General information | |
Product type designation | F-RQ 1x24VDC/24 ... 230VAC/5A |
Product function | |
| Yes; I&M0 to I&M3 |
Engineering with | |
| V13 |
| V5.5 SP4 and higher |
Supply voltage | |
Type of supply voltage | 24 V DC |
Rated value (DC) | 24 V; Coil voltage |
Digital outputs | |
Number of digital outputs | 1 |
Limitation of inductive shutdown voltage to | No |
Controlling a digital input | Yes |
Switching capacity of the outputs | |
| 5 A |
| 25 W |
Switching frequency | |
| 2 Hz |
| 0.1 Hz; See data in manual |
| 0.1 Hz |
| 2 Hz |
Total current of the outputs (per module) | |
horizontal installation | |
| 5 A; Note derating data in the manual |
| 4 A; Note derating data in the manual |
| 3 A; Note derating data in the manual |
vertical installation | |
| 3 A; Note derating data in the manual |
Relay outputs | |
| 1; 2 NO contacts |
| 24 V |
| 70 mA |
| yes; 6 A, see data in manual |
| Yes; Pilot Duty B300, R300 |
Switching capacity of contacts | |
| see additional description in the manual |
| see additional description in the manual |
| 5 A |
| 1 mA |
| 10 mA |
| 5 A |
| 24 V |
| 230 V |
Cable length | |
| 500 m; for load contacts |
| 300 m; for load contacts |
| 10 m |
Interrupts/diagnostics/status information | |
Diagnostics function | yes, firmware update |
Diagnostics indication LED | |
| Yes; green/red DIAG LED |
| Yes; Green LED |
Potential separation | |
Potential separation channels | |
| Yes |
Isolation | |
Isolation tested with | 2 545 V DC/2 s (routine test) |
Overvoltage category | III |
tested with | |
| DC 2545 V 2 s (routine test), impulse voltage test DC 7200 V / 5 positive and 5 negative pulses (type test) |
| 707 V DC (type test) |
Standards, approvals, certificates | |
Suitable for safety functions | Yes |
Highest safety class achievable in safety mode | |
| PLe |
| 4 |
| SIL 3 |
Probability of failure (for service life of 20 years and repair time of 100 hours) | |
| < 1.00E-04, function test 1x per year |
| < 1.00E-05, function test 1x per month |
| < 1.00E-08 1/h, function test 1x per year |
| < 6.00E-09 1/h, function test 1x per month |
Dimensions | |
Width | 20 mm |
Weights | |
Weight, approx. | 56 g |