SITRANS FUG1010 | |
Input | |
Flow range | ± 30 m/s (± 100 ft/s), bidirectional |
Flow sensitivity | 0.0003 m/s (0.001 ft/s), flow rate independent |
Minimum pressure | 7 … 10 bar (100 … 145 psi), typical (gas composition and application dependent; plastic pipes support operation at atmospheric pressure) |
Pipe size | 25 mm … 1.52 m (1”… 48“) (for other sizes, consult factory) |
Analog inputs | Current: 20 mA, programmable |
Output | |
Standard outputs | - Current: 20 mA, a programmable, standard
Additional 2 x optional - Voltage: 10 V DC, menu programmable
- Open collector digital pulses (quadrature)
- Pulse rate: 5 kHz
- VT100 RS 232
|
Extended outputs | - HART, BACnet MSTP/BACnet IP, Modbus RTU & TCP/IP, Ethernet IP, Johnson N2
|
Status/Alarm I/O | - Programmable form C relays
- Programmable N.O. Mer. Wet. Relays optional
- 1 Totalizer clear switch input
- 1 Totalizer hold switch input
|
Accuracy | |
Typical accuracy | 1 % … 2 % of actual volume reading (higher accuracy is pipe condition and flow profile dependent) |
Calibratable Accuracy | ± 0.2 ... 0.5 % of flow |
Repeatability | 0.05 % … 0.1 %, of actual volume reading, for 1.5 … 30 m/s (5 … 100 ft/s) velocities (pipe condition dependent) |
Zero drift | 0.0003 m/s (0.001 ft/s), with ZeroMatic Path active |
Data refresh rate | 5 Hz |
Rated operation conditions | |
Degree of protection | |
| IP65 (NEMA 4X) |
- Wall mount explosionproof
| IP66 (NEMA 7) |
Gas temperature | -40 … +60 °C (-40 … +140 °F) (for higher temperatures consult factory) |
Ambient temperature | -18 … +60 °C (0 … 140 °F) |
Design | |
Dimensions | see SITRANS F US Clamp-on "System info and selection guide" |
Weight | see diagrams |
Power supply | |
- For IP65 (NEMA 4X) and
IP66 (NEMA 7)
| - 90 … 240 V AC,
50 … 60 Hz (30 VA) or 9 … 36 V DC (12 W)
|
Indication and operation | |
Data logger memory | 1 Mbyte, programmable for 17 data functions |
Display | |
- IP65 (NEMA 4X) and
IP66 (NEMA 7) enclosures
| 128 x 240 pixel LCD with backlight |
Keypad | |
- IP65 (NEMA 4X) and
IP66 (NEMA 7) enclosures
| 33 keypad buttons with tactile feedback |
Language options | English, Spanish, German, Italian, French |
Certificates and approvals | |
IP65 (NEMA 4X) wall mount flow display transmitter ratings |
FM and CSA | N-I Class I, Div 2 S Class II, Div 2 I.S. Class I, II, Div 1 |
CE | EMC Directive 2014/30/EU ATEX Directive 2014/34/EU |
C-TICK | |
ATEX | - Transmitter:
Ex II (1) G [Ex ia] IIC Ex II 3 (1) G Ex nC [ia] IIC T5 - Sensors:
Ex II 1 G Ex ia IIC T5
|
IP66 (NEMA 7) wall mount explosionproof enclosure ratings |
FM and CSA | XP Class I, Div 1 D-I Class II, Div 1 N-I Class I, Div 2 S Class II, Div 2 I.S. Class I, II, Div 1 |
CE | EMC Directive 2014/30/EU ATEX Directive 2014/34/EU |
C-TICK | |
ATEX | - Transmitter:
Ex II (1) G [Ex ia] IIC Ex II 3 (1) G Ex nC [ia] IIC T5 Ex II 2 (1) G Ex d [ia IIC] IIB+H2 T5 - Sensors:
Ex II 1 G Ex ia IIC T5
|