General information | |
Product brand name | SIPLUS |
Product category | Condition Monitoring IEPE |
Product designation | CMS1200 SM 1281 Condition Monitoring |
Product description | S7-1200 module for the monitoring of vibrations on mechanical components based on parameters and frequency-selective analysis functions |
Physical measuring principle | Vibration acceleration |
Measurement range vibration frequency, min. | 0.1 Hz |
Measurement range vibration frequency, max. | 10 000 Hz |
Installation type/mounting | |
Mounting type | Rail or wall mounting |
Mounting position | Horizontal, vertical |
Recommended mounting position | Horizontal |
Supply voltage | |
Type of supply voltage | DC |
Rated value (DC) | |
| Yes |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
Input current | |
Current consumption, typ. | 200 mA |
Current consumption, max. | 250 mA |
from backplane bus 5 V DC, typ. | 80 mA |
from backplane bus 5 V DC, max. | 85 mA |
Memory | |
Total memory capacity | 1 Gbyte |
Hardware configuration | |
Design of hardware configuration | Modular, up to 7 modules per CPU |
Speed input | |
Number of speed inputs | 1 |
Protocols | |
| Yes |
Sensor input | |
Number of IEPE sensor inputs | 4 |
Sampling frequency, max. | 46 875 Hz |
Interfaces | |
Type of data transmission | Exporting of raw data as WAV file for further analyses (e.g. using CMS X-Tools) can be downloaded via browser |
Ethernet interface | Yes |
Protocols | |
Bus communication | Yes |
Web server | |
| Yes |
Interrupts/diagnostics/status information | |
Alarms | |
| Yes |
Diagnostics indication LED | |
| No |
| Yes |
| Yes |
Integrated Functions | |
Monitoring functions | |
| Yes; Cable break and short-circuit |
| Yes |
| Yes |
| Yes |
| Yes |
| Yes |
Degree and class of protection | |
Degree of protection acc. to EN 60529 | |
| Yes |
Standards, approvals, certificates | |
Certificate of suitability | CE |
CE mark | Yes |
UL approval | Yes |
EAC (formerly Gost-R) | Yes |
China RoHS compliance | Yes |
Device tag according to DIN EN 81346-2 | P |
Ambient conditions | |
Free fall | |
| 0.3 m; five times, in product package |
Ambient temperature during operation | |
| -20 °C |
| 60 °C |
| -20 °C |
| 45 °C |
Ambient temperature during storage/transportation | |
| -40 °C |
| 70 °C |
Air pressure acc. to IEC 60068-2-13 | |
| 795 hPa |
| 1 080 hPa |
| 660 hPa |
| 1 080 hPa |
Relative humidity | |
| 5 % |
| 95 % |
Software | |
Browser software required | Web browser Mozilla Firefox (ESR31) or Microsoft Internet Explorer (10/11) |
Connection method | |
required front connector | Yes |
Design of electrical connection | Screw connection |
Mechanics/material | |
Material of housing | Plastic: polycarbonate, abbreviation: PC- GF 10 FR |
Enclosure material (front) | |
| Yes |
Dimensions | |
Width | 70 mm |
Height | 112 mm |
Depth | 75 mm |
Weights | |
Weight | 260 g |