The most important directives and standards are listed below. These are used as basis for the SINAMICS G120P Cabinet converter cabinet units and they must be carefully observed to achieve an EMC-compliant configuration that is safe both functionally and in operation.

European directives

2014/35/EU

Low-voltage directive:

Directive of the European Parliament and Council of February 26, 2014 for the harmonization of the laws of the member states relating to the provision of electrical equipment designed for use within certain voltage limits on the market (amended version)

2014/30/EU

EMC directive:

Directive of the European Parliament and Council of February 26, 2014 for the harmonization of the laws of the member states relating to electromagnetic compatibility (amended version)

2006/42/EC

Machinery directive:

The directive of the European Parliament and Council of May 17, 2006 on machinery and for changing Directive 95/16/EC (amendment)

European standards

EN 60146‑1‑1

Semiconductor converters – General requirements and line-commutated converters

Part 1‑1: Specification of basic requirements

EN 60204‑1

Electrical equipment of machines

Part 1: General requirements

EN 60529

Degrees of protection provided by enclosures (IP code)

EN 61800‑2

Adjustable speed electrical power drive systems

Part 2: General requirements – Rating specifications for low-voltage adjustable frequency a.c. power drive systems

EN 61800‑3

Adjustable speed electrical power drive systems

Part 3: EMC product standard including specific test methods

EN 61800-5-1

Adjustable speed electrical power drive systems

Part 5: Safety requirements

Main section 1: Electrical and thermal requirements



 

General technical specifications

Electrical specifications

Line voltages and power ranges

380 ... 480 V 3 AC ±10 %, 75 ... 560 kW1)

500 ... 690 V 3 AC ±10 %, 315 ... 630 kW

Line system configurations

Grounded TN/TT systems or ungrounded IT systems, a grounded line conductor is not permissible in 690 V line supplies

Line frequency

47 ... 63 Hz

Output frequency

0 ... 150 Hz

Offset factor cos φ

0.96

Power factor λ

0.75 ... 0.93

Efficiency

>98 %

Overvoltage category

III according to EN 61800‑5‑1

Closed-loop control modes

Vector control without sensor or U/f control

Fixed speeds

15 fixed speeds plus 1 minimum speed, parameterizable
(in the default setting, 3 fixed setpoints plus 1 minimum speed are selectable using terminal block/fieldbus system)

Skipped speed ranges

4, parameterizable

Setpoint resolution of the Control Unit

0.01 Hz

12 bit analog

Braking operation

DC braking, dynamic braking with optional Braking Module

Mechanical specifications

Degree of protection

IP20 (higher degrees of protection up to IP54 optional)

Protection class

I according according to EN 61800‑5‑1

Touch protection

According to EN 50274 and DGUV Regulation 3 when used for the intended purpose

Cabinet system

Industry-compatible control cabinet, doors with double-barb lock, base plate with cable entry options, crane transport aid

Paint finish

RAL 7035 (indoor requirements)

Type of cooling

Forced air cooling AF according to EN 60146

Ambient conditions

Storage

Transport

Operation

Ambient temperature

-25 ... +55 °C (-13 ... 131 °F)

-25 ... +70 °C (-13 ... 158 °F)
above -40 °C (-40 °F) for 24 hours

0 ... 40 °C (32 ... 104 °F)
up to 50 °C (122 °F) see derating data

Relative humidity

(condensation not permissible)

5 ... 95 %

Class 1K4 acc. to EN 60721‑3‑1

5 ... 95 %

Class 2K3 acc. to EN 60721‑3‑2

5 ... 95 %

Class 3K3 to EN 60721‑3‑3

Environmental class/harmful chemical substances

Class 1C2 acc. to EN 60721‑3‑1

Class 2C2 acc. to EN 60721‑3‑2

Class 3C2 acc. to EN 60721‑3‑3

Organic/biological influences

Class 1B1 acc. to EN 60721‑3‑1

Class 2B1 acc. to EN 60721‑3‑2

Class 3B1 according to EN 60721‑3‑3
Restriction: No conductive dust particles permitted

Degree of pollution

2 according to EN 61800‑5‑1

Installation altitude

Up to 1000 m (3281 ft) above sea level without derating
> 1000 m (3281 ft) see derating data

Mechanical strength

Storage

Transport 2)

Operation

Vibratory load

Class 1M2 acc. to EN 60721‑3‑1

Class 2M2 acc. to EN 60721‑3‑2

Class 3M2 acc. to EN 60721‑3‑3

  • Deflection

1.5 mm at 5 ... 9 Hz

3.5 mm at 2 ... 9 Hz

0.075 mm at 10 ... 58 Hz

  • Acceleration

5 m/s2 at > 9 ... 200 Hz

10 m/s2 at > 9 ... 200 Hz

10 m/s2 at > 58 ... 200 Hz

Shock load

Class 1M2 acc. to EN 60721‑3‑1

Class 2M2 acc. to EN 60721‑3‑2

Class 3M2 acc. to EN 60721‑3‑3

  • Acceleration

40 m/s2 at 22 ms

150 m/s2 at 11 ms

50 m/s2 (5 Ã— g)/30 ms
150 m/s2 (15 Ã— g)/11 ms

Standards

Compliance with standards

cULus, CE, RCM, EAC, KC, SEMI F47 3)

CE marking

According to EMC Directive 2014/30/EU, Low Voltage Directive 2014/35/EU, Machinery Directive 2006/42/EC

Radio interference suppression

The SINAMICS G120P Cabinet converter systems are not designed for connection to the public power network ("first environment"). Radio interference suppression is compliant with the EMC product standard for variable-speed drives EN 61800-3 "Second environment" (industrial line supplies). The equipment can cause electromagnetic interference when it is connected to the public network. However, if supplementary measures are taken (e.g. line filter, see option L00) operation in the "first environment" is possible.



Deviations from the specified classes are underlined.

1) For the option L01, the line voltage is limited to 380 to 415 V AC ± 10%.

2) In transport packaging.

3) SEMI F47 for frame size HX (500 V to 690 V) and frame size JX available soon

 

Line voltage 380 ... 480 V 3 AC

SINAMICS G120P Cabinet converter cabinet units

 

6SL3710-1PE31-5AB0-Z

6SL3710-1PE31-8AB0-Z

6SL3710-1PE32-1AB0-Z

6SL3710-1PE32-5AB0-Z

Rated power

 

 

 

 

 

  • At IL 400 V/50 Hz 1)

kW

75

90

110

132

  • At IL 460 V/60 Hz 2)

hp

75

100

125

150

  • At IH 400 V/50 Hz 1)

kW

55

75

90

110

  • At IH 460 V/60 Hz 2)

hp

60

75

100

125

Output current

 

 

 

 

 

  • Rated current Irated (400 V ±10 %)

A

145

178

205

250

  • Rated current Irated (480 V ±10 %)

A

120

148

170

207

  • Base-load current IL (400 V ±10 %) 3)

A

145

178

205

250

  • Base-load current IL (480 V ±10 %) 3)

A

120

148

170

207

  • Base-load current IH (400 V ±10 %) 4)

A

110

145

178

205

  • Base-load current IH (480 V ±10 %) 4)

A

91

120

148

170

  • Output current, max.

A

196

241

277

338

Input current

 

 

 

 

 

  • Rated current Irated (400 V ±10 %) 5)

A

140

172

198

242

  • Rated current Irated (480 V ±10 %) 5)

A

117

143

165

202

  • Base-load current IL (400 V ±10 %) 3)

A

140

172

198

242

  • Base-load current IL (480 V ±10 %) 3)

A

117

143

165

202

  • Base-load current IH (400 V ±10 %) 4)

A

117

154

189

218

  • Base-load current IH (480 V ±10 %) 4)

A

97.5

128

157.5

182

  • Input current, max.

A

189

232

267

327

Current requirement, 24 V DC auxiliary power supply 6)

A

1

1

1

1

Short-circuit current rating acc. to IEC

in conjunction with the specified fuses without/with option L26

kA

65

65

65

65

Minimum short-circuit current 7)

 

 

 

 

 

  • For 3NE1 fuses

A

1800

2400

3000

3000

  • For 3NA3 fuses

A

4400

5000

7000

7000

Power loss, max.

at Irated (400 V/40 °C), without options

kW

1.68

2.17

2.38

3.07

Coolant

 

Air

Air

Air

Air

Coolant requirements

m3/s (ft3/s)

0.16 (5.65)

0.16 (5.65)

0.16 (5.65)

0.16 (5.65)

Sound pressure level LpA (1 m) at 50/60 Hz

dB

66/66

66/66

66/66

66/66

Cable length, max. 8)

between Power Module and motor

 

 

 

 

 

  • When compliant with Categories C2 and C3 according to EN 61800‑3
    shielded

m (ft)

150 (492)

150 (492)

150 (492)

150 (492)

  • When non-compliant with the limit values for RI suppression and without output reactor
    unshielded

m (ft)

450 (1476)

450 (1476)

450 (1476)

450 (1476)

Dimensions

 

 

 

 

 

  • Width

mm (in)

400 (15.75)

400 (15.75)

400 (15.75)

400 (15.75)

  • Height

mm (in)

2000 (78.74)

2000 (78.74)

2000 (78.74)

2000 (78.74)

  • Depth

mm (in)

600 (23.62)

600 (23.62)

600 (23.62)

600 (23.62)

Frame size

 

F

F

F

F

Weight

(degree of protection IP20, without options)

kg (lb)

165 (364)

165 (364)

165 (364)

165 (364)



1) Rated power of a typ. 4-pole standard induction motor based on base-load current IL or IH at 400 V 3 AC/50 Hz.

2) Rated power of a typ. 4-pole standard induction motor based on base-load current IL or IH at 460 V 3 AC/60 Hz.

3) The base-load current IL is based on a duty cycle of 110 % for 60 s or 135 % for 3 s with a duty cycle duration of 300 s (see overload capability characteristics).

4) The base-load current IH is based on a duty cycle of 150 % for 60 s with a duty cycle duration of 300 s (see overload capability characteristics).

5) The current values given here are based on the rated output current.

6) If the drive closed-loop control is still to remain active when the main line supply fails, then the converter must be provided with an external 24 V DC supply.

7) 10 ms value from current-time characteristic for reliable tripping of installed protection devices. If the minimum short-circuit current is not reached, the tripping time of the fuses is increased, which can lead to damage.

8) Longer cable lengths are available on request.

Note:

The power data in hp units are based on the NEC/CEC standards for the North American market.

Information on the line connection, motor connection and cabinet grounding can be found in section Cable cross-sections and connections.

 

Line voltage 380 ... 480 V 3 AC

SINAMICS G120P Cabinet converter cabinet units

 

6SL3710-1PE33‑0.A0-Z

6SL3710-1PE33‑7.A0-Z

6SL3710-1PE34‑6.A0-Z

6SL3710-1PE35‑8.A0-Z

6SL3710-1PE36‑6.A0-Z

6SL3710-1PE37‑4.A0-Z

Rated power

 

 

 

 

 

 

 

  • At IL 400 V/50 Hz 1)

kW

160

200

250

315

355

400

  • At IL 460 V/60 Hz 2)

hp

200

250

300

400

450

500

  • At IH 400 V/50 Hz 1)

kW

132

160

200

250

250

315

  • At IH 460 V/60 Hz 2)

hp

150

200

200

300

300

350

Output current

 

 

 

 

 

 

 

  • Rated current Irated (400 V ±10 %)

A

300

370

460

585

655

735

  • Rated current Irated (480 V ±10 %)

A

245

308

369

487

526

602

  • Base-load current IL (400 V ±10 %) 3)

A

290

360

450

570

640

720

  • Base-load current IL (480 V ±10 %) 3)

A

240

302

361

477

515

590

  • Base-load current IH (400 V ±10 %) 4)

A

240

296

368

468

491

551

  • Base-load current IH (480 V ±10 %) 4)

A

196

247

295

390

394

452

  • Output current, max.

A

392

486

608

770

864

972

Input current

 

 

 

 

 

 

 

  • Rated current Irated (400 V ±10 %) 5)

A

317

375

469

597

668

750

  • Rated current Irated (480 V ±10 %) 5)

A

262

314

376

497

536

614

  • Base-load current IL (400 V ±10 %) 3)

A

307

365

459

585

654

735

  • Base-load current IL (480 V ±10 %) 3)

A

257

308

368

486

525

602

  • Base-load current IH (400 V ±10 %) 4)

A

254

300

375

477

501

562

  • Base-load current IH (480 V ±10 %) 4)

A

210

251

301

397

402

461

  • Input current, max.

A

415

493

620

785

881

992

Current requirement, 24 V DC auxiliary power supply 6)

 

 

 

 

 

 

 

  • Version A

A

1

1

1

1

1

1

  • Version C

A

0.5

0.5

0.5

0.5

0.5

0.5

Short-circuit current rating acc. to IEC

in conjunction with the specified fuses
without/with option L26

kA

65/65

65/65

65/50

65/50

65/50

65/50

Minimum short-circuit current 7)

 

 

 

 

 

 

 

  • For 3NE1 fuses

A

3500

4500

7000

10000

11000

13000

  • For 3NA3 fuses

A

9500

14000

20000

20000

30000

30000

Power loss, max.

at Irated (400 V/40 °C), without options

kW

4.01

4.871

5.683

7.358

8.287

9.101

Coolant

 

Air

Air

Air

Air

Air

Air

Coolant requirements

m3/s (ft3/s)

0.21 (7.42)

0.21 (7.42)

0.21 (7.42)

0.6 (21.2)

0.6 (21.2)

0.6 (21.2)

Sound pressure level LpA (1 m) at 50/60 Hz

 

 

 

 

 

 

 

  • Version A

dB

66/66

66/66

66/66

69/69

69/69

69/69

  • Version C

dB

63/63

63/63

63/63

66/66

66/66

66/66

Cable length, max.

between Power Module and motor

 

 

 

 

 

 

 

  • When compliant with Categories C2 and C3 according to EN 61800‑3
    shielded

m (ft)

150 (492)

150 (492)

150 (492)

150 (492)

150 (492)

150 (492)

  • When non-compliant with the limit values for RI suppression and without output reactor
    unshielded

m (ft)

200 (656)

200 (656)

200 (656)

200 (656)

200 (656)

200 (656)

  • When non-compliant with the limit values for RI suppression with output reactor
    shielded/unshielded

m (ft)

300/450 (984/1476)

300/450 (984/1476)

300/450 (984/1476)

300/450 (984/1476)

300/450 (984/1476)

300/450 (984/1476)

Dimensions

 

 

 

 

 

 

 

  • Width for
    version A/C

mm (in)

1000/600 (39.37/23.62)

1000/600 (39.37/23.62)

1000/600 (39.37/23.62)

1200 9)/800 (47.24 9)/31.50)

1200 9)/800 (47.24 9)/31.50)

1200 9)/800 (47.24 9)/31.50)

  • Height 8)

mm (in)

2000 (78.74)

2000 (78.74)

2000 (78.74)

2000 (78.74)

2000 (78.74)

2000 (78.74)

  • Depth

mm (in)

600 (23.62)

600 (23.62)

600 (23.62)

600 (23.62)

600 (23.62)

600 (23.62)

Frame size

 

GX

GX

GX

HX

HX

HX

Weight

Versions A/C
(degree of protection IP20, without options)

kg (lb)

370/290 (816/639)

380/300 (838/661)

400/300 (882/661)

500/430 (1102/948)

500/440 (1102/970)

530/440 (1169/970)



1) Rated power of a typ. 4-pole standard induction motor based on base-load current IL or IH at 400 V 3 AC/50 Hz.

2) Rated power of a typ. 4-pole standard induction motor based on base-load current IL or IH at 460 V 3 AC/60 Hz.

3) The base-load current IL is based on a duty cycle of 110 % for 60 s or 135 % for 3 s with a duty cycle duration of 300 s (see overload capability characteristics).

4) The base-load current IH is based on a duty cycle of 150 % for 60 s with a duty cycle duration of 300 s (see overload capability characteristics).

5) The current values given here are based on the rated output current.

6) If the drive closed-loop control is still to remain active when the main line supply fails, then the converter must be provided with an external 24 V DC supply.

7) 10 ms value from current-time characteristic for reliable tripping of installed protection devices. If the minimum short-circuit current is not reached, the tripping time of the fuses is increased, which can lead to damage.

8) The cabinet height increases by 300 mm (11.81 in) for IP21 degree of protection, and by 400 mm (15.75 in) for IP23, IP43 and IP54 degrees of protection.

9) The specified cabinet widths increase depending on the options selected. For details, see description of option L01.

Note:

The power data in hp units are based on the NEC/CEC standards for the North American market.

Information on the line connection, motor connection and cabinet grounding can be found in section Cable cross-sections and connections.

 

Line voltage 380 ... 480 V 3 AC

SINAMICS G120P Cabinet converter cabinet units

 

6SL3710-1PE38-4AA0-Z

6SL3710-1PE38-8AA0-Z

6SL3710-1PE41-0AA0-Z

Rated power

 

 

 

 

  • At IL 400 V/50 Hz 1)

kW

450

500

560

  • At IL 460 V/60 Hz 2)

hp

500

600

700

  • At IH 400 V/50 Hz 1)

kW

355

400

450

  • At IH 460 V/60 Hz 2)

hp

450

500

500

Output current

 

 

 

 

  • Rated current Irated (400 V ±10 %)

A

840

910

1021

  • Rated current Irated (480 V ±10 %)

A

677

739

847

  • Base-load current IL (400 V ±10 %) 3)

A

820

890

1000

  • Base-load current IL (480 V ±10 %) 3)

A

663

724

830

  • Base-load current IH (400 V ±10 %) 4)

A

672

728

786

  • Base-load current IH (480 V ±10 %) 4)

A

542

591

652

  • Output current, max.

A

1107

1202

1350

Input current

 

 

 

 

  • Rated current Irated (400 V ±10 %) 5)

A

870

945

1061

  • Rated current Irated (480 V ±10 %) 5)

A

702

767

880

  • Base-load current IL (400 V ±10 %) 3)

A

850

925

1039

  • Base-load current IL (480 V ±10 %) 3)

A

687

751

862

  • Base-load current IH (400 V ±10 %) 4)

A

696

756

816

  • Base-load current IH (480 V ±10 %) 4)

A

561

614

677

  • Input current, max.

A

1147

1248

1402

Current requirement, 24 V DC auxiliary power supply 6)

A

1

1

1

Short-circuit current rating acc. to IEC

in conjunction with the specified fuses
without/with option L26

kA

65/65

65/65

65/65

Minimum short-circuit current 7)

 

 

 

 

  • For 3NE1 fuses

A

10400

14000

16000

  • For 3NA3 fuses

A

40000

40000

52000

Power loss, max.

at Irated (400 V/40 °C), without options

kW

11.098

11.605

13.348

Coolant

 

Air

Air

Air

Coolant requirements

m3/s (ft3/s)

0.7 (24.7)

0.7 (24.7)

0.7 (24.7)

Sound pressure level LpA (1 m) at 50/60 Hz

dB

69/69

69/69

69/69

Cable length, max.

between Power Module and motor

 

 

 

 

  • When compliant with Categories C2 and C3 according to EN 61800‑3
    shielded

m (ft)

150 (492)

150 (492)

150 (492)

  • When non-compliant with the limit values for RI suppression and without output reactor
    unshielded

m (ft)

200 (656)

200 (656)

200 (656)

  • When non-compliant with the limit values for RI suppression with output reactor
    shielded/unshielded

m (ft)

300/450 (984/1476)

300/450 (984/1476)

300/450 (984/1476)

Dimensions

 

 

 

 

  • Width

mm (in)

1200 (47.24) 9)

1200 (47.24) 9)

1200 (47.24) 9)

  • Height 8)

mm (in)

2000 (78.74)

2000 (78.74)

2000 (78.74)

  • Depth

mm (in)

600 (23.62)

600 (23.62)

600 (23.62)

Frame size

 

JX

JX

JX

Weight

(degree of protection IP20, without options)

kg (lb)

655 (1444)

676 (1490)

681 (1501)



1) Rated power of a typ. 4-pole standard induction motor based on base-load current IL or IH at 400 V 3 AC/50 Hz.

2) Rated power of a typ. 4-pole standard induction motor based on base-load current IL or IH at 460 V 3 AC/60 Hz.

3) The base-load current IL is based on a duty cycle of 110 % for 60 s or 135 % for 3 s with a duty cycle duration of 300 s (see overload capability characteristics).

4) The base-load current IH is based on a duty cycle of 150 % for 60 s with a duty cycle duration of 300 s (see overload capability characteristics).

5) The current values given here are based on the rated output current.

6) If the drive closed-loop control is still to remain active when the main line supply fails, then the converter must be provided with an external 24 V DC supply.

7) 10 ms value from current-time characteristic for reliable tripping of installed protection devices. If the minimum short-circuit current is not reached, the tripping time of the fuses is increased, which can lead to damage.

8) The cabinet height increases by 300 mm (11.8 in) for degree of protection IP21, and by 400 mm (15.7 in) for degrees of protection IP23, IP43 and IP54.

9) The specified cabinet widths increase depending on the options selected. For details, see description of options L00 and L01.

Note:

The power data in hp units are based on the NEC/CEC standards for the North American market.

Information on the line connection, motor connection and cabinet grounding can be found in section Cable cross-sections and connections.

 

Line voltage 500 ... 690 V 3 AC

SINAMICS G120P Cabinet converter cabinet units

 

6SL3710-1PG33-7 . A0-Z

6SL3710-1PG34-0 . A0-Z

6SL3710-1PG34-5 . A0-Z

6SL3710-1PG35-2 . A0-Z

Rated power

 

 

 

 

 

  • At IL 690 V/50 Hz 1)

kW

315

355

400

450

  • At IL 575 V/60 Hz 2)

hp

350

400

450

450

  • At IH 690 V/50 Hz 1)

kW

250

315

355

400

  • At IH 575 V/60 Hz 2)

hp

250

300

350

450

Output current

 

 

 

 

 

  • Rated current Irated (500 V ±10 %)

A

368

400

453

516

  • Rated current Irated (600 V ±10 %)

A

353

396

441

497

  • Rated current Irated (690 V ±10 %)

A

340

393

430

480

  • Base-load current IL (500 V ±10 %) 3)

A

361

392

443

505

  • Base-load current IL (690 V ±10 %) 3)

A

330

385

420

470

  • Base-load current IH (500 V ±10 %) 4)

A

295

320

367

423

  • Base-load current IH (690 V ±10 %) 4)

A

272

314

348

394

  • Output current, max.

A

487

529

598

682

Input current

 

 

 

 

 

  • Rated current Irated (500 V ±10 %) 5)

A

383

416

471

537

  • Rated current Irated (600 V ±10 %) 5)

A

367

412

459

517

  • Rated current Irated (690 V ±10 %) 5)

A

354

409

447

499

  • Base-load current IL (500 V ±10 %) 3)

A

375

408

461

526

  • Base-load current IL (690 V ±10 %) 3)

A

343

401

437

489

  • Base-load current IH (500 V ±10 %) 4)

A

307

333

381

440

  • Base-load current IH (690 V ±10 %) 4)

A

283

327

362

410

  • Input current, max.

A

507

550

623

710

Current requirement, 24 V DC auxiliary power supply 6)

 

 

 

 

 

  • Version A

A

1.0

1.0

1.0

1.0

  • Version C

A

0.5

0.5

0.5

0.5

Short-circuit current rating acc. to IEC

in conjunction with the specified fuses without/with Option L26

kA

65/65

65/50

65/50

65/50

Minimum short-circuit current 7)

 

 

 

 

 

  • For 3NE1 fuses

A

3500

4500

7000

8500

  • For 3NA3 fuses

A

10000

10500

13000

14600

Power loss, max.

at Irated (500 V/40 °C), without options

kW

5.838

6.665

7.429

8.259

Coolant

 

Air

Air

Air

Air

Coolant requirements

m3/s (ft3/s)

0.6 (21.2)

0.6 (21.2)

0.6 (21.2)

0.6 (21.2)

Sound pressure level LpA (1 m) at 50/60 Hz

 

 

 

 

 

  • Version A/C

dB

69/69

69/69

69/69

69/69

Cable length, max.

between Power Module and motor

 

 

 

 

 

  • When compliant with Categories C2 and C3 according to EN 61800‑3
    shielded

m (ft)

150 (492)

150 (492)

150 (492)

150 (492)

  • When non-compliant with the limit values for RI suppression and without output reactor
    unshielded

m (ft)

200 (656)

200 (656)

200 (656)

200 (656)

  • When non-compliant with the limit values for RI suppression with output reactor
    shielded/unshielded

m (ft)

300/450 (984/1476)

300/450 (984/1476)

300/450 (984/1476)

300/450 (984/1476)

Dimensions

 

 

 

 

 

  • Width for
    version A/C

mm (in)

1200 (47.24)

1200 (47.24)

1200 (47.24)

1200 (47.24)

  • Height 8)

mm (in)

2000 (78.74)

2000 (78.74)

2000 (78.74)

2000 (78.74)

  • Depth

mm (in)

600 (23.62)

600 (23.62)

600 (23.62)

600 (23.62)

Frame size

 

HX

HX

HX

HX

Weight

Versions A/C
(degree of protection IP20, without options)

kg (lb)

515/435 (1135/959)

522/442 (1151/974)

522/442 (1151/974)

535/455 (1179/1003)



1) Rated power of a typ. 4-pole standard induction motor based on base-load current IL or IH at 690 V 3 AC/50 Hz.

2) Rated power of a typ. 4-pole standard induction motor based on base-load current IL or IH at 575 V 3 AC/60 Hz.

3) The base-load current IL is based on a duty cycle of 110 % for 60 s or 135 % for 3 s with a duty cycle duration of 300 s (see overload capability characteristics).

4) The base-load current IH is based on a duty cycle of 150 % for 60 s with a duty cycle duration of 300 s (see overload capability characteristics).

5) The current values given here are based on the rated output current.

6) If the drive closed-loop control is still to remain active when the main line supply fails, then the converter must be provided with an external 24 V DC supply.

7) 10 ms value from current-time characteristic for reliable tripping of installed protection devices. If the minimum short-circuit current is not reached, the tripping time of the fuses is increased, which can lead to damage.

8) The cabinet height increases by 300 mm (11.8 in) for degrees of protection IP20 and IP21, and by 400 mm (15.7 in) for degrees of protection IP23, IP43 and IP54.

Line voltage 500 ... 690 V 3 AC

SINAMICS G120P Cabinet converter cabinet units

 

6SL3710-1PG35-8AA0-Z

6SL3710-1PG36-5AA0-Z

6SL3710-1PG37-2AA0-Z

Rated power

 

 

 

 

  • At IL 690 V/50 Hz 1)

kW

500

560

630

  • At IL 575 V/60 Hz 2)

hp

500

600

700

  • At IH 690 V/50 Hz 1)

kW

450

500

560

  • At IH 575 V/60 Hz 2)

hp

450

500

500

Output current

 

 

 

 

  • Rated current Irated (500 V ±10 %)

A

581

654

725

  • Rated current Irated (600 V ±10 %)

A

557

623

693

  • Rated current Irated (690 V ±10 %)

A

535

595

665

  • Base-load current IL (500 V ±10 %) 3)

A

569

640

710

  • Base-load current IL (690 V ±10 %) 3)

A

520

580

650

  • Base-load current IH (500 V ±10 %) 4)

A

482

523

580

  • Base-load current IH (690 V ±10 %) 4)

A

444

476

532

  • Output current, max.

A

768

864

959

Input current

 

 

 

 

  • Rated current Irated (500 V ±10 %) 5)

A

596

679

753

  • Rated current Irated (600 V ±10 %) 5)

A

578

647

720

  • Rated current Irated (690 V ±10 %) 5)

A

555

618

690

  • Base-load current IL (500 V ±10 %) 3)

A

591

665

737

  • Base-load current IL (690 V ±10 %) 3)

A

540

602

675

  • Base-load current IH (500 V ±10 %) 4)

A

501

543

602

  • Base-load current IH (690 V ±10 %) 4)

A

461

494

552

  • Input current, max.

A

798

897

995

Current requirement, 24 V DC auxiliary power supply 6)

A

1

1

1

Short-circuit current rating acc. to IEC

in conjunction with the specified fuses

kA

65

65

65

Minimum short-circuit current 7)

 

 

 

 

  • For 3NE1 fuses

A

10000

11000

13000

  • For 3NA3 fuses

A

16000

20000

21000

Power loss, max.

at Irated (500 V/40 °C), without options

kW

8.688

9.468

10.688

Coolant

 

Air

Air

Air

Coolant requirements

m3/s (ft3/s)

0.7 (24.7)

0.7 (24.7)

0.7 (24.7)

Sound pressure level LpA (1 m) at 50/60 Hz

dB

69/69

69/69

69/69

Cable length, max.

between Power Module and motor

 

 

 

 

  • When compliant with Categories C2 and C3 according to EN 61800‑3
    shielded

m (ft)

150 (492)

150 (492)

150 (492)

  • When non-compliant with the limit values for RI suppression and without output reactor
    unshielded

m (ft)

200 (656)

200 (656)

200 (656)

  • When non-compliant with the limit values for RI suppression with output reactor
    shielded/unshielded

m (ft)

300/450 (984/1476)

300/450 (984/1476)

300/450 (984/1476)

Dimensions

 

 

 

 

  • Width

mm (in)

1200 (47.24) 9)

1200 (47.24) 9)

1200 (47.24) 9)

  • Height 8)

mm (in)

2000 (78.74)

2000 (78.74)

2000 (78.74)

  • Depth

mm (in)

600 (23.62)

600 (23.62)

600 (23.62)

Frame size

 

JX

JX

JX

Weight

(degree of protection IP20, without options)

kg (lb)

654 (1442)

697 (1537)

716 (1579)



1) Rated power of a typ. 4-pole standard induction motor based on base-load current IL or IH at 690 V 3 AC/50 Hz.

2) Rated power of a typ. 4-pole standard induction motor based on base-load current IL or IH at 575 V 3 AC/60 Hz.

3) The base-load current IL is based on a duty cycle of 110 % for 60 s or 135 % for 3 s with a duty cycle duration of 300 s (see overload capability characteristics).

4) The base-load current IH is based on a duty cycle of 150 % for 60 s with a duty cycle duration of 300 s (see overload capability characteristics).

5) The current values given here are based on the rated output current.

6) If the drive closed-loop control is still to remain active when the main line supply fails, then the converter must be provided with an external 24 V DC supply.

7) 10 ms value from current-time characteristic for reliable tripping of installed protection devices. If the minimum short-circuit current is not reached, the tripping time of the fuses is increased, which can lead to damage.

8) The cabinet height increases by 300 mm (11.8 in) for degree of protection IP21, and by 400 mm (15.7 in) for degrees of protection IP23, IP43 and IP54.

9) The specified cabinet widths increase depending on the options selected. For details, see description of option L00.

Note:

The power data in hp units are based on the NEC/CEC standards for the North American market.

Information on the line connection, motor connection and cabinet grounding can be found in section Cable cross-sections and connections.

















skener.ru

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Àðìàòóðà DENDOR

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Äàò÷èêè è èçìåðèòåëè

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ðåãóëÿòîðû è ðåãèñòðàòîðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ïíåâìàòè÷åñêîå îáîðóäîâàíèå

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Êðàíû è Êëàïàíû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Èçìåðèòåëüíûå ïðèáîðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ñèñòåìû áåñïðîâîäíîãî óïðàâëåíèÿ «óìíûé äîì»

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Áåñêîíòàêòíûå âûêëþ÷àòåëè Êîíå÷íûå âûêëþ÷àòåëè Îïòè÷åñêèå äàò÷èêè Ýíêîäåðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Óñòàíîâêà óìÿã÷åíèÿ

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Óñòàíîâêà îáåçæåëåçèâàíèÿ

  © ÎÎÎ "ÑÊ ÝÍÅÐÃÎ" 2007-2022
  (4872) 700-366  skenergo@mail.ru
ßíäåêñ.Ìåòðèêà