General information | | | |
Product type designation | DI 16x24 VDC ST | DI 8xNAMUR HF | DI 4x120 ... 230 V AC ST |
Firmware version | | | |
| Yes | Yes | Yes |
usable BaseUnits | BU type A0 | BU type A0 | BU type B1 |
Color code for module-specific color identification plate | CC00 | CC01 | CC41 |
Product function | | | |
| Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 |
Operating mode | | | |
| Yes | Yes | Yes |
| No | No | No |
| No | No | No |
| No | No | No |
Supply voltage | | | |
Rated value (DC) | 24 V | 24 V | |
permissible range, lower limit (DC) | 19.2 V | 19.2 V | |
permissible range, upper limit (DC) | 28.8 V | 28.8 V | |
Rated value (AC) | | | 230 V |
Reverse polarity protection | Yes | Yes | No |
Input current | | | |
Current consumption (rated value) | | | 10 mA |
Current consumption, max. | 90 mA | | |
Encoder supply | | | |
Number of outputs | | 8 | 4 |
Short-circuit protection | No | Yes | No; when using BU type B1, a fuse with 10 A tripping current must be provided |
Output current | | | |
| | | 10 A |
24 V encoder supply | | | |
| No | No | No |
| No | No | No |
Power loss | | | |
Power loss, typ. | 1.7 W | 1.5 W | 1 W; Active power, load voltage 230 V, all inputs connected with 230 V, 50 Hz |
Address area | | | |
Address space per module | | | |
| 2 byte; + 2 bytes for QI information | 1 byte; + 1 byte for QI information | 1 byte; + 1 byte for QI information |
| | | 1 byte |
Selection of BaseUnit for connection variants | | | |
| | BU type A0 | BU type B1 |
| | BU type A0 | BU type B1 |
| | BU type A0 + external terminals | BU type B1 |
| | BU type A0 + external terminals | BU type B1 + external terminals |
Digital inputs | | | |
Number of digital inputs | 16; > +60 °C, number of simultaneously controllable inputs max. 4 | 8; > +60 °C number of simultaneously controllable inputs max. 4 (no adjacent points) | 4 |
Digital inputs, parameterizable | | Yes | |
Source/sink input | P-reading | | No |
Input characteristic curve in accordance with IEC 61131, type 1 | Yes | | |
Input characteristic curve in accordance with IEC 61131, type 2 | No | | |
Input characteristic curve in accordance with IEC 61131, type 3 | Yes | | Yes |
Pulse extension | No | Yes; 0.5 s, 1 s, 2 s | No |
Edge evaluation | | Yes; rising edge, falling edge, edge change | |
Signal change flutter | | Yes; 2 to 32 signal changes | |
Flutter observation window | | Yes; 0.5 s, 1 s to 100 s in 1-s steps | |
Input voltage | | | |
| DC | DC | 120/230 V AC (47 Hz to 63 Hz) |
| 24 V | 8.2 V | |
| | | 230 V |
| -30 to +5V | | 0V AC to 40V AC |
| +11 to +30V | | 74 V AC to 264 V AC |
Input current | | | |
| 2.5 mA | | 10.8 mA |
for 10 k switched contact | | | |
| | 0.35 to 1.2 mA | |
| | 2.1 to 7 mA | |
for unswitched contact | | | |
| | 0.5 mA | |
| | typ. 8 mA | |
for NAMUR encoders | | | |
| | 0.35 to 1.2 mA | |
| | 2.1 to 7 mA | |
Input delay (for rated value of input voltage) | | | |
| | 300 ms | |
for standard inputs | | | |
| Yes; 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms (in each case + delay of 30 to 500 µs, depending on line length) | No | No |
| 0.05 ms | | 1.5 ms |
| 20 ms | | 4 ms |
| 0.05 ms | | 10 ms |
| 20 ms | | 10 ms |
for interrupt inputs | | | |
| No | | |
for counter/technological functions | | | |
| No | | |
for NAMUR inputs | | | |
| | 12 ms | |
| | 12 ms | |
Cable length | | | |
| 1 000 m | 200 m | 1 000 m |
| 600 m | | 600 m |
Encoder | | | |
Connectable encoders | | | |
| | Yes | |
| | Yes | |
| | Yes | |
| Yes | | Yes |
| 1.5 mA | | |
Isochronous mode | | | |
Isochronous operation (application synchronized up to terminal) | No | No | No |
Interrupts/diagnostics/status information | | | |
Diagnostics function | Yes | Yes | |
Alarms | | | |
| Yes | Yes; channel by channel | No |
| | Yes; Parameterizable, channels 0 to 7 | No |
Diagnostic messages | | | |
| Yes | Yes | |
| Yes | Yes | |
| Yes | Yes | |
| No | Yes; channel by channel | |
| Yes; Module-wise | Yes; channel by channel | No |
| No | Yes; channel by channel | No |
| Yes | Yes | Yes |
Diagnostics indication LED | | | |
| Yes; green PWR LED | Yes; green PWR LED | Yes; green PWR LED |
| Yes; Green LED | Yes; Green LED | Yes; Green LED |
| No | Yes; Red LED | No |
| Yes; green/red DIAG LED | Yes; green/red DIAG LED | Yes; green/red DIAG LED |
Potential separation | | | |
Potential separation channels | | | |
| No | No | No |
| Yes | Yes | Yes |
| No | Yes | No |
Isolation | | | |
Isolation tested with | 707 V DC (type test) and according to EN 50155 (routine test) | 707 V DC (type test) and according to EN 50155 (routine test) | 2 300 V AC for 1 minute (type test) and according to EN 50155 (routine test) |
Standards, approvals, certificates | | | |
Railway application | | | |
| Yes; EMC for rail vehicles | Yes; EMC for rail vehicles | Yes; EMC for rail vehicles |
| Yes; EMC for signal and telecommunications systems | Yes; EMC for signal and telecommunications systems | Yes; EMC for signal and telecommunications systems |
| Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC | Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC | Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC |
| Yes; Rail vehicles - see ambient conditions | Yes; Rail vehicles - see ambient conditions | Yes; Rail vehicles - see ambient conditions |
| Yes; Stationary electrical equipment - see ambient conditions | Yes; Stationary electrical equipment - see ambient conditions | Yes; Stationary electrical equipment - see ambient conditions |
| Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track) | Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track) | Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track) |
| Yes; Rail vehicles - temperature class Tx, horizontal mounting position, salt spray Class ST2 | Yes; Rail vehicles - temperature class Tx, horizontal mounting position, salt spray Class ST2 | Yes; Rail vehicles - temperature class Tx, horizontal mounting position, salt spray Class ST2 |
| Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B | Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B | Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B |
| Yes; Rail vehicles - verification on request | Yes; Rail vehicles - verification on request | Yes; Rail vehicles - verification on request |
Ambient conditions | | | |
Ambient temperature during operation | | | |
| -40 °C; = Tmin | -40 °C; = Tmin | -40 °C; = Tmin |
| 70 °C; = Tmax; +85 °C for 10 min (Tx acc. to EN 50155) | 70 °C; = Tmax; +85 °C for 10 min (Tx acc. to EN 50155) | 70 °C; = Tmax; +85 °C for 10 min (Tx acc. to EN 50155) |
Altitude during operation relating to sea level | | | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) |
Relative humidity | | | |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 100 %; incl. condensation / frost permitted (no commissioning under condensation conditions) |
Use in stationary industrial systems | | | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Use on land craft, rail vehicles and special-purpose vehicles | | | |
| Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request | Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request | Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request |
| Yes; Class 5C3 (RH < 75%) including salt spray according to EN 50155 (ST2). The supplied plug covers must remain in place over the unused interfaces during operation! | Yes; Class 5C3 (RH < 75%) including salt spray according to EN 50155 (ST2). The supplied plug covers must remain in place over the unused interfaces during operation! | Yes; Class 5C3 (RH < 75%) including salt spray according to EN 50155 (ST2). The supplied plug covers must remain in place over the unused interfaces during operation! |
| Yes; Class 5S3 including sand and dust. The supplied plug covers must remain in place over the unused interfaces during operation! | Yes; Class 5S3 including sand and dust. The supplied plug covers must remain in place over the unused interfaces during operation! | Yes; Class 5S3 including sand and dust. The supplied plug covers must remain in place over the unused interfaces during operation! |
Dimensions | | | |
Width | 15 mm | 15 mm | 20 mm |
Height | 73 mm | 73 mm | 73 mm |
Depth | 58 mm | 58 mm | 58 mm |
Weights | | | |
Weight, approx. | 28 g | 32 g | 36 g |
Other | | | |
Note: | For use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A Online Support article 109736776 | For use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A Online Support article 109736776 | For use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A Online Support article 109736776 |