General information | |
Product type designation | F-PM-E 24 V DC/8 A PPM ST |
Product function | |
| Yes; I&M0 to I&M3 |
Engineering with | |
| V2.3 |
| V2.31 |
Supply voltage | |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes |
Input current | |
Current consumption (rated value) | 75 mA; without load |
Current consumption, max. | 21 mA; From the backplane bus |
Output voltage | |
Rated value (DC) | 24 V |
Encoder supply | |
Number of outputs | 2 |
Short-circuit protection | Yes; Electronic (response threshold 0.7 A to 2.1 A) |
Output current | |
| 0.3 A |
24 V encoder supply | |
| Yes; min. L+ (-1.5 V) |
| Yes |
| 600 mA; Total current of all encoders |
Power | |
Power available from the backplane bus | 70 mW |
Power loss | |
Power loss, typ. | 5 W |
Address area | |
Address space per module | |
| 7 byte |
| 5 byte |
Digital inputs | |
Number of digital inputs | 2 |
Source/sink input | Yes; P-reading |
Input characteristic curve in accordance with IEC 61131, type 1 | Yes |
Input voltage | |
| DC |
| 24 V |
| -30 to +5V |
| +15 to +30V |
Input current | |
| 3.7 mA |
Input delay (for rated value of input voltage) | |
for standard inputs | |
| Yes |
| 0.4 ms |
| 20 ms |
| 0.4 ms |
| 20 ms |
for counter/technological functions | |
| No |
Cable length | |
| 1 000 m |
| 500 m |
Digital outputs | |
Number of digital outputs | 1 |
Short-circuit protection | Yes |
| > 14.8 A |
Open-circuit detection | Yes |
| 8 mA |
Overload protection | Yes |
| 8.8 A |
Limitation of inductive shutdown voltage to | max. 1.5 V |
Switching capacity of the outputs | |
| 8 A |
| 100 W |
Load resistance range | |
| 3 Ω |
| 2 000 Ω |
Output voltage | |
| 24 V; L+ (-0.5 V) |
Output current | |
| 8 A |
| 1.5 mA; PP-switching: max. 1.5 mA; PM-switching: max. 1 mA |
Switching frequency | |
| 10 Hz; Symmetrical |
| 0.1 Hz; according to IEC 60947-5-1, DC-13, symmetrical |
| 4 Hz; Symmetrical |
Total current of the outputs | |
| 8 A; Note derating data in the manual |
| 8 A; Note derating data in the manual |
Cable length | |
| 1 000 m |
| 500 m |
Interrupts/diagnostics/status information | |
Diagnostics function | Yes, "Alarms/diagnostic messages" section in the manual |
Substitute values connectable | No |
Alarms | |
| Yes |
| No |
Diagnostics indication LED | |
| Yes; Green LED |
| Yes; Red LED |
| Yes; green PWR LED |
| Yes; Green LED |
| Yes; Red LED |
| Yes; green/red DIAG LED |
Potential separation | |
Potential separation channels | |
| No |
| Yes |
| No |
Permissible potential difference | |
between different circuits | 60 V DC/75 V AC |
Isolation | |
Isolation tested with | 707 V DC (type test) |
Highest safety class achievable in safety mode | |
| SIL 3 |
Ambient conditions | |
Ambient temperature during operation | |
| -25 °C |
| 60 °C |
| -25 °C |
| 50 °C |
Altitude during operation relating to sea level | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) |
Relative humidity | |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Use in stationary industrial systems | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Dimensions | |
Width | 20 mm |
Height | 72 mm |
Depth | 55 mm |
Weights | |
Weight, approx. | 70 g |