Process media | - Suitable for virtually any sonically conductive fluid, including hazardous liquids
- Aggregate state: Light slurry and liquid
|
Process variables | - Volume flow
- Mass flow
- Flow velocity
- Sound velocity
- Standard volume flow
(hydrocarbon variant only) - Density
- Kinematic viscosity
- Pressure
- Medium temperature
- Specific gravity
(hydrocarbon variant only) - Totalizer 1
- Totalizer 2
- Totalizer 3
- Standard density
(hydrocarbon variant only) - Standard specific gravity
(hydrocarbon variant only) - Standardizing factor
(hydrocarbon variant only) - LiquIdent
(hydrocarbon variant only) - API gravity
(hydrocarbon variant only) - Standard API gravity
(hydrocarbon variant only) - Standard kinematic viscosity
(hydrocarbon variant only) - Liquid identifier
(hydrocarbon variant only)
|
Current output | |
Current | 0 ... 20 mA or 4 ... 20 mA (channel 1 only 4 ... 20 mA) |
Load | < 500 О© per channel |
Time constant | 0 ... 100 s adjustable |
Digital output1) | |
Pulse | 41.6 µs ... 5 s pulse duration |
Frequency | 0 ... 10 kHz, 50 % duty cycle, 120 % overscale provision |
Time constant | 0 ... 100 s adjustable |
Active | 0 ... 22 V DC, 30 mA, short-circuit-protected |
Passive | 3 ... 30 V DC, max. 110 mA |
Relay | |
Type | SPDT dry contact relay |
Load | 30 V AC/100 mA |
Functions | Alarm level, alarm number, limit, flow direction |
Digital input | |
Voltage | 15 ... 30 V DC (2 ... 15 mA) |
Current | 4 ... 20 mA |
Functionality | Reset totalizer 1, 2 and 3, force output, freeze process values, zero point adjustment |
Galvanic isolation | All inputs and outputs are galvanically isolated, isolation voltage 500 V |
Alarm and warning limit | Available for all process values |
Totalizer | Three counters for forward, net and reverse flow |
Display | - Background illumination with alphanumerical text to indicate flow rate, totalized values, settings and faults
- Adjustable damping constant of 0 ... 100 s
- Reverse flow indicated by negative sign
|
SD card functions | |
Ambient temperature | |
Operation | |
| -40 ... +60 °C (-40 ... +140 °F), humidity max. 95 % |
| -20 ... +60 °C (-4 ... +140 °F) |
Storage | |
| -40 ... +70 °C (-40 ... +158 °F), humidity max. 95 % |
Communication | HART 7.5 |
Modbus RTU RS 485 |
Enclosure | |
Material | Aluminum |
Rating | IP66/67, NEMA 4X to IEC 529 and DIN 40050 (1 mH2O for 30 min.) |
Mechanical load | 18 ... 400 Hz random, 3.17 g RMS, in all directions |
Supply voltage | |
Supply | 20 ... 27 V DC 100 ... 240 V AC, 47 ... 63 Hz |
Fluctuation | No limit |
Power consumption | 20 W/22 VA |
NAMUR | NAMUR requirements fulfilled when using Triax cable. Within the value limits according to "General requirements" with error criteria A in accordance with NE 21. Icons according to NE 107 status. |
Environment Environmental conditions according to IEC/EN/UL 61010‑1 | - Altitude up to 2 000 m
- Pollution degree 2
- Overvoltage category II
|
Maintenance | The flowmeter has a built-in error log/pending menu which should be inspected on a regular basis |
Cable glands | Cable glands are available in nylon, nickel plated brass or stainless steel (316L/W1.4404) |
Approvals | |
For non-hazardous area | No approval required |
For hazardous area | |
| |
| Zone 0, 1, 2 |
- Transmitter with integrated DSL
| Zone 2 |
| |
| Class 1, Div 1, 2 |
| Class 1, Div 2 |
| |
| Class 1, Div 1, 2 (Zone 0, 1, 2) |
- Transmitter with integrated DSL
| Class 1, Div 2 (Zone 2) |
- Combination Approval:
ATEX, IECEx, FM, FM Canada
| |
| Zone 0, 1, 2 (Div 1, 2) |
- Transmitter with integrated DSL
| Zone 2 (Div 2) |
Certificates | |
CE conformity marking | - Low voltage directive
- WEEE
- RoHS
|
EMC performance | |
Emission | CISPR 11:2009/A1:2010 and EN 55011:2009/A1:2010 |
Immunity | IEC/EN 61326‑1:2013 |