR) 2), max. acc. to UL | 100 kA See recommended line-side components – the value depends on the fuses and circuit breakers used | Protection functions | - Undervoltage
- Overvoltage
- Overload
- Ground fault
- Short-circuit
- Stall protection
- Motor blocking protection
- Motor overtemperature
- Converter overtemperature
|
1) Non-filtered devices are designed for operation in IT systems or in conjunction with an RCD. The customer must provide suitable RI suppression equipment to ensure that these devices comply with the limits defined for Category C3 or C2. 2) Applies to industrial control panel installations to NEC article 409 or UL 508A. Line voltage 380 ... 480 V 3 AC | SINAMICS G120C power electronics |
---|
| 6SL3210-1KE11-8..2 | 6SL3210-1KE12-3..2 | 6SL3210-1KE13-2..2 | 6SL3210-1KE14-3..2 |
---|
Output current at 400 V 3 AC | | | | | | | A | 1.8 | 2.3 | 3.2 | 4.3 | | A | 1.7 | 2.2 | 3.1 | 4.1 | | A | 1.3 | 1.7 | 2.2 | 3.1 | | A | 2.6 | 3.4 | 4.4 | 6.2 | Rated power | | | | | | | kW (hp) | 0.55 (0.74) | 0.75 (1.01) | 1.1 (1.48) | 1.5 (2.01) | | kW | 0.37 (0.50) | 0.55 (0.74) | 0.75 (1.01) | 1.1 (1.48) | Rated pulse frequency | kHz | 4 | 4 | 4 | 4 | Efficiency η | % | 97 | 97 | 97 | 97 | Power loss 4) at rated current | kW | 0.034 (0.05) | 0.039 (0.05) | 0.049 (0.007) | 0.062 (0.08) | Cooling air requirement | m3/s (ft3/s) | 0.005 (0.2) | 0.005 (0.2) | 0.005 (0.2) | 0.005 (0.2) | Sound pressure level LpA (1 m (3.28 ft)) | dB | <49 | <49 | <49 | <49 | Rated input current 5) | | | | | | | A | 2.3 | 2.9 | 4.1 | 5.5 | | A | 1.9 | 2.5 | 3.2 | 4.5 | Length of cable to braking resistor, max. | m (ft) | 15 (49.2) | 15 (49.2) | 15 (49.2) | 15 (49.2) | Line supply connection U1/L1, V1/L2, W1/L3 | | Plug-in screw terminals | Plug-in screw terminals | Plug-in screw terminals | Plug-in screw terminals | | mm2 | 1 ... 2.5 (18 ... 14 AWG) | 1 ... 2.5 (18 ... 14 AWG) | 1 ... 2.5 (18 ... 14 AWG) | 1 ... 2.5 (18 ... 14 AWG) | Motor connection U2, V2, W2 | | Plug-in screw terminals | Plug-in screw terminals | Plug-in screw terminals | Plug-in screw terminals | | mm2 | 1 ... 2.5 (18 ... 14 AWG) | 1 ... 2.5 (18 ... 14 AWG) | 1 ... 2.5 (18 ... 14 AWG) | 1 ... 2.5 (18 ... 14 AWG) | Connection for braking resistor R1, R2 | | Plug-in screw terminals | Plug-in screw terminals | Plug-in screw terminals | Plug-in screw terminals | | mm2 | 1 ... 2.5 (18 ... 14 AWG) | 1 ... 2.5 (18 ... 14 AWG) | 1 ... 2.5 (18 ... 14 AWG) | 1 ... 2.5 (18 ... 14 AWG) | PE connection | | On housing with M4 screw | On housing with M4 screw | On housing with M4 screw | On housing with M4 screw | Motor cable length, max. 6) | | | | | | - Without filter, shielded/unshielded
| m (ft) | 50/100 (164/328) | 50/100 (164/328) | 50/100 (164/328) | 50/100 (164/328) | - With integrated filter class A, shielded/unshielded
| m (ft) | 50/100 (164/328) | 50/100 (164/328) | 50/100 (164/328) | 50/100 (164/328) | Dimensions | | | | | | | mm (in) | 73 (2.87) | 73 (2.87) | 73 (2.87) | 73 (2.87) | | mm (in) | 181 (7.13) | 181 (7.13) | 181 (7.13) | 181 (7.13) | | | | | | | | mm (in) | 155 (6.1) (PN version: 178 (7.01)) | 155 (6.1) (PN version: 178 (7.01)) | 155 (6.1) (PN version: 178 (7.01)) | 155 (6.1) (PN version: 178 (7.01)) | | mm (in) | 166/177 (PN version: 189 (7.44)/200 (7.87)) | 166/177 (PN version: 189 (7.44)/200 (7.87)) | 166/177 (PN version: 189 (7.44)/200 (7.87)) | 166/177 (PN version: 189 (7.44)/200 (7.87)) | Frame size | | FSAA | FSAA | FSAA | FSAA | Weight, approx. | | | | | | | kg (lb) | 1.1 (2.43) (PN version: 1.2 (2.65)) | 1.1 (2.43) (PN version: 1.2 (2.65)) | 1.1 (2.43) (PN version: 1.2 (2.65)) | 1.1 (2.43) (PN version: 1.2 (2.65)) | - With integrated filter class A
| kg (lb) | 1.3 (2.87) (PN version: 1.4 (3.09)) | 1.3 (2.87) (PN version: 1.4 (3.09)) | 1.3 (2.87) (PN version: 1.4 (3.09)) | 1.3 (2.87) (PN version: 1.4 (3.09)) |
1) The rated output current Irated can be used up to 100 %; however, without overload. 2) The base-load current IL is based on the duty cycle for low overload (LO). 3) The base-load current IH is based on the duty cycle for high overload (HO). 4) Typical values. You can find more information on the Internet at https://support.industry.siemens.com/cs/document/94059311 5) The rated input currents are valid for an input voltage of 400 V 3 AC and a line impedance corresponding to uK = 1 % (without line reactor). The rated input current based on IL is stamped on the inverter rating plate. In the particular application, the input current depends on the motor load and line impedance. The input current is reduced when using a line reactor. 6) The maximum motor cable lengths are valid for an input voltage of 400 V 3 AC and operation with a 4 kHz pulse frequency. When an inverter with an integrated line filter class A is used to comply with the limits of EN 61800‑3 Category C2 for line-conducted interference emissions, the maximum permissible motor cable length is 25 m (82 ft) (shielded). Line voltage 380 ... 480 V 3 AC | SINAMICS G120C power electronics |
---|
| 6SL3210-1KE15-8..2 | 6SL3210-1KE17-5..1 | 6SL3210-1KE18-8..1 | 6SL3210-1KE21-3..1 |
---|
Output current at 400 V 3 AC | | | | | | | A | 5.8 | 7.5 | 9 | 13 | | A | 5.6 | 7.3 | 8.8 | 12.5 | | A | 4.1 | 5.6 | 7.3 | 8.8 | | A | 8.2 | 11.2 | 14.6 | 17.6 | Rated power | | | | | | | kW | 2.2 (2.95) | 3 (4.02) | 4 (5.36) | 5.5 (7.38) | | kW | 1.5 (2.01) | 2.2 (2.95) | 3 (4.02) | 4 (5.36) | Rated pulse frequency | kHz | 4 | 4 | 4 | 4 | Efficiency η | % | 97 | 97 | 97 | 97 | Power loss 4) at rated current | kW | 0.073 | 0.099 | 0.122 | 0.174 | Cooling air requirement | m3/s (ft3/s) | 0.005 (0.2) | 0.005 (0.2) | 0.005 (0.2) | 0.009 (0.32) | Sound pressure level LpA (1 m (3.28 ft)) | dB | <49 | <52 | <52 | <63 | Rated input current 5) | | | | | | | A | 7.4 | 9.5 | 11.4 | 16.5 | | A | 6 | 8.2 | 10.6 | 12.8 | Length of cable to braking resistor, max. | m (ft) | 15 (49.2) | 15 (49.2) | 15 (49.2) | 15 (49.2) | Line supply connection U1/L1, V1/L2, W1/L3 | | Plug-in screw terminals | Plug-in screw terminals | Plug-in screw terminals | Plug-in screw terminals | | mm2 | 1 ... 2.5 (18 ... 14 AWG) | 1 ... 2.5 (18 ... 14 AWG) | 1 ... 2.5 (18 ... 14 AWG) | 4 .. 6 (12 ... 10 AWG) | Motor connection U2, V2, W2 | | Plug-in screw terminals | Plug-in screw terminals | Plug-in screw terminals | Plug-in screw terminals | | mm2 | 1 ... 2.5 (18 ... 14 AWG) | 1 ... 2.5 (18 ... 14 AWG) | 1 ... 2.5 (18 ... 14 AWG) | 4 ... 6 (12 ... 10 AWG) | Connection for braking resistor R1, R2 | | Plug-in screw terminals | Plug-in screw terminals | Plug-in screw terminals | Plug-in screw terminals | | mm2 | 1 ... 2.5 (18 ... 14 AWG) | 1 ... 2.5 (18 ... 14 AWG) | 1 ... 2.5 (18 ... 14 AWG) | 4 ... 6 (12 ... 10 AWG) | PE connection | | On housing with M4 screw | On housing with M4 screw | On housing with M4 screw | On housing with M4 screw | Motor cable length, max. 6) | | | | | | - Without filter, shielded/unshielded
| m (ft) | 50/100 (164/328) | 150/150 (492/492) | 150/150 (492/492) | 150/150 (492/492) | - With integrated filter class A, shielded/unshielded
| m (ft) | 50/100 (164/328) | 50/100 (164/328) | 50/100 (164/328) | 50/100 (164/328) | Dimensions | | | | | | | mm (in) | 73 (2.87) | 73 (2.87) | 73 (2.87) | 100 (3.94) | | mm (in) | 181 (7.13) | 196 (7.72) | 196 (7.72) | 196 (7.72) | | | | | | | | mm (in) | 155 (6.1) (PN version: 178 (7.01)) | 203 (7.99) (PN version: 226 (8.90)) | 203 (7.99) (PN version: 226 (8.90)) | 203 (7.99) (PN version: 226 (8.90)) | | mm (in) | 166 (6.54)/177 (6.97) (PN version: 189 (7.44)/200 (7.87)) | 214 (8.43)/125 (4.92)(PN version: 237 (9.33)/248 (9.76)) | 214 (8.43)/125 (4.92)(PN version: 237 (9.33)/248 (9.76)) | 214 (8.43)/125 (4.92)(PN version: 237 (9.33)/248 (9.76)) | Frame size | | FSAA | FSA | FSA | FSB | Weight, approx. | | | | | | | kg (lb) | 1.1 (2.43) (PN version: 1.2 (2.65)) | 1.7 (3.75) | 1.7 (3.75) | 2.3 (5.07) | - With integrated filter class A
| kg (lb) | 1.3 (2.87) (PN version: 1.4 (3.09)) | 1.9 (4.19) | 1.9 (4.19) | 2.5 (5.51) |
1) The rated output current Irated can be used up to 100 %; however, without overload. 2) The base-load current IL is based on the duty cycle for low overload (LO). 3) The base-load current IH is based on the duty cycle for high overload (HO). 4) Typical values. You can find more information on the Internet at https://support.industry.siemens.com/cs/document/94059311 5) The rated input currents are valid for an input voltage of 400 V 3 AC and a line impedance corresponding to uK = 1 % (without line reactor). The rated input current based on IL is stamped on the inverter rating plate. In the particular application, the input current depends on the motor load and line impedance. The input current is reduced when using a line reactor. 6) The maximum motor cable lengths are valid for an input voltage of 400 V 3 AC and operation with a 4 kHz pulse frequency. When an inverter with an integrated line filter class A is used to comply with the limits of EN 61800‑3 Category C2 for line-conducted interference emissions, the maximum permissible motor cable length is 25 m (82 ft) (shielded) as standard - for frame sizes FSA and FSB with low-capacitance CY cable (shielded) it is 50 m (164 ft). Line voltage 380 ... 480 V 3 AC | SINAMICS G120C power electronics |
---|
| 6SL3210-1KE21-7..1 | 6SL3210-1KE22-6..1 | 6SL3210-1KE23-2..1 | 6SL3210-1KE23-8..1 |
---|
Output current at 400 V 3 AC | | | | | | | A | 17 | 26 | 32 | 38 | | A | 16.5 | 25 | 31 | 37 | | A | 12.5 | 16.5 | 25 | 31 | | A | 25 | 33 | 50 | 62 | Rated power | | | | | | | kW | 7.5 (10.1) | 11 (14.8) | 15 (20.1) | 18.5 (24.8) | | kW | 5.5 (7.38) | 7.5 (10.1) | 11 (14.8) | 15 (20.1) | Rated pulse frequency | kHz | 4 | 4 | 4 | 4 | Efficiency η | % | 97 | 97 | 97 | 97 | Power loss 4) at rated current | kW | 0.236 | 0.301 | 0.373 | 0.45 (15.9) | Cooling air requirement | m3/s (ft3/s) | 0.009 (0.32) | 0.018 (0.64) | 0.018 (0.64) | 0.018 (0.64) | Sound pressure level LpA (1 m (3.28 ft)) | dB | <63 | <66 | <66 | <66 | Rated input current 5) | | | | | | | A | 21.5 | 33 | 40.6 | 48.2 | | A | 18.2 | 24.1 | 36.4 | 45.2 | Length of cable to braking resistor, max. | m (ft) | 15 (49.2) | 15 (49.2) | 15 (49.2) | 15 (49.2) | Line supply connection U1/L1, V1/L2, W1/L3 | | Plug-in screw terminals | Plug-in screw terminals | Plug-in screw terminals | Plug-in screw terminals | | mm2 | 4 ... 6 (12 ... 10 AWG) | 6 ... 16 (10 ... 5 AWG) | 10 ... 16 (7 ... 5 AWG) | 10 ... 16 (7 ... 5 AWG) | Motor connection U2, V2, W2 | | Plug-in screw terminals | Plug-in screw terminals | Plug-in screw terminals | Plug-in screw terminals | | mm2 | 4 ... 6 (12 ... 10 AWG) | 6 ... 16 (10 ... 5 AWG) | 10 ... 16 (7 ... 5 AWG) | 10 ... 16 (7 ... 5 AWG) | Connection for braking resistor R1, R2 | | Plug-in screw terminals | Plug-in screw terminals | Plug-in screw terminals | Plug-in screw terminals | | mm2 | 4 ... 6 (12 ... 10 AWG) | 6 ... 16 (10 ... 5 AWG) | 10 ... 16 (7 ... 5 AWG) | 10 ... 16 (7 ... 5 AWG) | PE connection | | On housing with M4 screw | On housing with M4 screw | On housing with M4 screw | On housing with M4 screw | Motor cable length, max. 6) | | | | | | - Without filter, shielded/unshielded
| m (ft) | 150/150 (492/492) | 150/150 (492/492) | 150/150 (492/492) | 150/150 (492/492) | - With integrated filter class A, shielded/unshielded
| m (ft) | 50/100 (164/328) | 50/100 (164/328) | 50/100 (164/328) | 50/100 (164/328) | Dimensions | | | | | | | mm (in) | 100 (3.94) | 140 (5.51) | 140 (5.51) | 140 (5.51) | | mm (in) | 196 (7.72) | 295 (11.6) | 295 (11.6) | 295 (11.6) | | | | | | | | mm (in) | 203 (7.99) (PN version: 226 (8.90)) | 203 (7.99) (PN version: 226 (8.90)) | 203 (7.99) (PN version: 226 (8.90)) | 203 (7.99) (PN version: 226 (8.90)) | | mm (in) | 214 (8.43)/125 (4.92)(PN version: 237 (9.33)/248 (9.76)) | 214 (8.43)/125 (4.92)(PN version: 237 (9.33)/248 (9.76)) | 214 (8.43)/125 (4.92)(PN version: 237 (9.33)/248 (9.76)) | 214 (8.43)/125 (4.92)(PN version: 237 (9.33)/248 (9.76)) | Frame size | | FSB | FSC | FSC | FSC | Weight, approx. | | | | | | | kg (lb) | 2.3 (5.07) | 4.4 (9.70) | 4.4 (9.70) | 4.4 (9.70) | - With integrated filter class A
| kg (lb) | 2.5 (5.51) | 4.7 (10.4) | 4.7 (10.4) | 4.7 (10.4) |
1) The rated output current Irated can be used up to 100 %; however, without overload. 2) The base-load current IL is based on the duty cycle for low overload (LO). 3) The base-load current IH is based on the duty cycle for high overload (HO). 4) Typical values. You can find more information on the Internet at https://support.industry.siemens.com/cs/document/94059311 5) The rated input currents are valid for an input voltage of 400 V 3 AC and a line impedance corresponding to uK = 1 % (without line reactor). The rated input current based on IL is stamped on the inverter rating plate. In the particular application, the input current depends on the motor load and line impedance. The input current is reduced when using a line reactor. 6) The maximum motor cable lengths are valid for an input voltage of 400 V 3 AC and operation with a 4 kHz pulse frequency. When an inverter with an integrated line filter class A is used to comply with the limits of EN 61800-3 Category C2 for line-conducted interference emission, the maximum permissible motor cable length is 25 m (82 ft) (shielded) as standard - with low-capacitance CY cable for frame size FSB 50 m (164 ft) (shielded), for FSC 100 m (328 ft) (shielded). Line voltage 380 ... 480 V 3 AC | SINAMICS G120C power electronics |
---|
| 6SL3210-1KE24-4.F1 | 6SL3210-1KE26-0.F1 | 6SL3210-1KE27-0.F1 | 6SL3210-1KE28-4.F1 |
---|
Output current at 400 V 3 AC | | | | | | | A | ??? | ??? | ??? | ??? | | A | 43 | 58 | 68 | 82.5 | | A | 37 | 43 | 58 | 68 | | A | ??? | ??? | ??? | ??? | Rated power | | | | | | | kW | 22 (29.5) | 30 (40.2) | 37 (49.6) | 45 (60.3) | | kW | 18.5 (24.8) | 22 (29.5) | 30 (40.2) | 37 (49.6) | Rated pulse frequency | kHz | 4 | 4 | 4 | 4 | Efficiency η | % | ??? | ??? | ??? | ??? | Power loss 4) at rated current | kW | ??? | ??? | ??? | ??? | Cooling air requirement | m3/s (ft3/s) | 0.055 (1.94) | 0.055 (1.94) | 0.055 (1.94) | 0.055 (1.94) | Sound pressure level LpA (1 m (3.28 ft)) | dB | ??? | ??? | ??? | ??? | Rated input current 5) | | | | | | | A | 41 | 53 | 64 | 76 | | A | 39 | 44 | 61 | 69 | Length of cable to braking resistor, max. | m (ft) | ??? | ??? | ??? | ??? | Line supply connection U1/L1, V1/L2, W1/L3 | | Plug-in screw terminals | Plug-in screw terminals | Plug-in screw terminals | Plug-in screw terminals | | mm2 | 10 ... 35 (20 ... 10 AWG) | 10 ... 35 (20 ... 10 AWG) | 10 ... 35 (20 ... 10 AWG) | 10 ... 35 (20 ... 10 AWG) | Motor connection U2, V2, W2 | | Plug-in screw terminals | Plug-in screw terminals | Plug-in screw terminals | Plug-in screw terminals | | mm2 | 10 ... 35 (20 ... 10 AWG) | 10 ... 35 (20 ... 10 AWG) | 10 ... 35 (20 ... 10 AWG) | 10 ... 35 (20 ... 10 AWG) | Connection for braking resistor R1, R2 | | Plug-in screw terminals | Plug-in screw terminals | Plug-in screw terminals | Plug-in screw terminals | | mm2 | 10 ... 35 (20 ... 10 AWG) | 10 ... 35 (20 ... 10 AWG) | 10 ... 35 (20 ... 10 AWG) | 10 ... 35 (20 ... 10 AWG) | PE connection | | ??? | ??? | ??? | ??? | Motor cable length, max. 6) | | | | | | - Without filter, shielded/unshielded
| m (ft) | 200/300 (656/984) | 200/300 (656/984) | 200/300 (656/984) | 200/300 (656/984) | - With integrated filter class A, shielded/unshielded
| m (ft) | ??? | ??? | ??? | ??? | Dimensions | | | | | | | mm (in) | 200 (7.87) | 200 (7.87) | 200 (7.87) | 200 (7.87) | | mm (in) | 472 (18.6) | 472 (18.6) | 472 (18.6) | 472 (18.6) | | | | | | | | mm (in) | 237 (9.33) | 237 (9.33) | 237 (9.33) | 237 (9.33) | | mm (in) | 248/259 | 248/259 | 248/259 | 248/259 | Frame size | | FSD | FSD | FSD | FSD | Weight, approx. | | | | | | | kg (lb) | 17 (37.5) | 17 (37.5) | 18 (39.7) | 18 (39.7) | - With integrated filter class A
| kg (lb) | 19 (41.9) | 19 (41.9) | 20 (44.1) | 20 (44.1) |
1) The rated output current Irated can be used up to 100 %; however, without overload. 2) The base-load current IL is based on the duty cycle for low overload (LO). 3) The base-load current IH is based on the duty cycle for high overload (HO). 4) Typical values. You can find more information on the Internet at https://support.industry.siemens.com/cs/document/94059311 5) The rated input currents are valid for an input voltage of 400 V 3 AC and a line impedance corresponding to uK = 1 % (without line reactor). The rated input current based on IL is stamped on the inverter rating plate. In the particular application, the input current depends on the motor load and line impedance. The input current is reduced when using a line reactor. 6) The maximum motor cable lengths are valid for an input voltage of 400 V 3 AC and operation with a 4 kHz pulse frequency. When an inverter with an integrated line filter class A is used to comply with the limits of EN 61800-3 Category C2 for line-conducted interference emission, the maximum permissible motor cable length is 25 m (82 ft) (shielded) as standard - with low-capacitance CY cable for frame size FSB 50 m (164 ft) (shielded), for FSC 100 m (328 ft) (shielded). Line voltage 380 ... 480 V 3 AC | SINAMICS G120C power electronics |
---|
| 6SL3210-1KE31-1.F1 | 6SL3210-1KE31-4.F1 | 6SL3210-1KE31-7.F1 | 6SL3210-1KE32-1.F1 | 6SL3210-1KE32-4.F1 |
---|
Output current at 400 V 3 AC | | | | | | | | A | ??? | ??? | ??? | ??? | ??? | | A | 103 | 136 | 164 | 201 | 237 | | A | 83 | 103 | 136 | 164 | 201 | | A | ??? | ??? | ??? | ??? | ??? | Rated power | | | | | | | | kW | 55 (73.8) | 75 (101) | 90 (121) | 110 (148) | 132 (177) | | kW | 45 (60.3) | 55 (73.8) | 75 (101) | 90 (121) | 110 (148) | Rated pulse frequency | kHz | 4 | 4 | 4 | 4 | 4 | Efficiency η | % | ??? | ??? | ??? | ??? | ??? | Power loss 4) at rated current | kW | ??? | ??? | ??? | ??? | ??? | Cooling air requirement | m3/s (ft3/s) | 0.083 (2.93) | 0.153 (5.40) | 0.153 (5.40) | 0.153 (5.40) | 0.153 (5.40) | Sound pressure level LpA (1 m (3.28 ft)) | dB | ??? | ??? | ??? | ??? | ??? | Rated input current 5) | | | | | | | | A | 96 | 134 | 156 | 187 | 221 | | A | 85 | 112 | 144 | 169 | 207 | Length of cable to braking resistor, max. | m (ft) | ??? | ??? | ??? | ??? | ??? | Line supply connection U1/L1, V1/L2, W1/L3 | | Plug-in screw terminals | Plug-in screw terminals | Plug-in screw terminals | Plug-in screw terminals | Plug-in screw terminals | | mm2 | 25 ... 70 (6 ... 3/0 AWG) | 35 ... 2×120 (1 ... 2×4/0 AWG) | 35 ... 2×120 (1 ... 2×4/0 AWG) | 35 ... 2×120 (1 ... 2×4/0 AWG) | 35 ... 2×120 (1 ... 2×4/0 AWG) | Motor connection U2, V2, W2 | | Plug-in screw terminals | Plug-in screw terminals | Plug-in screw terminals | Plug-in screw terminals | Plug-in screw terminals | | mm2 | 25 ... 70 (6 ... 3/0 AWG) | 35 ... 2×120 (1 ... 2×4/0 AWG) | 35 ... 2×120 (1 ... 2×4/0 AWG) | 35 ... 2×120 (1 ... 2×4/0 AWG) | 35 ... 2×120 (1 ... 2×4/0 AWG) | Connection for braking resistor R1, R2 | | Plug-in screw terminals | Plug-in screw terminals | Plug-in screw terminals | Plug-in screw terminals | Plug-in screw terminals | | mm2 | 25 ... 70 (6 ... 3/0 AWG) | 35 ... 2×120 (1 ... 2×4/0 AWG) | 35 ... 2×120 (1 ... 2×4/0 AWG) | 35 ... 2×120 (1 ... 2×4/0 AWG) | 35 ... 2×120 (1 ... 2×4/0 AWG) | PE connection | | ??? | ??? | ??? | ??? | ??? | Motor cable length, max. 6) | | | | | | | - Without filter, shielded/unshielded
| m (ft) | 200/300 (656/984) | 300/450 (984/1476) | 300/450 (984/1476) | 300/450 (984/1476) | 300/450 (984/1476) | - With integrated filter class A, shielded/unshielded
| m (ft) | ??? | ??? | ??? | ??? | ??? | Dimensions | | | | | | | | mm (in) | 275 (10.8) | 305 (12.01) | 305 (12.01) | 305 (12.01) | 305 (12.01) | | mm (in) | 551 (21.7) | 708 (27.9) | 708 (27.9) | 708 (27.9) | 708 (27.9) | | | | | | | | | mm (in) | 237 (9.33) | 357 (14.1) | 357 (14.1) | 357 (14.1) | 357 (14.1) | | mm (in) | 248/259 | 368/379 | 368/379 | 368/379 | 368/379 | Frame size | | FSE | FSF | FSF | FSF | FSF | Weight, approx. | | | | | | | | kg (lb) | 27 (59.5) | 59 (130) | 59 (130) | 64 (141) | 64 (141) | - With integrated filter class A
| kg (lb) | 29 (63.9) | 62 (137) | 62 (137) | 66 (146) | 66 (146) |
1) The rated output current Irated can be used up to 100 %; however, without overload. 2) The base-load current IL is based on the duty cycle for low overload (LO). 3) The base-load current IH is based on the duty cycle for high overload (HO). 4) Typical values. You can find more information on the Internet at https://support.industry.siemens.com/cs/document/94059311 5) The rated input currents are valid for an input voltage of 400 V 3 AC and a line impedance corresponding to uK = 1 % (without line reactor). The rated input current based on IL is stamped on the inverter rating plate. In the particular application, the input current depends on the motor load and line impedance. The input current is reduced when using a line reactor. 6) The maximum motor cable lengths are valid for an input voltage of 400 V 3 AC and operation with a 4 kHz pulse frequency. When an inverter with an integrated line filter class A is used to comply with the limits of EN 61800-3 Category C2 for line-conducted interference emission, the maximum permissible motor cable length is 25 m (82 ft) (shielded) as standard - with low-capacitance CY cable for frame size FSB 50 m (164 ft) (shielded), for FSC 100 m (328 ft) (shielded).
|
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Àðìàòóðà DENDOR
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Äàò÷èêè è èçìåðèòåëè
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ðåãóëÿòîðû è ðåãèñòðàòîðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ïíåâìàòè÷åñêîå îáîðóäîâàíèå
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Êðàíû è Êëàïàíû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Èçìåðèòåëüíûå ïðèáîðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ñèñòåìû áåñïðîâîäíîãî óïðàâëåíèÿ «óìíûé äîì»
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Áåñêîíòàêòíûå âûêëþ÷àòåëè Êîíå÷íûå âûêëþ÷àòåëè Îïòè÷åñêèå äàò÷èêè Ýíêîäåðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Óñòàíîâêà óìÿã÷åíèÿ
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Óñòàíîâêà îáåçæåëåçèâàíèÿ
|