Integration in automation systems | |
SIMATIC S7-300, S7-400, S7-1200 and S7-1500 | Via SIMATIC ET 200SP interface module (PROFIBUS or PROFINET) |
Other manufacturers (with restrictions) | Via SIMATIC ET 200SP interface module (PROFIBUS or PROFINET) |
Communication interfaces | - SIMATIC ET 200SP backplane bus
- RS 485 (SIWATOOL, Siebert remote display)
|
Commissioning options | - Using SIWATOOL V7
- Using function block in SIMATIC CPU / Touch Panel
|
Measuring accuracy | |
according to DIN 1319-1 of full-scale value at 20 °C ± 10 K (68 °F ± 10 K) | 0.05% |
Internal resolution | ± 2 million parts |
Measuring frequency | 100 / 120 Hz |
Digital filter | Variable adjustable low-pass and average filter |
Typical applications | - Non-automatic weighing instruments
- Force measurements
- Fill-level monitoring
- Belt tension monitors
|
Weighing functions | |
Weight values | |
Limit values | |
Zeroing | Via command by controller or HMI |
Tare | Via command by controller or HMI |
External tare specification | Via command by controller or HMI |
Calibration commands | Via command by controller or HMI |
Load cells | Full-bridge strain gauges in 4-wire or 6-wire system |
Load cell powering | |
Supply voltage (value applies at sensor, cable-related voltage drops of up to 5 V are controlled) | 4.85 V DC ±2% |
Permissible load resistance | |
| > 40 О© |
| < 4100 О© |
With SIWAREX IS Ex interface | |
| > 50 О© |
| < 4100 О© |
Load cell characteristic | 1 … 4 mV/V |
Permissible range of measuring signal (at greatest set characteristic value) | -21.3 ... +21.3 mV |
Max. distance of load cells | 1000 m (459.32 ft) |
Connection to load cells in Ex zone 1 | Optionally via SIWAREX IS Ex interface (compatibility of the load cells must be checked) |
Approvals/certificates | - ATEX Zone 2
- UL
- FM
- EAC
- KCC
- IECEx
- RCM
|
Auxiliary power supply | |
Rated voltage | 24 V DC |
Max. power consumption | typ. 0.1 A @ 24 V DC (0.2 A max.) |
Max. power consumption SIMATIC Bus | 30 mA |
IP degree of protection according to DIN EN 60529; IEC 60529 | IP20 |
Climatic requirements Tmin (IND) ... Tmax (IND) (operating temperature) | |
- Vertical installation in SIMATIC S7 1)
| -25 ... +50 °C (-13 ... 122 °F) |
- Horizontal installation in SIMATIC S7 1)
| -25 ... +60 °C (-13 ... 140 °F) |
EMC requirements | according to IEC 61000-6-2, IEC 61000-6-4, OIML-R76-1 |
Dimensions (width) | 15 mm (0.6 in) |