The most important directives and standards are listed below. These are used as basis for the SINAMICS G150 converter cabinet units and they must be carefully observed to achieve an EMC-compliant configuration that is safe both functionally and in operation. European directives |
---|
2006/95/EC | Low-voltage directive: Directive of the European Parliament and Council of December 12, 2006, on the approximation of the laws of the member states relating to electrical equipment designed for use within certain voltage limits | 2006/42/EC | Machinery directive: Directive of the European Parliament and Council of May 17, 2006 on machinery and for changing Directive 95/16/EC (amendment) | 2004/108/EC | EMC directive: Directive of the European Parliament and Council of December 15, 2004, which repeals directive 89/336/EEC, on the approximation of laws of the member states relating to electromagnetic compatibility | European standards | EN ISO 3744 | Acoustics – Determination of the sound power level and sound energy level for noise sources that result from sound pressure measurements – envelope surface procedure of the accuracy class 2 for a largely free sound field over a reflecting plane | EN ISO 13849-1 | Safety of machinery – Safety-related parts of control systems Part 1: General design principles (ISO 13849‑1:2006) (replaced EN 954‑1) | EN 60146-1-1 | Semiconductor converters – General requirements and line-commutated converters Part 1‑1: Specification of basic requirements | EN 60204-1 | Electrical equipment of machines Part 1: General definitions | EN 60529 | Degrees of protection provided by enclosures (IP code) | EN 61508-1 | Functional safety of electrical/electronic/programmable electronic safety-related systems Part 1: General requirements | EN 61800-2 | Adjustable speed electrical power drive systems Part 2: General requirements – Rating specifications for the measurement of low-voltage adjustable frequency AC power drive systems | EN 61800-3 | Adjustable speed electrical power drive systems Part 3: EMC product standard including special test procedure | EN 61800-5-1 | Adjustable speed electrical power drive systems Part 5: Safety requirements Main section 1: Electrical and thermal requirements | EN 61800-5-2 | Adjustable speed electrical power drive systems Part 5-2: Safety requirements – Functional safety (IEC 61800‑5‑2:2007) |
General technical specificationsElectrical specifications | | Single connection | Parallel connection |
---|
Line voltages and power ranges | - 380 ... 480 V 3 AC ±10% (‑15% < 1 min)
| 110 ... 560 kW | 630 ... 900 kW | - 500 ... 600 V 3 AC ±10% (‑15% < 1 min)
| 110 ... 560 kW | 630 ... 1000 kW | - 660 ... 690 V 3 AC ±10% (‑15% < 1 min)
| 75 ... 800 kW | 1000 ... 2700 kW | Line system configurations | Grounded TN/TT systems or ungrounded IT systems (a grounded line conductor is not permissible in 690 V line supplies) | Line frequency | 47 ... 63 Hz | Output frequency | 0 ... 550 Hz1) | Line power factor | | | > 0.96 | | 0.75 ... 0.93 | Efficiency | > 98% | Overvoltage category | III according to EN 61800-5-1 | Control method | Vector control with and without encoder or V/f control | Fixed speeds | 15 fixed speeds plus 1 minimum speed, parameterizable (in the default setting, 3 fixed setpoints plus 1 minimum speed are selectable using terminal block / PROFIBUS) | Speed ranges that can be skipped | 4, parameterizable | Setpoint resolution | 0.001 rpm digital 12-bit analog | Braking operation | Optional via braking unit | Mechanical specifications | Degree of protection | IP20 (higher degrees of protection up to IP54 optional) | Protection class | I according to EN 61800‑5‑1 | Touch protection | EN 50274 / BGV A3 when used for the intended purpose | Cabinet system | Rittal TS8, doors with double-bit key, three-section base plates for cable entry | Paint finish | RAL 7035 (indoor requirements) | Cooling method | Forced air cooling AF according to EN 60146 | Ambient conditions | Storage | Transport | Operation | Ambient temperature | -25 ... +55 °C | -25 ... +70 °C as of -40 °C for 24 hours | 0 ... +40 °C to +50 °C see derating data | Relative humidity (condensation not permissible) | 5 ... 95% | 5 ... 95% at 40 °C | 5 ... 95% | | Class 1K4 according to EN 60721‑3‑1 | Class 2K3 according to EN 60721‑3‑2 | Class 3K3 according to EN 60721‑3‑3 | Environmental class / harmful chemical substances | Class 1C2 according to EN 60721‑3‑1 | Class 2C2 according to EN 60721‑3‑2 | Class 3C2 according to EN 60721‑3‑3 | Organic/biological influences | Class 1B1 according to EN 60721‑3‑1 | Class 2B1 according to EN 60721‑3‑2 | Class 3B1 according to EN 60721‑3‑3 | Degree of pollution | 2 according to EN 61800‑5‑1 | Installation altitude | Up to 2000 m above sea level without derating; > 2000 m see derating data | Mechanical stability | Storage | Transport | Operation | Vibratory load | | | 1.5 mm at 5 ... 9 Hz | 3.1 mm at 5 ... 9 Hz | 0.075 mm at 10 ... 58 Hz | | 5 m/s2 at > 9 ... 200 Hz | 10 m/s2 at > 9 ... 200 Hz | 10 m/s2 at > 58 … 200 Hz | | Class 1M2 according to EN 60721‑3‑1 | Class 2M2 according to EN 60721‑3‑2 | – | Shock load | | | 40 m/s2 for 22 ms | 100 m/s2 for 11 ms | 100 m/s2 for 11 ms | | Class 1M2 according to EN 60721‑3‑1 | Class 2M2 according to EN 60721‑3‑2 | Class 3M4 according to EN 60721‑3‑3 | Compliance with standards | CE marking | According to EMC Directive No. 2004/108/EC and Low Voltage Directive No. 2006/95/EC and Machinery Directive No. 2006/42/EC for functional safety | Radio interference suppression | The SINAMICS G150 converter systems are not designed for connection to the public power network ("first environment"). Radio interference suppression is compliant with the EMC product standard for variable-speed drives EN 61800‑3, "Second environment" (industrial networks). EMC disturbances can occur when connected to the public power networks. However, if supplementary measures are taken (e.g. line filter, see option L00) operation in the "first environment" is possible. 2) |
Deviations from the specified classes are underlined. 1) The output frequency is also affected by the selected control method and the pulse frequency. For further information, please refer to the SINAMICS Low Voltage Engineering Manual. 2) Applies to motor cable lengths < 100 m. Technical specifications for single connectionLine voltage 380 ... 480 V 3 AC | SINAMICS G150 converter cabinet units 6SL3710-1GE..-.... |
---|
Single connection | 32‑1.A3 | 32‑6.A3 | 33‑1.A3 | 33‑8.A3 | 35‑0.A3 | 36‑1.A3 | 37‑5.A3 | 38‑4.A3 | 41‑0.A3 |
---|
Type rating | | | | | | | | | | | | kW | 110 | 132 | 160 | 200 | 250 | 315 | 400 | 450 | 560 | | kW | 90 | 110 | 132 | 160 | 200 | 250 | 315 | 400 | 450 | | hp | 150 | 200 | 250 | 300 | 400 | 500 | 600 | 600 | 800 | | hp | 125 | 150 | 200 | 250 | 350 | 350 | 450 | 500 | 700 | Output current | | | | | | | | | | | | A | 210 | 260 | 310 | 380 | 490 | 605 | 745 | 840 | 985 | | A | 205 | 250 | 302 | 370 | 477 | 590 | 725 | 820 | 960 | | A | 178 | 233 | 277 | 340 | 438 | 460 | 570 | 700 | 860 | Input current | | | | | | | | | | | | A | 229 | 284 | 338 | 395 | 509 | 629 | 775 | 873 | 1024 | | A | 335 | 410 | 495 | 606 | 781 | 967 | 1188 | 1344 | 1573 | - Current requirement, 24 V DC auxiliary power supply 6)
| A | 1.1 | 1.1 | 1.35 | 1.35 | 1.35 | 1.4 | 1.4 | 1.4 | 1.5 | Rated short-circuit current according to IEC 7) | kA | 65 | 65 | 65 | 65 | 65 | 65 | 65 | 84 | 84 | Minimum short-circuit current 8) | A | 3000 | 3600 | 4400 | 4400 | 8000 | 10000 | 10500 | 16000/1800 9) | 18400/2000 9) | Power loss, max. 10) | | | | | | | | | | | | kW | 2.9 | 3.8 | 4.4 | 5.3 | 6.4 | 8.2 | 9.6 | 10.1 | 14.4 | | kW | 2.54 | 3.36 | 4.07 | 4.67 | 5.96 | 8.3 | 9.7 | 10.2 | 14.7 | Cooling air requirement | m3/s | 0.17 | 0.23 | 0.36 | 0.36 | 0.36 | 0.78 | 0.78 | 0.78 | 1.48 | Sound pressure level LpA (1 m) at 50/60 Hz | dB | 67/68 | 69/73 | 69/73 | 69/73 | 69/73 | 70/73 | 70/73 | 70/73 | 72/75 | Cable lengths between converter and motor 11) | | | | | | | | | | | | m | 300 | 300 | 300 | 300 | 300 | 300 | 300 | 300 | 300 | | m | 450 | 450 | 450 | 450 | 450 | 450 | 450 | 450 | 450 | Dimensions | | | | | | | | | | | | mm | 800/400 | 800/400 | 800/400 | 1000/400 | 1000/400 | 1200/600 | 1200/600 | 1200/600 | 1600/1000 | | mm | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | | mm | 600 | 600 | 600 | 600 | 600 | 600 | 600 | 600 | 600 | Weight, approx. (degree of protection IP20, without options) for version A/C | kg | 460/225 | 460/225 | 670/300 | 670/300 | 670/300 | 750/670 | 750/670 | 780/670 | 1100/880 |
Note: The power data in hp units is based on the NEC/CEC standards for the North American market. For information on the line connection, motor connection and cabinet grounding, see Section Configuration. 1) Rated output of a typical 6-pole standard induction motor based on IL or IH for 3 AC 50 Hz 400 V. 2) Rated output of a typical 6-pole standard induction motor based on IL or IH for 3 AC 60 Hz 460 V. 3) The base-load current IL is based on a load cycle of 110% for 60 s or 150% for 10 s with a load cycle duration of 300 s. See Characteristic curves, Section Overload capability. 4) The base-load current IH is based on a duty cycle of 150% for 60 s or 160% for 10 s with a duty cycle duration of 300 s. See Characteristic curves, Section Overload capability. 5) The currents listed here are based on the rated output current. 6) If the drive control is to remain active after a main infeed failure, the converter must be externally supplied with 24 V DC. The following must also be taken into account: – CU320-2: 1 A – TM31: 0.5 A – AOP30: 0.2 A – SMC: 0.6 A – Current requirement of digital inputs/outputs. 7) In conjunction with the specified fuses or circuit breakers. 8) Minimum current required for reliably triggering the protective devices. 9) For option L26 (version A) the low value applies. 10) The specified power losses are the maximum values for a utilization of 100%. The values are lower under normal operating conditions. 11) Longer cable lengths for specific configurations are available on request. 12)Version A: The cabinet height increases by – 250 mm for degree of protection IP21 – 400 mm for degrees of protection IP23, IP43 and IP54 – 405 mm for options M13 and M78 Version C: The cabinet height increases by – 250 mm for degree of protection IP21 – 400 mm for degrees of protection IP23, IP43 and IP54 Line voltage 500 ... 600 V 3 AC | SINAMICS G150 converter cabinet units 6SL3710-1GF..-.... |
---|
Single connection | 31‑8.A3 | 32‑2.A3 | 32‑6.A3 | 33‑3.A3 | 34‑1.A3 | 34‑7.A3 | 35‑8.A3 | 37‑4.A3 | 38‑1.A3 |
---|
Type rating | | | | | | | | | | | | kW | 110 | 132 | 160 | 200 | 250 | 315 | 400 | 500 | 560 | | kW | 90 | 110 | 132 | 160 | 200 | 250 | 315 | 450 | 500 | | hp | 150 | 200 | 250 | 300 | 400 | 450 | 600 | 700 | 800 | | hp | 150 | 200 | 200 | 250 | 350 | 450 | 500 | 700 | 700 | Output current | | | | | | | | | | | | A | 175 | 215 | 260 | 330 | 410 | 465 | 575 | 735 | 810 | | A | 171 | 208 | 250 | 320 | 400 | 452 | 560 | 710 | 790 | | A | 157 | 192 | 233 | 280 | 367 | 416 | 514 | 657 | 724 | Input current | | | | | | | | | | | | A | 191 | 224 | 270 | 343 | 426 | 483 | 598 | 764 | 842 | | A | 279 | 341 | 410 | 525 | 655 | 740 | 918 | 1164 | 1295 | - Current requirement, 24 V DC auxiliary power supply 6)
| A | 1.35 | 1.35 | 1.35 | 1.4 | 1.4 | 1.4 | 1.4 | 1.5 | 1.5 | Rated short-circuit current according to IEC 7) | kA | 65 | 65 | 65 | 65 | 65 | 65 | 65 | 84 | 84 | Minimum short-circuit current 8) | A | 2400 | 3000 | 3600 | 5200 | 5200 | 6200 | 8400 | 10500 | 10400/1800 9) | Power loss, max. 10) | | | | | | | | | | | | kW | 3.8 | 4.2 | 5 | 6.1 | 8.1 | 7.8 | 8.7 | 12.7 | 14.1 | | kW | 3.2 | 3.6 | 4.1 | 5.1 | 6.7 | 7.5 | 8.4 | 12.5 | 13.8 | Cooling air requirement | m3/s | 0.36 | 0.36 | 0.36 | 0.36 | 0.78 | 0.78 | 0.78 | 1.48 | 1.48 | Sound pressure level LpA (1 m) at 50/60 Hz | dB | 69/73 | 69/73 | 69/73 | 69/73 | 72/75 | 72/75 | 72/75 | 72/75 | 72/75 | Cable lengths between converter and motor 11) | | | | | | | | | | | | m | 300 | 300 | 300 | 300 | 300 | 300 | 300 | 300 | 300 | | m | 450 | 450 | 450 | 450 | 450 | 450 | 450 | 450 | 450 | Dimensions | | | | | | | | | | | | mm | 800/400 | 800/400 | 800/400 | 800/400 | 1200/600 | 1200/600 | 1200/600 | 1600/1000 | 1600/1000 | | mm | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | | mm | 600 | 600 | 600 | 600 | 600 | 600 | 600 | 600 | 600 | Weight, approx. (degree of protection IP20, without options) for version A/C | kg | 460/300 | 460/300 | 460/300 | 460/300 | 750/670 | 750/670 | 860/670 | 1150/940 | 1150/960 |
Note: The power data in hp units is based on the NEC/CEC standards for the North American market. For information on the line connection, motor connection and cabinet grounding, see Section Configuration. 1) Rated output of a typical 6-pole standard induction motor based on IL or IH for 3 AC 50 Hz 500 V. 2) Rated output of a typical 6-pole standard induction motor based on IL or IH for 3 AC 60 Hz 575 V. 3) The base-load current IL is based on a load cycle of 110% for 60 s or 150% for 10 s with a load cycle duration of 300 s. See Characteristic curves, Section Overload capability. 4) The base-load current IH is based on a duty cycle of 150% for 60 s or 160% for 10 s with a duty cycle duration of 300 s. See Characteristic curves, Section Overload capability. 5) The currents listed here are based on the rated output current. 6) If the drive control is to remain active after a main infeed failure, the converter must be externally supplied with 24 V DC. The following must also be taken into account: – CU320-2: 1 A – TM31: 0.5 A – AOP30: 0.2 A – SMC: 0.6 A – Current requirement of digital inputs/outputs. 7) In conjunction with the specified fuses or circuit breakers. 8) Minimum current required for reliably triggering the protective devices. 9) For option L26 (version A) the low value applies. 10) The specified power losses are the maximum values for a utilization of 100%. The values are lower under normal operating conditions. 11) Longer cable lengths for specific configurations are available on request. 12)Version A: The cabinet height increases by – 250 mm for degree of protection IP21 – 400 mm for degrees of protection IP23, IP43 and IP54 – 405 mm for options M13 and M78 Version C: The cabinet height increases by – 250 mm for degree of protection IP21 – 400 mm for degrees of protection IP23, IP43 and IP54 Line voltage 660 ... 690 V 3 AC | SINAMICS G150 converter cabinet units 6SL3710-1GH..-.... |
---|
Single connection | 28‑5.A3 | 31‑0.A3 | 31‑2.A3 | 31‑5.A3 | 31‑8.A3 | 32‑2.A3 | 32‑6.A3 |
---|
Type rating | | | | | | | | | | kW | 75 | 90 | 110 | 132 | 160 | 200 | 250 | | kW | 55 | 75 | 90 | 110 | 132 | 160 | 200 | Output current | | | | | | | | | | A | 85 | 100 | 120 | 150 | 175 | 215 | 260 | | A | 80 | 95 | 115 | 142 | 171 | 208 | 250 | | A | 76 | 89 | 107 | 134 | 157 | 192 | 233 | Input current | | | | | | | | | | A | 93 | 109 | 131 | 164 | 191 | 224 | 270 | | A | 131 | 155 | 188 | 232 | 279 | 341 | 410 | - Current requirement, 24 V DC auxiliary power supply 5)
| A | 1.1 | 1.1 | 1.1 | 1.1 | 1.35 | 1.35 | 1.35 | Rated short-circuit current according to IEC 6) | kA | 65 | 65 | 65 | 65 | 65 | 65 | 65 | Minimum short-circuit current 7) | A | 1500 | 1500 | 1200 | 1600 | 2400 | 3000 | 3600 | Power loss, max. 8) at 50 Hz 690 V | kW | 1.7 | 2.1 | 2.7 | 2.8 | 3.8 | 4.2 | 5 | Cooling air requirement | m3/s | 0.17 | 0.17 | 0.17 | 0.17 | 0.36 | 0.36 | 0.36 | Sound pressure level LpA (1 m) at 50/60 Hz | dB | 67/68 | 67/68 | 67/68 | 67/68 | 67/73 | 67/73 | 67/73 | Cable lengths between converter and motor 9) | | | | | | | | | | m | 300 | 300 | 300 | 300 | 300 | 300 | 300 | | m | 450 | 450 | 450 | 450 | 450 | 450 | 450 | Dimensions | | | | | | | | | | mm | 800/400 | 800/400 | 800/400 | 800/400 | 800/400 | 800/400 | 800/400 | | mm | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | | mm | 600 | 600 | 600 | 600 | 600 | 600 | 600 | Weight, approx. (degree of protection IP20, without options) for version A/C | kg | 460/225 | 460/225 | 460/225 | 460/225 | 670/300 | 670/300 | 670/300 |
Note: The power data in hp units is based on the NEC/CEC standards for the North American market. For information on the line connection, motor connection and cabinet grounding, see Section Configuration. 1) Rated output of a typical 6-pole standard induction motor based on IL or IH for 3 AC 50 Hz 690 V. 2) The base-load current IL is based on a load cycle of 110% for 60 s or 150% for 10 s with a load cycle duration of 300 s. See Characteristic curves, Section Overload capability. 3) The base-load current IH is based on a duty cycle of 150% for 60 s or 160% for 10 s with a duty cycle duration of 300 s. See Characteristic curves, Section Overload capability. 4) The currents listed here are based on the rated output current. 5) If the drive control is to remain active after a main infeed failure, the converter must be externally supplied with 24 V DC. The following must also be taken into account: – CU320-2: 1 A – TM31: 0.5 A – AOP30: 0.2 A – SMC: 0.6 A – Current requirement of digital inputs/outputs. 6) In conjunction with the specified fuses or circuit breakers. 7) Minimum current required for reliably triggering the protective devices. 8) The specified power losses are the maximum values for a utilization of 100%. The values are lower under normal operating conditions. 9) Longer cable lengths for specific configurations are available on request. 10)Version A: The cabinet height increases by – 250 mm for degree of protection IP21 – 400 mm for degrees of protection IP23, IP43 and IP54 – 405 mm for options M13 and M78 Version C: The cabinet height increases by – 250 mm for degree of protection IP21 – 400 mm for degrees of protection IP23, IP43 and IP54 Line voltage 660 ... 690 V 3 AC | SINAMICS G150 converter cabinet units 6SL3710-1GH..-.... |
---|
Single connection | 33‑3.A3 | 34‑1.A3 | 34‑7.A3 | 35‑8.A3 | 37‑4.A3 | 38‑1.A3 |
---|
Type rating | | | | | | | | | kW | 315 | 400 | 450 | 560 | 710 | 800 | | kW | 250 | 315 | 400 | 450 | 560 | 710 | Output current | | | | | | | | | A | 330 | 410 | 465 | 575 | 735 | 810 | | A | 320 | 400 | 452 | 560 | 710 | 790 | | A | 280 | 367 | 416 | 514 | 657 | 724 | Input current | | | | | | | | | A | 343 | 426 | 483 | 598 | 764 | 842 | | A | 525 | 655 | 740 | 918 | 1164 | 1295 | - Current requirement, 24 V DC auxiliary power supply 5)
| A | 1.35 | 1.4 | 1.4 | 1.4 | 1.5 | 1.5 | Rated short-circuit current according to IEC 6) | kA | 65 | 65 | 84 | 84 | 85 | 85 | Minimum short-circuit current 7) | A | 5200 | 5200 | 6200 | 8400 | 10500 | 10400/1800 8) | Power loss, max. 9) at 50 Hz 690 V | kW | 6.1 | 8.1 | 9.1 | 10.8 | 13.5 | 14.7 | Cooling air requirement | m3/s | 0.36 | 0.78 | 0.78 | 0.78 | 1.48 | 1.48 | Sound pressure level LpA (1 m) at 50/60 Hz | dB | 67/73 | 72/75 | 72/75 | 72/75 | 72/75 | 72/75 | Cable lengths between converter and motor 10) | | | | | | | | | m | 300 | 300 | 300 | 300 | 300 | 300 | | m | 450 | 450 | 450 | 450 | 450 | 450 | Dimensions | | | | | | | | | mm | 800/400 | 1200/600 | 1200/600 | 1200/600 | 1600/1000 | 1600/1000 | | mm | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | | mm | 600 | 600 | 600 | 600 | 600 | 600 | Weight, approx. (degree of protection IP20, without options) for version A/C | kg | 670/300 | 780/670 | 780/670 | 840/670 | 1320/940 | 1360/980 |
Note: The power data in hp units is based on the NEC/CEC standards for the North American market. For information on the line connection, motor connection and cabinet grounding, see Section Configuration. 1) Rated output of a typical 6-pole standard induction motor based on IL or IH for 3 AC 50 Hz 690 V. 2) The base-load current IL is based on a load cycle of 110% for 60 s or 150% for 10 s with a load cycle duration of 300 s. See Characteristic curves, Section Overload capability. 3) The base-load current IH is based on a duty cycle of 150% for 60 s or 160% for 10 s with a duty cycle duration of 300 s. See Characteristic curves, Section Overload capability. 4) The currents listed here are based on the rated output current. 5) If the drive control is to remain active after a main infeed failure, the converter must be externally supplied with 24 V DC. The following must also be taken into account: – CU320-2: 1 A – TM31: 0.5 A – AOP30: 0.2 A – SMC: 0.6 A – Current requirement of digital inputs/outputs. 6) In conjunction with the specified fuses or circuit breakers. 7) Minimum current required for reliably triggering the protective devices. 8) For option L26 (version A) the low value applies. 9) The specified power losses are the maximum values for a utilization of 100%. The values are lower under normal operating conditions. 10) Longer cable lengths for specific configurations are available on request. 11)Version A: The cabinet height increases by – 250 mm for degree of protection IP21 – 400 mm for degrees of protection IP23, IP43 and IP54 – 405 mm for options M13 and M78 Version C: The cabinet height increases by – 250 mm for degree of protection IP21 – 400 mm for degrees of protection IP23, IP43 and IP54 Technical specifications for parallel connection | SINAMICS G150 converter cabinet units, version A 6SL3710-2GE..-.... | SINAMICS G150 converter cabinet units, version A 6SL3710-2GF..-.... |
---|
Parallel connection | 41‑1AA3 | 41‑4AA3 | 41‑6AA3 | 38‑6AA3 | 41‑1AA3 | 41‑4AA3 |
---|
Line voltage | | 380 ... 480 V 3 AC | 500 ... 600 V 3 AC |
---|
Type rating | | | | | | | | | kW | 630 | 710 | 900 | 630 | 710 | 1000 | | kW | 500 | 560 | 710 | 560 | 630 | 800 | - For IL at 60 Hz 460 V or 575 V 2)
| hp | 900 | 1000 | 1250 | 900 | 1000 | 1250 | - For IH at 60 Hz 460 V or 575 V 2)
| hp | 700 | 900 | 1000 | 800 | 900 | 1000 | Output current | | | | | | | | | A | 1120 | 1380 | 1560 | 860 | 1070 | 1360 | | A | 1092 | 1340 | 1516 | 836 | 1036 | 1314 | | A | 850 | 1054 | 1294 | 770 | 950 | 1216 | Input current | | | | | | | | | A | 1174 | 1444 | 1624 | 904 | 1116 | 1424 | | A | 1800 | 2215 | 2495 | 1388 | 1708 | 2186 | - Current requirement, 24 V DC auxiliary power supply 7)
| A | 2.8 | 2.8 | 3 | 2.8 | 2.8 | 3 | Rated short-circuit current according to IEC 8) | kA | 2 × 65 | 2 × 65 | 2 × 65 | 2 × 65 | 2 × 65 | 2 × 84 | Minimum short-circuit current 9) | A | 2 × 1000 | 2 × 10500 | 2 × 1800 | 2 × 6200 | 2 × 8400 | 2 × 10500 | Power loss, max. 10) | | | | | | | | | kW | 16.2 | 19 | 19.9 | 15.4 | 17.2 | 23.8 | | kW | 16.6 | 19.4 | 20.4 | 15 | 16.8 | 25 | Cooling air requirement | m3/s | 1.56 | 1.56 | 1.56 | 1.56 | 1.56 | 2.96 | Sound pressure level LpA (1 m) at 50/60 Hz | dB | 73/76 | 73/76 | 73/76 | 75/78 | 75/78 | 75/78 | Cable lengths between converter and motor 11) | | | | | | | | | m | 300 | 300 | 300 | 300 | 300 | 300 | | m | 450 | 450 | 450 | 450 | 450 | 450 | Dimensions | | | | | | | | | mm | 2400 | 2400 | 2400 | 2400 | 2400 | 3200 | | mm | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | | mm | 600 | 600 | 600 | 600 | 600 | 600 | Weight, approx. (degree of protection IP20, without options) | kg | 1700 | 1710 | 2130 | 1700 | 1700 | 2620 |
Note: The power data in hp units is based on the NEC/CEC standards for the North American market. For information on the line connection, motor connection and cabinet grounding, see Section Configuration. 1) Rated output of a typical 6-pole standard induction motor based on IL or IH at 3 AC 50 Hz 400 V, 500 V or 690 V. 2) Rated output of a typical 6-pole standard induction motor based on IL or I or H at 3 AC 60 Hz 460 V or 575 V. 3) The currents specified here are the total current of both converter sections. 4) The base-load current IL is based on a load cycle of 110% for 60 s or 150% for 10 s with a load cycle duration of 300 s. See Characteristic curves, Section Overload capability. 5) The base-load current IH is based on a duty cycle of 150% for 60 s or 160% for 10 s with a duty cycle duration of 300 s. See Characteristic curves, Section Overload capability. 6) The currents listed here are based on the rated output current. 7) If the drive control is to remain active after a main infeed failure, the converter must be externally supplied with 24 V DC. The following must also be taken into account: – CU320-2: 1 A – TM31: 0.5 A – AOP30: 0.2 A – SMC: 0.6 A – Current requirement of digital inputs/outputs. 8) In conjunction with the specified fuses or circuit breakers. 9) Minimum current required for reliably triggering the protective devices. 10) The specified power losses are the maximum values for a utilization of 100%. The values are lower under normal operating conditions. 11) Longer cable lengths for specific configurations are available on request. 12) The power units connected in parallel are supplied as two transport units. 13) The cabinet height increases by – 250 mm for degree of protection IP21 – 400 mm for degrees of protection IP23, IP43 and IP54 – 405 mm for options M13 and M78 | SINAMICS G150 converter cabinet units, version A 6SL3710-2GH..-.... |
---|
Parallel connection | 41‑1AA3 | 41‑4AA3 | 41‑5AA3 | 41‑8EA3 | 42‑0EA3 | 42‑2EA3 | 42‑4E A3 | 42‑7E A3 |
---|
Line voltage | 660 ... 690 V 3 AC |
---|
Type rating | | | | | | | | | | | kW | 1000 | 1350 | 1500 | 1750 | 1950 | 2150 | 2400 | 2700 | | kW | 900 | 1200 | 1350 | 1500 | 1750 | 1950 | 2150 | 2400 | - For IL at 60 Hz 460 V or 575 V 2)
| hp | – | – | – | – | – | – | – | – | - For IH at 60 Hz 460 V or 575 V 2)
| hp | – | – | – | – | – | – | – | – | Output current | | | | | | | | | | | A | 1070 | 1360 | 1500 | 1729 | 1948 | 2158 | 2413 | 2752 | | A | 1036 | 1314 | 1462 | 1720 | 1940 | 2150 | 2390 | 2685 | | A | 950 | 1216 | 1340 | 1547 | 1742 | 1930 | 2158 | 2463 | Input current | | | | | | | | | | | A | 1116 | 1424 | 1568 | 1800 | 2030 | 2245 | 2510 | 2865 | | A | 1708 | 2186 | 2406 | 2765 | 3115 | 3450 | 3860 | 4400 | - Current requirement, 24 V DC auxiliary power supply 7)
| A | 2.8 | 2.8 | 3 | 4.7 | 4.7 | 4.7 | 4.7 | 6 | Rated short-circuit current according to IEC 8) | kA | 2 × 65 | 2 × 84 | 2 × 84 | 2 × 85 | 2 × 85 | 2 × 85 | 2 × 85 | 2 × 85 | Minimum short-circuit current 9) | A | 2 × 8400 | 2 × 10500 | 2 × 1800 | 2 × 1800 | 2 × 2000 | 2 × 2300 | 2 × 2500 | 2 × 3000 | Power loss, max. 10) at 50 Hz 690 V | kW | 21.3 | 26.6 | 29 | 35 | 38 | 40 | 46 | 52 | Cooling air requirement | m3/s | 1.56 | 2.96 | 2.96 | 3.67 | 3.67 | 3.67 | 3.67 | 5.15 | Sound pressure level LpA (1 m) at 50/60 Hz | dB | 75/78 | 75/78 | 75/78 | 75/78 | 75/78 | 75/78 | 75/78 | 75/78 | Cable lengths between converter and motor 11) | | | | | | | | | | | m | 300 | 300 | 300 | 300 | 300 | 300 | 300 | 300 | | m | 450 | 450 | 450 | 450 | 450 | 450 | 450 | 450 | Dimensions | | | | | | | | | | | mm | 2400 | 3200 | 3200 | 3600 | 3600 | 3600 | 3600 | 4400 | | mm | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | | mm | 600 | 600 | 600 | 600 | 600 | 600 | 600 | 600 | Weight, approx. (degree of protection IP20, without options) | kg | 1700 | 2620 | 2700 | 3010 | 3010 | 3070 | 3860 | 4580 |
Note: The power data in hp units is based on the NEC/CEC standards for the North American market. For information on the line connection, motor connection and cabinet grounding, see Section Configuration. 1) Rated output of a typical 6-pole standard induction motor based on IL or IH at 3 AC 50 Hz 400 V, 500 V or 690 V. 2) Rated output of a typical 6-pole standard induction motor based on IL or I or H at 3 AC 60 Hz 460 V or 575 V. 3) The currents specified here are the total current of both converter sections. 4) The base-load current IL is based on a load cycle of 110% for 60 s or 150% for 10 s with a load cycle duration of 300 s. See Characteristic curves, Section Overload capability. 5) The base-load current IH is based on a duty cycle of 150% for 60 s or 160% for 10 s with a duty cycle duration of 300 s. See Characteristic curves, Section Overload capability. 6) The currents listed here are based on the rated output current. 7) If the drive control is to remain active after a main infeed failure, the converter must be externally supplied with 24 V DC. The following must also be taken into account: – CU320-2: 1 A – TM31: 0.5 A – AOP30: 0.2 A – SMC: 0.6 A – Current requirement of digital inputs/outputs. 8) In conjunction with the specified fuses or circuit breakers. 9) Minimum current required for reliably triggering the protective devices. 10) The specified power losses are the maximum values for a utilization of 100%. The values are lower under normal operating conditions. 11) Longer cable lengths for specific configurations are available on request. 12) The power units connected in parallel are supplied as two transport units. 13) The cabinet height increases by – 250 mm for degree of protection IP21 – 400 mm for degrees of protection IP23, IP43 and IP54 – 405 mm for options M13 and M78
|
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Àðìàòóðà DENDOR
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Äàò÷èêè è èçìåðèòåëè
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ðåãóëÿòîðû è ðåãèñòðàòîðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ïíåâìàòè÷åñêîå îáîðóäîâàíèå
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Êðàíû è Êëàïàíû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Èçìåðèòåëüíûå ïðèáîðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ñèñòåìû áåñïðîâîäíîãî óïðàâëåíèÿ «óìíûé äîì»
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Áåñêîíòàêòíûå âûêëþ÷àòåëè Êîíå÷íûå âûêëþ÷àòåëè Îïòè÷åñêèå äàò÷èêè Ýíêîäåðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Óñòàíîâêà óìÿã÷åíèÿ
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Óñòàíîâêà îáåçæåëåçèâàíèÿ
|