Standard motors up to frame size 315 L
The standard motors from Siemens are suitable for converter-fed operation at rated voltages up to 460 V. The following table shows the available motor series:
Standard motors up to frame size 315 L for converter-fed operation up to 460 V rated voltage
Motor type |
Standard type of protection |
Frame design |
Motor series |
Motor frame sizes |
Output range |
---|---|---|---|---|---|
kW | |||||
Self-ventilated motors with improved efficiency (energy-saving motors according to efficiency class EFF2 Improved Efficiency for 2-pole and 4-pole motors with outputs from 1.1 to 90 kW) |
IP55 |
Aluminum |
1LA7 |
56 M ... 160 L |
0.06 ... 18.5 |
1LA5 |
180 M ... 225 M |
11 ... 45 | |||
Cast-iron |
1LA6 |
100 L ... 160 L |
0.75 ... 18.5 | ||
1LG4 |
180 M ... 315 L |
11 ... 200 | |||
Self-ventilated motors with high efficiency (energy-saving motors according to efficiency class EFF1 High Efficiency for 2-pole and 4-pole motors with outputs from 1.1 to 90 kW) |
IP55 |
Aluminum |
1LA9 |
56 M ... 200 L |
0.06 ... 37 |
Cast-iron |
1LG6 |
180 M ... 315 L |
11 ... 200 | ||
Self-ventilated motors with increased output |
IP55 |
Aluminum |
1LA9 |
56 M ... 200 L |
0.14 ... 53 |
Cast-iron |
1LG4 |
180 M ... 280 M |
15 ... 110 | ||
Self-ventilated motors without external fan |
IP55 |
Aluminum |
1LP7 |
63 M ... 160 L |
0.045 ... 7 |
1LP5 |
180 M ... 200 L |
5.5 ... 16.5 | |||
Cast-iron |
1LP4 |
180 L ... 315 L |
3.7 ... 67 | ||
Pole-changing motors |
IP55 |
Aluminum |
1LA7 |
63 M ... 160 L |
0.1 ... 17 |
1LA5 |
180 M ... 200 L |
11 ... 31 |
For technical data, selection and ordering data and special versions, see the relevant sections of “Standard motors up to frame size 315 L”.
Non-standard motors frame size 315 and above
The non-standard motors from Siemens are suitable for converter-fed operation at rated voltages up to 500 V. The following table shows the available motor series:
Non-standard motors up to frame size 315 for converter-fed operation up to 500 V rated voltage
Motor type |
Standard type of protection |
Frame design |
Motor series |
Motor frame sizes |
Output range |
---|---|---|---|---|---|
kW | |||||
Self-ventilated motors for converter-fed operation - Cast-iron series 1LA8 |
IP55 |
Cast-iron |
1LA8 |
315 ... 450 |
145 ... 1000 |
Forced-air cooled motors with externally-mounted fan for converter-fed operation - Cast-iron series 1PQ8 |
IP55 |
Cast-iron |
1PQ8 |
315 ... 450 |
145 ... 1000 |
Self-ventilated motors with through ventilation for converter-fed operation - Cast-iron series 1LL8 |
IP23 |
Cast-iron |
1LL8 |
315 ... 450 |
200 ... 1250 |
For technical data, selection and ordering data and special versions, see the relevant sections of “Non-standard motors up to frame size 315“.
Explosion-proof motors
The explosion-proof motors from Siemens listed below up to frame size 315 L can be operated with a converter at rated voltages up to 460 V (for motor series 1LA8 and PQ8 up to 500 V):
Explosion-proof motors up to frame size 315 L for converter-fed operation up to 460 V rated voltage (for motor series 1LA8 and PQ8 up to 500 V)
Motor type |
Standard type of protection |
Frame design |
Motor series 1) |
Motor frame sizes |
Output range |
---|---|---|---|---|---|
kW | |||||
Self-ventilated motors in Zone 1 with type of protection “d” |
IP55 |
Cast-iron |
1MJ6 |
71 M ... 200 L |
0.25 ... 37 |
1MJ7 |
225 M ... 315 L |
30 ... 132 | |||
1MJ8 |
355 |
200 ... 400 | |||
Cast-iron/steel |
1MJ1 |
315 M ... 450 |
90 ... 950 | ||
Self-ventilated motors in Zone 2 with type of protection “n” |
IP55 |
Aluminum |
1LA7 |
63 M ... 160 L |
0.09 ... 18.5 |
1LA9 |
56 M ... 200 L |
0.06 ... 37 | |||
Cast-iron |
1LA6 |
100 L ... 160 L |
0.75 ... 18.5 | ||
1LG4/1LG6 |
180 M ... 315 L |
11 ... 200 | |||
Self-ventilated motors in Zone 21 with type of protection “n” |
IP55 |
Aluminum |
1LA7 |
56 M ... 160 L |
0.09 ... 18.5 |
1LA5 |
180 M ... 225 M |
11 ... 45 | |||
1LA9 |
56 M ... 200 L |
0.06 ... 37 | |||
Cast-iron |
1LG4/1LG6 |
180 M ... 315 L |
11 ... 200 | ||
Self-ventilated motors in Zone 22 with type of protection “n” |
IP55 |
Aluminum |
1LA7 |
56 M ... 160 L |
0.09 ... 18.5 |
1LA5 |
180 M ... 225 M |
11 ... 45 | |||
1LA9 |
56 M ... 200 L |
0.06 ... 37 | |||
Cast-iron |
1LA6 |
100 L ... 160 L |
0.75 ... 18.5 | ||
1LG4/1LG6 |
180 M ... 315 L |
11 ... 200 | |||
Self-ventilated motors in Zones 2 and 22 with type of protection “n” |
IP55 |
Cast-iron |
1LA8 |
315 ... 450 |
145 ... 1000 |
Forced-air cooled motors with mounted separately driven fan for converter-fed operation |
IP55 |
Cast-iron |
1PQ8 |
315 ... 450 |
145 ... 1000 |
1) For converter-fed operation with frame size 225 and above, it is recommended that an “Insulated bearing cartridge” - Order codeL27 - is used. For motor series 1LA8 and 1PQ8, the insulated bearing cartridge is standard.
For technical data, selection and ordering data and special versions, see the relevant sections of “Explosion-proof motors“.
Fan motors
The fan motors from Siemens listed below are suitable for converter-fed operation at rated voltages up to 460 V:
Fan motors for converter-fed operation at 460 V rated voltage
Motor type |
Standard degree of protection |
Frame design |
Motor series |
Motor frame sizes |
Output range |
---|---|---|---|---|---|
kW | |||||
Self-ventilated motors in pole-changing version |
IP55 |
Aluminum |
1LA7 |
80 M ... 160 L |
0.15 ... 17 |
1LA5 |
180 M ... 200 L |
18 ... 31 | |||
Cast-iron |
1LG4 |
180 M ... 315 L |
11 ... 200 | ||
Forced-air cooled motors without external fan, without fan cover |
IP55 |
Aluminum |
1PP7 |
63 M ... 160 L |
0.09 ... 18.5 |
1PP5 |
180 M ... 200 L |
15 ... 37 | |||
Cast-iron |
1PP4 |
180 M ... 315 L |
11 ... 200 |
For technical data, selection and ordering data and special versions, see the relevant sections of “Fan motors“.