General information | | |
Product brand name | SIPLUS |
Type of control of heat emitters | Half-wave control |
Installation type/mounting | | |
Mounting type | screw fixing |
Mounting position | vertical |
Type of ventilation | Self-ventilation |
Supply voltage | | |
Type of supply voltage | AC |
Rated value (AC) | 400 V |
Line frequency | | |
| 50 Hz |
| 60 Hz |
| 5 % |
Power supply for the electronics | | |
Type of voltage | DC |
Supply voltage for electronics | 24 V |
Relative symmetrical tolerance of the input voltage | 20 % |
Input current | | |
Current consumption for the electronics, max. | 0.25 A |
Power electronics | | |
Type of load | Ohmic load |
Power capacity, max. | 25.2 kW |
Switching capacity current per phase, max. | 63 A |
Rated conditional short-circuit current (Iq) | 25 kA |
Heating power | | |
| 9 |
| 1 |
| 400 V |
| 10 A |
| Fuse 16 A | Fuse 15 A |
Fan control | | |
| 230 V | |
| 60 W | |
| 500 W | |
| Fuse 4 A | |
Integration and conversion time/resolution per channel | | |
| Connector, 5-pole |
| Connector, 20-pole + PE |
| 20x (1.5 ... 4 mmІ), 1x PE (1.5 ... 16 mmІ) | 18x (1.5 ... 4 mmІ), 1x PE (1.5 ... 16 mmІ) |
| 20x (18 ... 12) | 18x (18 ... 12) |
Interfaces | | |
PROFIBUS DP | | |
| 12 Mbit/s |
| ECOFAST |
Protocols | | |
PROFIBUS DP | Yes |
Interrupts/diagnostics/status information | | |
Number of status displays | 2 |
LED status display | LED green = status indicator, LED red = fault indicator |
Diagnostics function | Voltage diagnostics |
Integrated Functions | | |
Monitoring functions | | |
| NTC thermistor |
Potential separation | | |
Design of electrical isolation | Optocoupler between main circuit and PELV |
between the outputs | No |
Isolation | | |
Degree of pollution | 2 |
EMC | | |
EMC interference emission | in accordance with IEC 61000-6-4:2007 + A1:2011 |
Electrostatic discharge acc. to IEC 61000-4-2 | 4 kV contact discharge / 8 kV air discharge |
Field-related interference acc. to IEC 61000-4-3 | 10 V/m (80 ... 1 000 MHz), 3 V/m (1.4 ... 2.0 GHz), 1 V/m (2.0 ... 2.7 GHz) |
Conducted interference due to burst acc. to IEC 61000-4-4 | 2 kV power supply lines / 1 kV signal lines |
Conducted interference due to surge acc. to IEC 61000-4-5 | On supply lines: 1 kV symmetrical, 2 kV asymmetrical, (24 V DC supply only with external protective measure) for PROFIBUS cable : asymmetrical 1 kV |
Conducted interference due to high-frequency radiation acc. to IEC 61000-4-6 | 10 V (0.15 ... 80 MHz) |
Degree and class of protection | | |
IP degree of protection | IP65 |
Standards, approvals, certificates | | |
Certificate of suitability | CE | CE, UL |
CE mark | Yes |
UL approval | | Yes |
KC approval | Yes |
EAC (formerly Gost-R) | Yes |
China RoHS compliance | Yes |
Ambient conditions | | |
Ambient temperature during operation | | |
| 0 °C |
| 50 °C |
Ambient temperature during storage/transportation | | |
| -40 °C |
| 70 °C |
| -40 °C |
| 70 °C |
Air pressure acc. to IEC 60068-2-13 | | |
| 860 hPa |
| 1 080 hPa |
| 660 hPa |
| 1 080 hPa |
| 2 000 m |
Relative humidity | | |
| 95 % |
| 50 % |
Vibrations | | |
| 10 ... 58 Hz / 0.15 mm, 58 ... 150 Hz / 1 g |
| 5 ... 9 Hz / 3.5 mm, 9 ... 500 Hz / 1 g |
Shock testing | | |
| 15 g / 11 ms / 3 shocks/axis |
Dimensions | | |
Width | 300 mm |
Height | 380 mm |
Depth | 200 mm |