The most important directives and standards are listed below. These are used as basis for the SINAMICS G150 converter cabinet units and they must be carefully observed to achieve an EMC-compliant configuration that is safe both functionally and in operation.
European directives
2006/95/EC
Low-voltage directive:
Directive of the European Parliament and Council of December 12, 2006, on the approximation of the laws of the member states relating to electrical equipment designed for use within certain voltage limits
2006/42/EC
Machinery directive:
Directive of the European Parliament and Council of May 17, 2006 on machinery and for changing Directive 95/16/EC (amendment)
2004/108/EC
EMC directive:
Directive of the European Parliament and Council of December 15, 2004, which repeals directive 89/336/EEC, on the approximation of laws of the member states relating to electromagnetic compatibility
European standards
EN ISO 3744
Acoustics – Determination of the sound power level and sound energy level for noise sources that result from sound pressure measurements – envelope surface procedure of the accuracy class 2 for a largely free sound field over a reflecting plane
EN ISO 13849-1
Safety of machinery – Safety-related parts of control systems
Part 1: General design principles (ISO 13849?1:2006) (replaced EN 954?1)
EN 60146-1-1
Semiconductor converters – General requirements and line-commutated converters
Part 1?1: Specification of basic requirements
EN 60204-1
Electrical equipment of machines
Part 1: General definitions
EN 60529
Degrees of protection provided by enclosures (IP code)
EN 61508-1
Functional safety of electrical/electronic/programmable electronic safety-related systems
Part 1: General requirements
EN 61800-2
Adjustable speed electrical power drive systems
Part 2: General requirements – Rating specifications for the measurement of low-voltage adjustable frequency AC power drive systems
EN 61800-3
Adjustable speed electrical power drive systems
Part 3: EMC product standard including special test procedure
EN 61800-5-1
Adjustable speed electrical power drive systems
Part 5: Safety requirements
Main section 1: Electrical and thermal requirements
EN 61800-5-2
Adjustable speed electrical power drive systems
Part 5-2: Safety requirements – Functional safety (IEC 61800?5?2:2007)
General technical specifications
Electrical specifications
Single connection
Parallel connection
Line voltages and power ranges
380 ... 480 V 3 AC ±10% (?15% < 1 min)
110 ... 560 kW
630 ... 900 kW
500 ... 600 V 3 AC ±10% (?15% < 1 min)
110 ... 560 kW
630 ... 1000 kW
660 ... 690 V 3 AC ±10% (?15% < 1 min)
75 ... 800 kW
1000 ... 2700 kW
Line system configurations
Grounded TN/TT systems or ungrounded IT systems (a grounded line conductor is not permissible in 690 V line supplies)
Line frequency
47 ... 63 Hz
Output frequency
0 ... 550 Hz1)
Line power factor
Fundamental
> 0.96
Total
0.75 ... 0.93
Efficiency
> 98%
Overvoltage category
III according to EN 61800-5-1
Control method
Vector control with and without encoder or V/f control
Fixed speeds
15 fixed speeds plus 1 minimum speed, parameterizable (in the default setting, 3 fixed setpoints plus 1 minimum speed are selectable using terminal block / PROFIBUS)
Speed ranges that can be skipped
4, parameterizable
Setpoint resolution
0.001 rpm digital
12-bit analog
Braking operation
Optional via braking unit
Mechanical specifications
Degree of protection
IP20 (higher degrees of protection up to IP54 optional)
Protection class
I according to EN 61800?5?1
Touch protection
EN 50274 / BGV A3 when used for the intended purpose
Cabinet system
Rittal TS8, doors with double-bit key, three-section base plates for cable entry
Paint finish
RAL 7035 (indoor requirements)
Cooling method
Forced air cooling AF according to EN 60146
Ambient conditions
Storage
Transport
Operation
Ambient temperature
-25 ... +55 °C
-25 ... +70 °C as of -40 °C for 24 hours
0 ... +40 °C to +50 °C see derating data
Relative humidity
(condensation not permissible)
5 ... 95%
5 ... 95% at 40 °C
5 ... 95%
Class 1K4 according to EN 60721?3?1
Class 2K3 according to EN 60721?3?2
Class 3K3 according to EN 60721?3?3
Environmental class / harmful chemical substances
Class 1C2 according to EN 60721?3?1
Class 2C2 according to EN 60721?3?2
Class 3C2 according to EN 60721?3?3
Organic/biological influences
Class 1B1 according to EN 60721?3?1
Class 2B1 according to EN 60721?3?2
Class 3B1 according to EN 60721?3?3
Degree of pollution
2 according to EN 61800?5?1
Installation altitude
Up to 2000 m above sea level without derating; > 2000 m see derating data
Mechanical stability
Storage
Transport
Operation
Vibratory load
Deflection
1.5 mm at 5 ... 9 Hz
3.1 mm at 5 ... 9 Hz
0.075 mm at 10 ... 58 Hz
Acceleration
5 m/s2 at > 9 ... 200 Hz
10 m/s2 at > 9 ... 200 Hz
10 m/s2 at > 58 … 200 Hz
Class 1M2 according to EN 60721?3?1
Class 2M2 according to EN 60721?3?2
–
Shock load
Acceleration
40 m/s2 for 22 ms
100 m/s2 for 11 ms
100 m/s2 for 11 ms
Class 1M2 according to EN 60721?3?1
Class 2M2 according to EN 60721?3?2
Class 3M4 according to EN 60721?3?3
Compliance with standards
CE marking
According to EMC Directive No. 2004/108/EC and Low Voltage Directive No. 2006/95/EC and Machinery Directive No. 2006/42/EC for functional safety
Radio interference suppression
The SINAMICS G150 converter systems are not designed for connection to the public power network ("first environment"). Radio interference suppression is compliant with the EMC product standard for variable-speed drives EN 61800?3, "Second environment" (industrial networks). EMC disturbances can occur when connected to the public power networks. However, if supplementary measures are taken (e.g. line filter, see option L00) operation in the "first environment" is possible. 2)
Deviations from the specified classes are underlined.
1) The output frequency is also affected by the selected control method and the pulse frequency. For further information, please refer to the SINAMICS Low Voltage Engineering Manual.
2) Applies to motor cable lengths < 100 m.
Technical specifications for single connection
Line voltage 380 ... 480 V 3 AC
SINAMICS G150 converter cabinet units 6SL3710-1GE..-....
Single connection
32?1.A3
32?6.A3
33?1.A3
33?8.A3
35?0.A3
36?1.A3
37?5.A3
38?4.A3
41?0.A3
Type rating
For IL at 50 Hz 400 V 1)
kW
110
132
160
200
250
315
400
450
560
For IH at 50 Hz 400 V 1)
kW
90
110
132
160
200
250
315
400
450
For IL at 60 Hz 460 V 2)
hp
150
200
250
300
400
500
600
600
800
For IH at 60 Hz 460 V 2)
hp
125
150
200
250
350
350
450
500
700
Output current
Rated current In
A
210
260
310
380
490
605
745
840
985
Base-load current IL3)
A
205
250
302
370
477
590
725
820
960
Base-load current IH4)
A
178
233
277
340
438
460
570
700
860
Input current
Rated input current 5)
A
229
284
338
395
509
629
775
873
1024
Input current, max.
A
335
410
495
606
781
967
1188
1344
1573
Current requirement, 24 V DC auxiliary power supply 6)
A
1.1
1.1
1.35
1.35
1.35
1.4
1.4
1.4
1.5
Rated short-circuit current
according to IEC 7)
kA
65
65
65
65
65
65
65
84
84
Minimum short-circuit current 8)
A
3000
3600
4400
4400
8000
10000
10500
16000/1800 9)
18400/2000 9)
Power loss, max. 10)
At 50 Hz 400 V
kW
2.9
3.8
4.4
5.3
6.4
8.2
9.6
10.1
14.4
At 60 Hz 460 V
kW
2.54
3.36
4.07
4.67
5.96
8.3
9.7
10.2
14.7
Cooling air requirement
m3/s
0.17
0.23
0.36
0.36
0.36
0.78
0.78
0.78
1.48
Sound pressure level
LpA (1 m) at 50/60 Hz
dB
67/68
69/73
69/73
69/73
69/73
70/73
70/73
70/73
72/75
Cable lengths
between converter and motor 11)
Shielded
m
300
300
300
300
300
300
300
300
300
Unshielded
m
450
450
450
450
450
450
450
450
450
Dimensions
Width for version A/C
mm
800/400
800/400
800/400
1000/400
1000/400
1200/600
1200/600
1200/600
1600/1000
Height 12)
mm
2000
2000
2000
2000
2000
2000
2000
2000
2000
Depth
mm
600
600
600
600
600
600
600
600
600
Weight, approx.
(degree of protection IP20, without options) for version A/C
kg
460/225
460/225
670/300
670/300
670/300
750/670
750/670
780/670
1100/880
Note: The power data in hp units is based on the NEC/CEC standards for the North American market.
For information on the line connection, motor connection and cabinet grounding, see Section Configuration.
1) Rated output of a typical 6-pole standard induction motor based on IL or IH for 3 AC 50 Hz 400 V.
2) Rated output of a typical 6-pole standard induction motor based on IL or IH for 3 AC 60 Hz 460 V.
3) The base-load current IL is based on a load cycle of 110% for 60 s or 150% for 10 s with a load cycle duration of 300 s. See Characteristic curves, Section Overload capability.
4) The base-load current IH is based on a duty cycle of 150% for 60 s or 160% for 10 s with a duty cycle duration of 300 s. See Characteristic curves, Section Overload capability.
5) The currents listed here are based on the rated output current.
6) If the drive control is to remain active after a main infeed failure, the converter must be externally supplied with 24 V DC. The following must also be taken into account: – CU320-2: 1 A – TM31: 0.5 A – AOP30: 0.2 A – SMC: 0.6 A – Current requirement of digital inputs/outputs.
7) In conjunction with the specified fuses or circuit breakers.
8) Minimum current required for reliably triggering the protective devices.
9) For option L26 (version A) the low value applies.
10) The specified power losses are the maximum values for a utilization of 100%. The values are lower under normal operating conditions.
11) Longer cable lengths for specific configurations are available on request.
12)Version A: The cabinet height increases by – 250 mm for degree of protection IP21 – 400 mm for degrees of protection IP23, IP43 and IP54 – 405 mm for options M13 and M78
Version C: The cabinet height increases by – 250 mm for degree of protection IP21 – 400 mm for degrees of protection IP23, IP43 and IP54
Line voltage 500 ... 600 V 3 AC
SINAMICS G150 converter cabinet units 6SL3710-1GF..-....
Single connection
31?8.A3
32?2.A3
32?6.A3
33?3.A3
34?1.A3
34?7.A3
35?8.A3
37?4.A3
38?1.A3
Type rating
For IL at 50 Hz 500 V 1)
kW
110
132
160
200
250
315
400
500
560
For IH at 50 Hz 500 V 1)
kW
90
110
132
160
200
250
315
450
500
For IL at 60 Hz 575 V 2)
hp
150
200
250
300
400
450
600
700
800
For IH at 60 Hz 575 V 2)
hp
150
200
200
250
350
450
500
700
700
Output current
Rated current In
A
175
215
260
330
410
465
575
735
810
Base-load current IL3)
A
171
208
250
320
400
452
560
710
790
Base-load current IH4)
A
157
192
233
280
367
416
514
657
724
Input current
Rated input current 5)
A
191
224
270
343
426
483
598
764
842
Input current, max.
A
279
341
410
525
655
740
918
1164
1295
Current requirement, 24 V DC auxiliary power supply 6)
A
1.35
1.35
1.35
1.4
1.4
1.4
1.4
1.5
1.5
Rated short-circuit current
according to IEC 7)
kA
65
65
65
65
65
65
65
84
84
Minimum short-circuit current 8)
A
2400
3000
3600
5200
5200
6200
8400
10500
10400/1800 9)
Power loss, max. 10)
At 50 Hz 500 V
kW
3.8
4.2
5
6.1
8.1
7.8
8.7
12.7
14.1
At 60 Hz 575 V
kW
3.2
3.6
4.1
5.1
6.7
7.5
8.4
12.5
13.8
Cooling air requirement
m3/s
0.36
0.36
0.36
0.36
0.78
0.78
0.78
1.48
1.48
Sound pressure level
LpA (1 m) at 50/60 Hz
dB
69/73
69/73
69/73
69/73
72/75
72/75
72/75
72/75
72/75
Cable lengths
between converter and motor 11)
Shielded
m
300
300
300
300
300
300
300
300
300
Unshielded
m
450
450
450
450
450
450
450
450
450
Dimensions
Width for version A/C
mm
800/400
800/400
800/400
800/400
1200/600
1200/600
1200/600
1600/1000
1600/1000
Height 12)
mm
2000
2000
2000
2000
2000
2000
2000
2000
2000
Depth
mm
600
600
600
600
600
600
600
600
600
Weight, approx.
(degree of protection IP20, without options) for version A/C
kg
460/300
460/300
460/300
460/300
750/670
750/670
860/670
1150/940
1150/960
Note: The power data in hp units is based on the NEC/CEC standards for the North American market.
For information on the line connection, motor connection and cabinet grounding, see Section Configuration.
1) Rated output of a typical 6-pole standard induction motor based on IL or IH for 3 AC 50 Hz 500 V.
2) Rated output of a typical 6-pole standard induction motor based on IL or IH for 3 AC 60 Hz 575 V.
3) The base-load current IL is based on a load cycle of 110% for 60 s or 150% for 10 s with a load cycle duration of 300 s. See Characteristic curves, Section Overload capability.
4) The base-load current IH is based on a duty cycle of 150% for 60 s or 160% for 10 s with a duty cycle duration of 300 s. See Characteristic curves, Section Overload capability.
5) The currents listed here are based on the rated output current.
6) If the drive control is to remain active after a main infeed failure, the converter must be externally supplied with 24 V DC. The following must also be taken into account: – CU320-2: 1 A – TM31: 0.5 A – AOP30: 0.2 A – SMC: 0.6 A – Current requirement of digital inputs/outputs.
7) In conjunction with the specified fuses or circuit breakers.
8) Minimum current required for reliably triggering the protective devices.
9) For option L26 (version A) the low value applies.
10) The specified power losses are the maximum values for a utilization of 100%. The values are lower under normal operating conditions.
11) Longer cable lengths for specific configurations are available on request.
12)Version A: The cabinet height increases by – 250 mm for degree of protection IP21 – 400 mm for degrees of protection IP23, IP43 and IP54 – 405 mm for options M13 and M78
Version C: The cabinet height increases by – 250 mm for degree of protection IP21 – 400 mm for degrees of protection IP23, IP43 and IP54
Line voltage 660 ... 690 V 3 AC
SINAMICS G150 converter cabinet units 6SL3710-1GH..-....
Single connection
28?5.A3
31?0.A3
31?2.A3
31?5.A3
31?8.A3
32?2.A3
32?6.A3
Type rating
For IL at 50 Hz 690 V 1)
kW
75
90
110
132
160
200
250
For IH at 50 Hz 690 V 1)
kW
55
75
90
110
132
160
200
Output current
Rated current In
A
85
100
120
150
175
215
260
Base-load current IL 2)
A
80
95
115
142
171
208
250
Base-load current IH 3)
A
76
89
107
134
157
192
233
Input current
Rated input current 4)
A
93
109
131
164
191
224
270
Input current, max.
A
131
155
188
232
279
341
410
Current requirement, 24 V DC auxiliary power supply 5)
A
1.1
1.1
1.1
1.1
1.35
1.35
1.35
Rated short-circuit current
according to IEC 6)
kA
65
65
65
65
65
65
65
Minimum short-circuit current 7)
A
1500
1500
1200
1600
2400
3000
3600
Power loss, max. 8)
at 50 Hz 690 V
kW
1.7
2.1
2.7
2.8
3.8
4.2
5
Cooling air requirement
m3/s
0.17
0.17
0.17
0.17
0.36
0.36
0.36
Sound pressure level
LpA (1 m) at 50/60 Hz
dB
67/68
67/68
67/68
67/68
67/73
67/73
67/73
Cable lengths
between converter and motor 9)
Shielded
m
300
300
300
300
300
300
300
Unshielded
m
450
450
450
450
450
450
450
Dimensions
Width for version A/C
mm
800/400
800/400
800/400
800/400
800/400
800/400
800/400
Height 10)
mm
2000
2000
2000
2000
2000
2000
2000
Depth
mm
600
600
600
600
600
600
600
Weight, approx.
(degree of protection IP20, without options) for version A/C
kg
460/225
460/225
460/225
460/225
670/300
670/300
670/300
Note: The power data in hp units is based on the NEC/CEC standards for the North American market.
For information on the line connection, motor connection and cabinet grounding, see Section Configuration.
1) Rated output of a typical 6-pole standard induction motor based on IL or IH for 3 AC 50 Hz 690 V.
2) The base-load current IL is based on a load cycle of 110% for 60 s or 150% for 10 s with a load cycle duration of 300 s. See Characteristic curves, Section Overload capability.
3) The base-load current IH is based on a duty cycle of 150% for 60 s or 160% for 10 s with a duty cycle duration of 300 s. See Characteristic curves, Section Overload capability.
4) The currents listed here are based on the rated output current.
5) If the drive control is to remain active after a main infeed failure, the converter must be externally supplied with 24 V DC. The following must also be taken into account: – CU320-2: 1 A – TM31: 0.5 A – AOP30: 0.2 A – SMC: 0.6 A – Current requirement of digital inputs/outputs.
6) In conjunction with the specified fuses or circuit breakers.
7) Minimum current required for reliably triggering the protective devices.
8) The specified power losses are the maximum values for a utilization of 100%. The values are lower under normal operating conditions.
9) Longer cable lengths for specific configurations are available on request.
10)Version A: The cabinet height increases by – 250 mm for degree of protection IP21 – 400 mm for degrees of protection IP23, IP43 and IP54 – 405 mm for options M13 and M78
Version C: The cabinet height increases by – 250 mm for degree of protection IP21 – 400 mm for degrees of protection IP23, IP43 and IP54
Line voltage 660 ... 690 V 3 AC
SINAMICS G150 converter cabinet units 6SL3710-1GH..-....
Single connection
33?3.A3
34?1.A3
34?7.A3
35?8.A3
37?4.A3
38?1.A3
Type rating
For IL at 50 Hz 690 V 1)
kW
315
400
450
560
710
800
For IH at 50 Hz 690 V 1)
kW
250
315
400
450
560
710
Output current
Rated current In
A
330
410
465
575
735
810
Base-load current IL 2)
A
320
400
452
560
710
790
Base-load current IH 3)
A
280
367
416
514
657
724
Input current
Rated input current 4)
A
343
426
483
598
764
842
Input current, max.
A
525
655
740
918
1164
1295
Current requirement, 24 V DC auxiliary power supply 5)
A
1.35
1.4
1.4
1.4
1.5
1.5
Rated short-circuit current
according to IEC 6)
kA
65
65
84
84
85
85
Minimum short-circuit current 7)
A
5200
5200
6200
8400
10500
10400/1800 8)
Power loss, max. 9)
at 50 Hz 690 V
kW
6.1
8.1
9.1
10.8
13.5
14.7
Cooling air requirement
m3/s
0.36
0.78
0.78
0.78
1.48
1.48
Sound pressure level
LpA (1 m) at 50/60 Hz
dB
67/73
72/75
72/75
72/75
72/75
72/75
Cable lengths
between converter and motor 10)
Shielded
m
300
300
300
300
300
300
Unshielded
m
450
450
450
450
450
450
Dimensions
Width for version A/C
mm
800/400
1200/600
1200/600
1200/600
1600/1000
1600/1000
Height 11)
mm
2000
2000
2000
2000
2000
2000
Depth
mm
600
600
600
600
600
600
Weight, approx.
(degree of protection IP20, without options) for version A/C
kg
670/300
780/670
780/670
840/670
1320/940
1360/980
Note: The power data in hp units is based on the NEC/CEC standards for the North American market.
For information on the line connection, motor connection and cabinet grounding, see Section Configuration.
1) Rated output of a typical 6-pole standard induction motor based on IL or IH for 3 AC 50 Hz 690 V.
2) The base-load current IL is based on a load cycle of 110% for 60 s or 150% for 10 s with a load cycle duration of 300 s. See Characteristic curves, Section Overload capability.
3) The base-load current IH is based on a duty cycle of 150% for 60 s or 160% for 10 s with a duty cycle duration of 300 s. See Characteristic curves, Section Overload capability.
4) The currents listed here are based on the rated output current.
5) If the drive control is to remain active after a main infeed failure, the converter must be externally supplied with 24 V DC. The following must also be taken into account: – CU320-2: 1 A – TM31: 0.5 A – AOP30: 0.2 A – SMC: 0.6 A – Current requirement of digital inputs/outputs.
6) In conjunction with the specified fuses or circuit breakers.
7) Minimum current required for reliably triggering the protective devices.
8) For option L26 (version A) the low value applies.
9) The specified power losses are the maximum values for a utilization of 100%. The values are lower under normal operating conditions.
10) Longer cable lengths for specific configurations are available on request.
11)Version A: The cabinet height increases by – 250 mm for degree of protection IP21 – 400 mm for degrees of protection IP23, IP43 and IP54 – 405 mm for options M13 and M78
Version C: The cabinet height increases by – 250 mm for degree of protection IP21 – 400 mm for degrees of protection IP23, IP43 and IP54
Technical specifications for parallel connection
SINAMICS G150 converter cabinet units, version A 6SL3710-2GE..-....
SINAMICS G150 converter cabinet units, version A 6SL3710-2GF..-....
Parallel connection
41?1AA3
41?4AA3
41?6AA3
38?6AA3
41?1AA3
41?4AA3
Line voltage
380 ... 480 V 3 AC
500 ... 600 V 3 AC
Type rating
For IL1)
kW
630
710
900
630
710
1000
For IH1)
kW
500
560
710
560
630
800
For IL at 60 Hz 460 V or 575 V 2)
hp
900
1000
1250
900
1000
1250
For IH at 60 Hz 460 V or 575 V 2)
hp
700
900
1000
800
900
1000
Output current
Rated current In 3)
A
1120
1380
1560
860
1070
1360
Base-load current IL3)4)
A
1092
1340
1516
836
1036
1314
Base-load current IH3)5)
A
850
1054
1294
770
950
1216
Input current
Rated input current 3)6)
A
1174
1444
1624
904
1116
1424
Input current, max.
A
1800
2215
2495
1388
1708
2186
Current requirement, 24 V DC auxiliary power supply 7)
A
2.8
2.8
3
2.8
2.8
3
Rated short-circuit current
according to IEC 8)
kA
2 ? 65
2 ? 65
2 ? 65
2 ? 65
2 ? 65
2 ? 84
Minimum short-circuit current 9)
A
2 ? 1000
2 ? 10500
2 ? 1800
2 ? 6200
2 ? 8400
2 ? 10500
Power loss, max. 10)
At 50 Hz 400 V / 500 V
kW
16.2
19
19.9
15.4
17.2
23.8
At 60 Hz 460 V / 575 V
kW
16.6
19.4
20.4
15
16.8
25
Cooling air requirement
m3/s
1.56
1.56
1.56
1.56
1.56
2.96
Sound pressure level
LpA (1 m) at 50/60 Hz
dB
73/76
73/76
73/76
75/78
75/78
75/78
Cable lengths
between converter and motor 11)
Shielded
m
300
300
300
300
300
300
Unshielded
m
450
450
450
450
450
450
Dimensions
Width 12)
mm
2400
2400
2400
2400
2400
3200
Height 13)
mm
2000
2000
2000
2000
2000
2000
Depth
mm
600
600
600
600
600
600
Weight, approx.
(degree of protection IP20, without options)
kg
1700
1710
2130
1700
1700
2620
Note: The power data in hp units is based on the NEC/CEC standards for the North American market.
For information on the line connection, motor connection and cabinet grounding, see Section Configuration.
1) Rated output of a typical 6-pole standard induction motor based on IL or IH at 3 AC 50 Hz 400 V, 500 V or 690 V.
2) Rated output of a typical 6-pole standard induction motor based on IL or I or H at 3 AC 60 Hz 460 V or 575 V.
3) The currents specified here are the total current of both converter sections.
4) The base-load current IL is based on a load cycle of 110% for 60 s or 150% for 10 s with a load cycle duration of 300 s. See Characteristic curves, Section Overload capability.
5) The base-load current IH is based on a duty cycle of 150% for 60 s or 160% for 10 s with a duty cycle duration of 300 s. See Characteristic curves, Section Overload capability.
6) The currents listed here are based on the rated output current.
7) If the drive control is to remain active after a main infeed failure, the converter must be externally supplied with 24 V DC. The following must also be taken into account: – CU320-2: 1 A – TM31: 0.5 A – AOP30: 0.2 A – SMC: 0.6 A – Current requirement of digital inputs/outputs.
8) In conjunction with the specified fuses or circuit breakers.
9) Minimum current required for reliably triggering the protective devices.
10) The specified power losses are the maximum values for a utilization of 100%. The values are lower under normal operating conditions.
11) Longer cable lengths for specific configurations are available on request.
12) The power units connected in parallel are supplied as two transport units.
13) The cabinet height increases by – 250 mm for degree of protection IP21 – 400 mm for degrees of protection IP23, IP43 and IP54 – 405 mm for options M13 and M78
SINAMICS G150 converter cabinet units, version A 6SL3710-2GH..-....
Parallel connection
41?1AA3
41?4AA3
41?5AA3
41?8EA3
42?0EA3
42?2EA3
42?4E A3
42?7E A3
Line voltage
660 ... 690 V 3 AC
Type rating
For IL1)
kW
1000
1350
1500
1750
1950
2150
2400
2700
For IH1)
kW
900
1200
1350
1500
1750
1950
2150
2400
For IL at 60 Hz 460 V or 575 V 2)
hp
–
–
–
–
–
–
–
–
For IH at 60 Hz 460 V or 575 V 2)
hp
–
–
–
–
–
–
–
–
Output current
Rated current In 3)
A
1070
1360
1500
1729
1948
2158
2413
2752
Base-load current IL3)4)
A
1036
1314
1462
1720
1940
2150
2390
2685
Base-load current IH3)5)
A
950
1216
1340
1547
1742
1930
2158
2463
Input current
Rated input current 3)6)
A
1116
1424
1568
1800
2030
2245
2510
2865
Input current, max.
A
1708
2186
2406
2765
3115
3450
3860
4400
Current requirement, 24 V DC auxiliary power supply 7)
A
2.8
2.8
3
4.7
4.7
4.7
4.7
6
Rated short-circuit current
according to IEC 8)
kA
2 ? 65
2 ? 84
2 ? 84
2 ? 85
2 ? 85
2 ? 85
2 ? 85
2 ? 85
Minimum short-circuit current 9)
A
2 ? 8400
2 ? 10500
2 ? 1800
2 ? 1800
2 ? 2000
2 ? 2300
2 ? 2500
2 ? 3000
Power loss, max. 10)
at 50 Hz 690 V
kW
21.3
26.6
29
35
38
40
46
52
Cooling air requirement
m3/s
1.56
2.96
2.96
3.67
3.67
3.67
3.67
5.15
Sound pressure level
LpA (1 m) at 50/60 Hz
dB
75/78
75/78
75/78
75/78
75/78
75/78
75/78
75/78
Cable lengths
between converter and motor 11)
Shielded
m
300
300
300
300
300
300
300
300
Unshielded
m
450
450
450
450
450
450
450
450
Dimensions
Width 12)
mm
2400
3200
3200
3600
3600
3600
3600
4400
Height 13)
mm
2000
2000
2000
2000
2000
2000
2000
2000
Depth
mm
600
600
600
600
600
600
600
600
Weight, approx.
(degree of protection IP20, without options)
kg
1700
2620
2700
3010
3010
3070
3860
4580
Note: The power data in hp units is based on the NEC/CEC standards for the North American market.
For information on the line connection, motor connection and cabinet grounding, see Section Configuration.
1) Rated output of a typical 6-pole standard induction motor based on IL or IH at 3 AC 50 Hz 400 V, 500 V or 690 V.
2) Rated output of a typical 6-pole standard induction motor based on IL or I or H at 3 AC 60 Hz 460 V or 575 V.
3) The currents specified here are the total current of both converter sections.
4) The base-load current IL is based on a load cycle of 110% for 60 s or 150% for 10 s with a load cycle duration of 300 s. See Characteristic curves, Section Overload capability.
5) The base-load current IH is based on a duty cycle of 150% for 60 s or 160% for 10 s with a duty cycle duration of 300 s. See Characteristic curves, Section Overload capability.
6) The currents listed here are based on the rated output current.
7) If the drive control is to remain active after a main infeed failure, the converter must be externally supplied with 24 V DC. The following must also be taken into account: – CU320-2: 1 A – TM31: 0.5 A – AOP30: 0.2 A – SMC: 0.6 A – Current requirement of digital inputs/outputs.
8) In conjunction with the specified fuses or circuit breakers.
9) Minimum current required for reliably triggering the protective devices.
10) The specified power losses are the maximum values for a utilization of 100%. The values are lower under normal operating conditions.
11) Longer cable lengths for specific configurations are available on request.
12) The power units connected in parallel are supplied as two transport units.
13) The cabinet height increases by – 250 mm for degree of protection IP21 – 400 mm for degrees of protection IP23, IP43 and IP54 – 405 mm for options M13 and M78
skener.ru
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Àðìàòóðà DENDOR
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Äàò÷èêè è èçìåðèòåëè
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ðåãóëÿòîðû è ðåãèñòðàòîðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ïíåâìàòè÷åñêîå îáîðóäîâàíèå
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Êðàíû è Êëàïàíû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Èçìåðèòåëüíûå ïðèáîðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ñèñòåìû áåñïðîâîäíîãî óïðàâëåíèÿ «óìíûé äîì»
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Áåñêîíòàêòíûå âûêëþ÷àòåëè Êîíå÷íûå âûêëþ÷àòåëè Îïòè÷åñêèå äàò÷èêè Ýíêîäåðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Óñòàíîâêà óìÿã÷åíèÿ
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Óñòàíîâêà îáåçæåëåçèâàíèÿ