General information | |
Product type designation | F-RQ 1x24 V DC/24 ... 230 V AC/5 A |
usable BaseUnits | BU type F0, BU20-P8+A4+0B |
Color code for module-specific color identification plate | CC42 |
Product function | |
| Yes; I&M0 to I&M3 |
Engineering with | |
| V13 |
| V5.5 SP4 and higher |
Supply voltage | |
Rated value (DC) | 24 V; Coil voltage |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
Power | |
Power available from the backplane bus | 100 mW |
Power loss | |
Power loss, typ. | 1 W |
Address area | |
Address space per module | |
| 1 byte |
Digital outputs | |
Number of digital outputs | 1 |
Limitation of inductive shutdown voltage to | No |
Controlling a digital input | Yes |
Switching capacity of the outputs | |
| 5 A |
| 25 W |
Switching frequency | |
| 2 Hz |
| 0.1 Hz; See data in manual |
| 0.1 Hz |
| 2 Hz |
Total current of the outputs (per module) | |
horizontal installation | |
| 5 A; Note derating data in the manual |
| 4 A; Note derating data in the manual |
| 3 A; Note derating data in the manual |
vertical installation | |
| 3 A; Note derating data in the manual |
Relay outputs | |
| 1; 2 NO contacts |
| 24 V |
| 70 mA |
| yes; 6 A, see data in manual |
| Yes; Pilot Duty B300, R300 |
Switching capacity of contacts | |
| see additional description in the manual |
| see additional description in the manual |
| 5 A |
| 1 mA |
| 10 mA |
| 5 A |
| 24 V |
| 230 V |
Cable length | |
| 500 m; for load contacts |
| 300 m; for load contacts |
| 10 m |
Interrupts/diagnostics/status information | |
Diagnostics function | yes, firmware update |
Diagnostics indication LED | |
| Yes; green/red DIAG LED |
| Yes; Green LED |
Potential separation | |
Potential separation channels | |
| Yes; for SELV / PELV only |
| Yes |
| Yes |
Permissible potential difference | |
between channels and backplane bus/supply voltage | 250 V AC (reinforced insulation) |
between backplane bus and supply voltage | 75 V DC/60 V AC |
Isolation | |
Isolation tested with | 2 545 V DC/2 s (routine test) |
Overvoltage category | III |
tested with | |
| DC 2545 V 2 s (routine test), impulse voltage test DC 7200 V / 5 positive and 5 negative pulses (type test) |
| 707 V DC (type test) |
Dimensions | |
Width | 20 mm |
Weights | |
Weight, approx. | 56 g |