General information | |
Product type designation | ET 200SP, DI 16x 24 V DC ST, PU 1 |
Product function | |
| Yes; I&M0 to I&M3 |
Operating mode | |
| Yes |
| No |
| No |
| No |
Supply voltage | |
Type of supply voltage | DC |
Rated value (DC) | 24 V |
Reverse polarity protection | Yes |
Encoder supply | |
Short-circuit protection | No |
24 V encoder supply | |
| No |
| No |
Digital inputs | |
Number of digital inputs | 16; > +60 °C, number of simultaneously controllable inputs max. 4 |
Source/sink input | P-reading |
Input characteristic curve in accordance with IEC 61131, type 1 | Yes |
Input characteristic curve in accordance with IEC 61131, type 2 | No |
Input characteristic curve in accordance with IEC 61131, type 3 | Yes |
Pulse extension | No |
Input voltage | |
| DC |
| 24 V |
| -30 to +5V |
| +11 to +30V |
Input current | |
| 2.5 mA |
Input delay (for rated value of input voltage) | |
for standard inputs | |
| Yes; 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms (in each case + delay of 30 to 500 µs, depending on line length) |
for interrupt inputs | |
| No |
for counter/technological functions | |
| No |
Cable length | |
| 1 000 m |
| 600 m |
Encoder | |
Connectable encoders | |
| Yes |
| 1.5 mA |
Isochronous mode | |
Isochronous operation (application synchronized up to terminal) | No |
Interrupts/diagnostics/status information | |
Diagnostics function | Yes |
Alarms | |
| Yes |
Diagnostic messages | |
| Yes |
| Yes |
| Yes |
| No |
| Yes; Module-wise |
| No |
| Yes |
Diagnostics indication LED | |
| Yes; green PWR LED |
| Yes; Green LED |
| No |
| Yes; green/red DIAG LED |
Potential separation | |
Potential separation channels | |
| Yes |
Isolation | |
Isolation tested with | 707 V DC (type test) and according to EN 50155 (routine test) |
Standards, approvals, certificates | |
Railway application | |
| Yes; EMC for rail vehicles |
| Yes; EMC for signal and telecommunications systems |
| Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC |
| Yes; Rail vehicles - see ambient conditions |
| Yes; Stationary electrical equipment - see ambient conditions |
| Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track) |
| Yes; Rail vehicles - temperature class Tx, horizontal mounting position, salt spray Class ST2 |
| Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B |
| Yes; Rail vehicles - verification on request |
Ambient conditions | |
Ambient temperature during operation | |
| -40 °C; = Tmin |
| 70 °C; = Tmax; +85 °C for 10 min (Tx acc. to EN 50155) |
Extended ambient conditions | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) |
Relative humidity | |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Resistance | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 5B2 mold and fungal spores (excluding fauna). The supplied plug covers must remain in place over the unused interfaces during operation! |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 5C3 (RH < 75%) including salt spray according to EN 50155 (ST2). The supplied plug covers must remain in place over the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 5S3 including sand and dust. The supplied plug covers must remain in place over the unused interfaces during operation! |
Dimensions | |
Width | 15 mm |
Weights | |
Weight, approx. | 28 g |
Other | |
Note: | For use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A Online Support article 109736776 |