Unless explicitly specified otherwise, the following technical specifications are valid for all SINAMICS G120C compact inverters.
General technical specifications
Mechanical specifications
Vibratory load
Transport acc. to EN 60721?3?2 1)
Class 1M2
Operation acc. to EN 60721?3?3
Class 3M1
Shock load
Transport acc. to EN 60721?3?2 1)
Class 1M2
Operation acc. to EN 60721?3?3
Class 3M2
Degree of protection
IP20/ UL open type
Permissible mounting position
Vertical wall mounting
Ambient conditions
Protection class
According to EN 61800?5?1
Class III (PELV1)
Touch protection
According to EN 61800?5?1
Class I (with protective conductor system)
Humidity, max.
95 % at 40 °C (104 °F), condensation and icing not permissible
Ambient temperature
Storage 1) acc. to EN 60068?2?1
-40 ... +70 °C (-40 ... +158 °F)
Transport 1) acc. to EN 60068?2?1
-40 ... +70 °C (-40 ... +158 °F)
Operation acc. to EN 60068?2?2
-10 ... +40 °C (14 ... 104 °F) without derating
>40 ... 60 °C (104 ... 140 °F) see derating characteristics
Environmental class in operation
Harmful chemical substances
Class 3C2 to EN 60721?3?3
Organic/biological pollutants
Class 3B1 to EN 60721?3?3
Degree of pollution
2 acc. to EN 61800
Standards
Compliance with standards
CE, UL, cUL, C-Tick (RCM)
Fail-safe certification
Function: Safe Torque Off (STO)
According to IEC 61508
SIL 2
According to EN ISO 13849?1
PL d and Category 3
CE marking, according to
EMC Directive 2004/108/EC
Low-Voltage Directive 2006/95/EC
EMC Directive 2)
According to EN 61800?3
Interference immunity
The SINAMICS G120C compact inverters are tested according to the interference immunity requirements for environments according to Category C3.
Interference emission
Frame sizes FSAA to FSC without integrated line filter
3)
Frame sizes FSAA to FSC with integrated line filter class A
The inverters comply with the limit values according to Category C3.
The inverters comply with the limit values for conducted interference and field-conducted interference emissions according to Category C2. 4) 5)
Note:
The EMC product standard EN 61800-3 does not apply directly to a frequency inverter but to a PDS (Power Drive System), which comprises the complete circuitry, motor and cables in addition to the inverter. The frequency inverters on their own do not generally require identification according to the EMC Directive.
1) In transport packaging.
2) For further general information, see also chapter SINAMICS G120, section Technical specifications, Compliance with standards.
3) Non-filtered devices are designed for operation in IT systems or in conjunction with an RCD. The customer must provide suitable RI suppression equipment to ensure that these devices comply with the limits defined for Category C3 or C2.
4) Max. permissible motor cable length of 25 m (82 ft) (shielded) as standard - with low-capacitance CY cable for frame sizes FSA and FSB 50 m (164 ft) (shielded), for FSC 100 m (328 ft) (shielded).
5) SINAMICS G120C compact inverters, frame size FSB, with PROFINET interface (article no.: 6SL3210-1KE21-.AF1) additionally require a line reactor.
SINAMICS G120C compact inverter
USS, Modbus RTU version
PROFIBUS DP version
PROFINET, EtherNet/IP version
6SL3210-1KE..-..B1 6SL3210-1KE..-..B2
6SL3210-1KE..-..P1 6SL3210-1KE..-..P2
6SL3210-1KE..-..F1 6SL3210-1KE..-..F2
Integrated bus interface
Fieldbus protocols
USS
Modbus RTU (switchable using a parameter)
PROFIBUS DP
PROFINET
EtherNet/IP
ODVA AC/DC drive
SINAMICS profiles
Profiles
–
PROFIdrive Profile V4.1
PROFIsafe
PROFIdrive Profile V4.1
PROFIsafe
PROFIenergy
Hardware
Plug-in terminal, insulated, USS: max. 187.5 kbaud Modbus RTU: 19.2 kBaud, Bus terminating resistor that can be switched in
9-pin SUB-D socket, insulated, max. 12 Mbit/s Slave address can be set using DIP switches
2 ? RJ45, max. 100 Mbit/s (full duplex), device name can be stored on the device
Optically isolated; Free reference potential (own potential group) NPN/PNP logic can be selected using the wiring
Switching level: 0 > 1
11 V
Switching level: 1 > 0
5 V
Input current, max.
15 mA
Digital inputs, fail-safe
1
When using the standard digital inputs (DI4+DI5) Safety function: Safe Torque Off (STO)
Digital outputs
1 relay changeover contact 30 V DC, 0.5 A (ohmic load)
1 transistor 30 V DC, 0.5 A (ohmic load)
Analog inputs
1 analog input
Differential input Switchable between voltage (-10 ... +10 V) and current (0/4 ... 20 mA) using a DIP switch 10?bit resolution Can be used as additional digital input
Analog inputs are protected in a voltage range of ± 30 V and have a common-mode voltage in the ± 15 V range.
Switching threshold: 0 > 1
4 V
Switching threshold: 1 > 0
1.6 V
Analog outputs
1 analog output
Non-isolated output Switchable between voltage (0 ... 10 V) and current (0/4 ... 20 mA) using a parameter Voltage mode: 10 V, min. burden 10 k? Current mode: 20 mA, max. burden 500 ?
The analog outputs have short circuit protection
PTC/KTY interface
1 motor temperature sensor input
Connectable sensors PTC, KTY and bimetal, Accuracy ±5 °C (41 °F)
Voltage supply for the integrated Control Unit
24 V DC via the Power Module or by connecting to an external 20.4 ... 28.8 V DC power supply
Typical input current: 500 mA at 24 V DC
Tool interfaces
Memory card
Optional SINAMICS SD card
Operator panels
Optional Basic Operator Panel BOP?2 or Intelligent Operator Panel IOP
General technical specifications of the power electronics
System operating voltage
380 ... 480 V 3 AC +10 % -20 %
Grid requirement Short-circuit power RSC
No restriction
Input frequency
47 ... 63 Hz
Output frequency
Control mode V/f
0 ... 550 Hz
Control type Vector
0 ... 240 Hz
Pulse frequency
4 kHz for higher pulse frequencies up to 16 kHz, see derating data
Power factor ?
0.7 ... 0.85
Offset factor cos ?
?0.95
Output voltage, max.
as % of input voltage
95 %
Overload capability
Low overload LO Note: No reduction in base-load current IL for use of overload.
1.5 ? base-load current IL (i. e. 150 % overload) for 3 s plus 1.1 ? base-load current IL (i. e. 110 % overload) for 57 s within a cycle time of 300 s
High overload HO Note: No reduction in base-load current IH for use of overload.
2 ? base-load current IH (i. e. 200 % overload) for 3 s plus 1.5 ? base-load current IH (i. e. 150 % overload) for 57 s within a cycle time of 300 s
Electromagnetic compatibility
Devices without line filter 1)
Devices with integrated line filter class A according to EN 55011
Cooling
Air cooling using an integrated fan
Installation altitude
Up to 1000 m (3281 ft) above sea level without derating, > 1000 m (3281 ft) see derating characteristics
Short Circuit Current Rating (SCCR) 2), max. acc. to UL
100 kA see recommended line-side components – the value depends on the fuses and circuit breakers used
Protection functions
Undervoltage
Overvoltage
Overload
Ground fault
Short-circuit
Stall protection
Motor blocking protection
Motor overtemperature
Inverter overtemperature
1) Non-filtered devices are designed for operation in IT systems or in conjunction with an RCD. The customer must provide suitable RI suppression equipment to ensure that these devices comply with the limits defined for Category C3 or C2.
2) Applies to industrial control panel installations to NEC article 409 or UL 508A.
Line voltage 380 ... 480 V 3 AC
SINAMICS G120C power electronics
6SL3210-1KE11-8..2
6SL3210-1KE12-3..2
6SL3210-1KE13-2..2
6SL3210-1KE14-3..2
Output current
at 400 V 3 AC
Rated current Irated 1)
A
1.8
2.3
3.2
4.3
Base-load current IL 2)
A
1.7
2.2
3.1
4.1
Base-load current IH 3)
A
1.3
1.7
2.2
3.1
Maximum current Imax
A
2.6
3.4
4.4
6.2
Rated power
Based on IL
kW (hp)
0.55 (0.75)
0.75 (1)
1.1 (1.5)
1.5 (2)
Based on IH
kW (hp)
0.37 (0.5)
0.55 (0.75)
0.75 (1)
1.1 (1.5)
Rated pulse frequency
kHz
4
4
4
4
Efficiency ?
%
97
97
97
97
Power loss 4)
At rated current
kW
0.034
0.039
0.049
0.062
Cooling air requirement
m3/s (ft3/s)
0.005 (0.18)
0.005 (0.18)
0.005 (0.18)
0.005 (0.18)
Sound pressure level LpA (1 m)
dB
<49
<49
<49
<49
Rated input current 5)
Based on IL
A
2.3
2.9
4.1
5.5
Based on IH
A
1.9
2.5
3.2
4.5
Length of cable to braking resistor, max.
m (ft)
15 (49)
15 (49)
15 (49)
15 (49)
Line supply connection
U1/L1, V1/L2, W1/L3
Plug-in screw-type terminals
Plug-in screw-type terminals
Plug-in screw-type terminals
Plug-in screw-type terminals
Conductor cross-section
mm2
1 ... 2.5 (16 ... 14 AWG)
1 ... 2.5 (16 ... 14 AWG)
1 ... 2.5 (16 ... 14 AWG)
1 ... 2.5 (16 ... 14 AWG)
Motor connection
U2, V2, W2
Plug-in screw-type terminals
Plug-in screw-type terminals
Plug-in screw-type terminals
Plug-in screw-type terminals
Conductor cross-section
mm2
1 ... 2.5 (16 ... 14 AWG)
1 ... 2.5 (16 ... 14 AWG)
1 ... 2.5 (16 ... 14 AWG)
1 ... 2.5 (16 ... 14 AWG)
Connection for braking resistor
R1, R2
Plug-in screw-type terminals
Plug-in screw-type terminals
Plug-in screw-type terminals
Plug-in screw-type terminals
Conductor cross-section
mm2
1 ... 2.5 (16 ... 14 AWG)
1 ... 2.5 (16 ... 14 AWG)
1 ... 2.5 (16 ... 14 AWG)
1 ... 2.5 (16 ... 14 AWG)
PE connection
On housing with M4 screw
On housing with M4 screw
On housing with M4 screw
On housing with M4 screw
Motor cable length, max. 6)
Without filter, shielded/unshielded
m (ft)
50/100 (164/328)
50/100 (164/328)
50/100 (164/328)
50/100 (164/328)
With integrated filter class A, shielded/unshielded
m (ft)
50/100 (164/328)
50/100 (164/328)
50/100 (164/328)
50/100 (164/328)
Dimensions
Width
mm (in)
73 (2.87)
73 (2.87)
73 (2.87)
73 (2.87)
Height
mm (in)
173 (6.81)
173 (6.81)
173 (6.81)
173 (6.81)
Depth
Without operator panel
mm (in)
155 (6.1) (PN version: 177.4 (6.98))
155 (6.1) (PN version: 177.4 (6.98))
155 (6.1) (PN version: 177.4 (6.98))
155 (6.1) (PN version: 177.4 (6.98))
With operator panel
mm (in)
176 (6.93) (PN version: 198.4 (7.81))
176 (6.93) (PN version: 198.4 (7.81))
176 (6.93) (PN version: 198.4 (7.81))
176 (6.93) (PN version: 198.4 (7.81))
Frame size
FSAA
FSAA
FSAA
FSAA
Weight, approx.
Without filter
kg (lb)
1.1 (2.43) (PN version: 1.2 (2.65))
1.1 (2.43) (PN version: 1.2 (2.65))
1.1 (2.43) (PN version: 1.2 (2.65))
1.1 (2.43) (PN version: 1.2 (2.65))
With integrated filter class A
kg (lb)
1.3 (2.87) (PN version: 1.4 (3.09))
1.3 (2.87) (PN version: 1.4 (3.09))
1.3 (2.87) (PN version: 1.4 (3.09))
1.3 (2.87) (PN version: 1.4 (3.09))
1) The rated output current Irated can be used up to 100 %; however, without overload.
2) The base-load current IL is based on the duty cycle for low overload (LO).
3) The base-load current IH is based on the duty cycle for high overload (HO).
5) The rated input currents are valid for an input voltage of 400 V 3 AC and a line impedance corresponding to uK = 1 % (without line reactor). The rated input current based on IL is stamped on the inverter rating plate. In the particular application, the input current depends on the motor load and line impedance. The input current is reduced when using a line reactor.
6) The maximum motor cable lengths are valid for an input voltage of 400 V 3 AC and operation with a 4 kHz pulse frequency. When an inverter with an integrated line filter class A is used to comply with the limits of EN 61800?3 Category C2 for line-conducted interference emissions, the maximum permissible motor cable length is 25 m (82 ft) (shielded).
Line voltage 380 ... 480 V 3 AC
SINAMICS G120C power electronics
6SL3210-1KE15-8..2
6SL3210-1KE17-5..1
6SL3210-1KE18-8..1
6SL3210-1KE21-3..1
Output current
at 400 V 3 AC
Rated current Irated 1)
A
5.8
7.5
9
13
Base-load current IL 2)
A
5.6
7.3
8.8
12.5
Base-load current IH 3)
A
4.1
5.6
7.3
8.8
Maximum current Imax
A
8.2
11.2
14.6
17.6
Rated power
Based on IL
kW (hp)
2.2 (3)
3 (4)
4 (5)
5.5 (7.5)
Based on IH
kW (hp)
1.5 (2)
2.2 (3)
3 (4)
4 (5)
Rated pulse frequency
kHz
4
4
4
4
Efficiency ?
%
97
97
97
97
Power loss 4)
At rated current
kW
0.073
0.105
0.13
0.177
Cooling air requirement
m3/s (ft3/s)
0.005 (0.18)
0.005 (0.18)
0.005 (0.18)
0.009 (0.32)
Sound pressure level LpA (1 m)
dB
<49
<52
<52
<63
Rated input current 5)
Based on IL
A
7.4
9.5
11.4
16.5
Based on IH
A
6
8.2
10.6
12.8
Length of cable to braking resistor, max.
m (ft)
15 (49)
15 (49)
15 (49)
15 (49)
Line supply connection
U1/L1, V1/L2, W1/L3
Plug-in screw-type terminals
Plug-in screw-type terminals
Plug-in screw-type terminals
Plug-in screw-type terminals
Conductor cross-section
mm2
1 ... 2.5 (16 ... 14 AWG)
1 ... 2.5 (16 ... 14 AWG)
1 ... 2.5 (16 ... 14 AWG)
4 .. 6 (12 ... 10 AWG)
Motor connection
U2, V2, W2
Plug-in screw-type terminals
Plug-in screw-type terminals
Plug-in screw-type terminals
Plug-in screw-type terminals
Conductor cross-section
mm2
1 ... 2.5 (16 ... 14 AWG)
1 ... 2.5 (16 ... 14 AWG)
1 ... 2.5 (16 ... 14 AWG)
4 ... 6 (12 ... 10 AWG)
Connection for braking resistor
R1, R2
Plug-in screw-type terminals
Plug-in screw-type terminals
Plug-in screw-type terminals
Plug-in screw-type terminals
Conductor cross-section
mm2
1 ... 2.5 (16 ... 14 AWG)
1 ... 2.5 (16 ... 14 AWG)
1 ... 2.5 (16 ... 14 AWG)
4 ... 6 (12 ... 10 AWG)
PE connection
On housing with M4 screw
On housing with M4 screw
On housing with M4 screw
On housing with M4 screw
Motor cable length, max. 6)
Without filter, shielded/unshielded
m (ft)
50/100 (164/328)
150/150 (492/492)
150/150 (492/492)
150/150 (492/492)
With integrated filter class A, shielded/unshielded
m (ft)
50/100 (164/328)
50/100 (164/328)
50/100 (164/328)
50/100 (164/328)
Dimensions
Width
mm (in)
73 (2.87)
73 (2.87)
73 (2.87)
100 (3.94)
Height
mm (in)
173 (6.81)
196 (7.72)
196 (7.72)
196 (7.72)
Depth
Without operator panel
mm (in)
155 (6.1) (PN version: 177.4 (6.98))
203 (7.99) (PN version: 225.4 (8.87))
203 (7.99) (PN version: 225.4 (8.87))
203 (7.99) (PN version: 225.4 (8.87))
With operator panel
mm (in)
176 (6.93) (PN version: 198.4 (7.81))
224 (8.82) (PN version: 246.4 (9.70))
224 (8.82) (PN version: 246.4 (9.70))
224 (8.82) (PN version: 246.4 (9.70))
Frame size
FSAA
FSA
FSA
FSB
Weight, approx.
Without filter
kg (lb)
1.1 (2.43) (PN version: 1.2 (2.65))
1.7 (3.75)
1.7 (3.75)
2.3 (5.07)
With integrated filter class A
kg (lb)
1.3 (2.87) (PN version: 1.4 (3.09))
1.9 (4.19)
1.9 (4.19)
2.5 (5.51)
1) The rated output current Irated can be used up to 100 %; however, without overload.
2) The base-load current IL is based on the duty cycle for low overload (LO).
3) The base-load current IH is based on the duty cycle for high overload (HO).
5) The rated input currents are valid for an input voltage of 400 V 3 AC and a line impedance corresponding to uK = 1 % (without line reactor). The rated input current based on IL is stamped on the inverter rating plate. In the particular application, the input current depends on the motor load and line impedance. The input current is reduced when using a line reactor.
6) The maximum motor cable lengths are valid for an input voltage of 400 V 3 AC and operation with a 4 kHz pulse frequency. When an inverter with an integrated line filter class A is used to comply with the limits of EN 61800?3 Category C2 for line-conducted interference emissions, the maximum permissible motor cable length is 25 m (82 ft) (shielded) as standard - for frame sizes FSA and FSB with low-capacitance CY cable (shielded) it is 50 m (164 ft).
Line voltage 380 ... 480 V 3 AC
SINAMICS G120C power electronics
6SL3210-1KE21-7..1
6SL3210-1KE22-6..1
6SL3210-1KE23-2..1
6SL3210-1KE23-8..1
Output current
at 400 V 3 AC
Rated current Irated 1)
A
17
26
32
38
Base-load current IL 2)
A
16.5
25
31
37
Base-load current IH 3)
A
12.5
16.5
25
31
Maximum current Imax
A
25
33
50
62
Rated power
Based on IL
kW (hp)
7.5 (7.5)
11 (10)
15 (15)
18.5 (20)
Based on IH
kW (hp)
5.5 (7.5)
7.5 (7.5)
11 (10)
15 (15)
Rated pulse frequency
kHz
4
4
4
4
Efficiency ?
%
97
97
97
97
Power loss 4)
At rated current
kW
0.241
0.306
0.381
0.461
Cooling air requirement
m3/s (ft3/s)
0.009 (0.32)
0.018 (0.64)
0.018 (0.64)
0.018 (0.64)
Sound pressure level LpA (1 m)
dB
<63
<66
<66
<66
Rated input current 5)
Based on IL
A
21.5
33
40.6
48.2
Based on IH
A
18.2
24.1
36.4
45.2
Length of cable to braking resistor, max.
m (ft)
15 (49)
15 (49)
15 (49)
15 (49)
Line supply connection
U1/L1, V1/L2, W1/L3
Plug-in screw-type terminals
Plug-in screw-type terminals
Plug-in screw-type terminals
Plug-in screw-type terminals
Conductor cross-section
mm2
4 ... 6 (12 ... 10 AWG)
6 ... 16 (10 ... 5 AWG)
6 ... 16 (10 ... 5 AWG)
6 ... 16 (10 ... 5 AWG)
Motor connection
U2, V2, W2
Plug-in screw-type terminals
Plug-in screw-type terminals
Plug-in screw-type terminals
Plug-in screw-type terminals
Conductor cross-section
mm2
4 ... 6 (12 ... 10 AWG)
6 ... 16 (10 ... 5 AWG)
6 ... 16 (10 ... 5 AWG)
6 ... 16 (10 ... 5 AWG)
Connection for braking resistor
R1, R2
Plug-in screw-type terminals
Plug-in screw-type terminals
Plug-in screw-type terminals
Plug-in screw-type terminals
Conductor cross-section
mm2
4 ... 6 (12 ... 10 AWG)
6 ... 16 (10 ... 5 AWG)
6 ... 16 (10 ... 5 AWG)
6 ... 16 (10 ... 5 AWG)
PE connection
On housing with M4 screw
On housing with M4 screw
On housing with M4 screw
On housing with M4 screw
Motor cable length, max. 6)
Without filter, shielded/unshielded
m (ft)
150/150 (492/492)
150/150 (492/492)
150/150 (492/492)
150/150 (492/492)
With integrated filter class A, shielded/unshielded
m (ft)
50/100 (164/328)
50/100 (164/328)
50/100 (164/328)
50/100 (164/328)
Dimensions
Width
mm (in)
100 (3.94)
140 (5.51)
140 (5.51)
140 (5.51)
Height
mm (in)
196 (7.72)
295 (11.61)
295 (11.61)
295 (11.61)
Depth
Without operator panel
mm (in)
203 (7.99) (PN version: 225.4 (8.87))
203 (7.99) (PN version: 225.4 (8.87))
203 (7.99) (PN version: 225.4 (8.87))
203 (7.99) (PN version: 225.4 (8.87))
With operator panel
mm (in)
224 (8.82) (PN version: 246.4 (9.70))
224 (8.82) (PN version: 246.4 (9.70))
224 (8.82) (PN version: 246.4 (9.70))
224 (8.82) (PN version: 246.4 (9.70))
Frame size
FSB
FSC
FSC
FSC
Weight, approx.
Without filter
kg (lb)
2.3 (5.07)
4.4 (9.70)
4.4 (9.70)
4.4 (9.70)
With integrated filter class A
kg (lb)
2.5 (5.51)
4.7 (10.36)
4.7 (10.36)
4.7 (10.36)
1) The rated output current Irated can be used up to 100 %; however, without overload.
2) The base-load current IL is based on the duty cycle for low overload (LO).
3) The base-load current IH is based on the duty cycle for high overload (HO).
5) The rated input currents are valid for an input voltage of 400 V 3 AC and a line impedance corresponding to uK = 1 % (without line reactor). The rated input current based on IL is stamped on the inverter rating plate. In the particular application, the input current depends on the motor load and line impedance. The input current is reduced when using a line reactor.
6) The maximum motor cable lengths are valid for an input voltage of 400 V 3 AC and operation with a 4 kHz pulse frequency. When an inverter with an integrated line filter class A is used to comply with the limits of EN 61800-3 Category C2 for line-conducted interference emission, the maximum permissible motor cable length is 25 m (82 ft) (shielded) as standard - with low-capacitance CY cable for frame size FSB 50 m (164 ft) (shielded), for FSC 100 m (328 ft) (shielded).
skener.ru
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Àðìàòóðà DENDOR
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Äàò÷èêè è èçìåðèòåëè
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ðåãóëÿòîðû è ðåãèñòðàòîðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ïíåâìàòè÷åñêîå îáîðóäîâàíèå
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Êðàíû è Êëàïàíû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Èçìåðèòåëüíûå ïðèáîðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ñèñòåìû áåñïðîâîäíîãî óïðàâëåíèÿ «óìíûé äîì»
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Áåñêîíòàêòíûå âûêëþ÷àòåëè Êîíå÷íûå âûêëþ÷àòåëè Îïòè÷åñêèå äàò÷èêè Ýíêîäåðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Óñòàíîâêà óìÿã÷åíèÿ
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Óñòàíîâêà îáåçæåëåçèâàíèÿ