SIWAREX WP321
|
|
|
Integration in automation systems
|
|
|
SIMATIC S7-300, S7-400, S7-1200 and S7-1500
|
Via SIMATIC ET 200SP interface module (PROFIBUS or PROFINET)
|
|
Other manufacturers (with restrictions)
|
Via SIMATIC ET 200SP interface module (PROFIBUS or PROFINET)
|
|
Communication interfaces
|
- SIMATIC ET 200SP backplane bus
- RS485 (SIWATOOL, Siebert remote indicator)
|
|
Optional remote weight indicator (via RS 485)
|
Siebert S102
|
|
Commissioning options for the scale
|
- using SIWATOOL (PC software)
- using CPU / Touch Panel
|
|
Measuring accuracy
|
|
|
according to DIN 1319-1 of full-scale value at 20 °C ± 10 K
|
0,05 %
|
|
Internal resolution
|
± 2 million parts
|
|
Number of measurements/second (internal)
|
100 / 120 Hz
|
|
Digital filter
|
Variable adjustable low-pass and average filter
|
|
Typical applications
|
- Non-automatic scales
- Force measurements
- Fill-level monitoring
- Belt tension monitors
|
|
Weighing functions
|
|
|
Weight values
|
|
|
Limits
|
|
|
Zeroing function
|
Via command by controller or HMI
|
|
Tare function
|
Via command by controller or HMI
|
|
External tare specification
|
Via command by controller or HMI
|
|
Calibration commands
|
Via command by controller or HMI
|
|
Load cells
|
Strain gauges in 4-wire or 6-wire system
|
|
Load cell excitation
|
|
|
Supply voltage (value applies at sensor, cable-related voltage drops of up to 5 V are controlled)
|
4.85 V DC ±2 %
|
|
Permissible load resistance
|
|
|
|
> 40 ?
|
|
|
< 4100 ?
|
|
With SIWAREX IS Ex interface
|
|
|
|
> 50 ?
|
|
|
< 4100 ?
|
|
Load cell characteristic
|
1 … 4 mV/V
|
|
Permissible range of measuring signal (at greatest set characteristic value)
|
-21.3 ... +21.3 mV
|
|
Max. distance of load cells
|
1000 m (459.32 ft)
|
|
Connection to load cells in Ex zone 1
|
Optionally via SIWAREX IS Ex interface (compatibility of the load cells must be checked)
|
|
Approvals
|
- ATEX Zone 2 (manufacturer declaration)
- UL available soon
- FM available soon
|
|
Max. cable length
|
1000 m
|
|
Transmission rate
|
9 600 … 115 000 bit/s
|
|
Auxiliary power supply
|
|
|
Rated voltage
|
24 V DC
|
|
Max. power consumption
|
typ. 0.1 A @ 24 V DC (0.2 A max.)
|
|
Max. power consumption SIMATIC Bus
|
30 mA
|
|
IP degree of protection to DIN EN 60529; IEC 60529
|
IP20
|
|
Climatic requirements Tmin (IND) ... Tmax (IND) (operating temperature)
|
|
|
Vertical installation in SIMATIC S7 1)
|
-25 ... +60 °C (-13 ... 140 °F)
|
|
Horizontal installation in SIMATIC S7 1)
|
-25 ... +60 °C (-13 ... 140 °F)
|
|
EMC requirements according to
|
IEC 61000-6-2, IEC 61000-6-4, OIML-R76-1
|
|
Dimensions (width)
|
15 mm (0.6 in.)
|