The most important directives and standards are listed below. These are used as basis for the SINAMICS G120P Cabinet converter cabinet units and they must be carefully observed to achieve an EMC-compliant configuration that is safe both functionally and in operation. European directives | 2014/35/EU | Low-voltage directive: Directive of the European Parliament and Council of February 26, 2014 for the harmonization of the laws of the member states relating to the provision of electrical equipment designed for use within certain voltage limits on the market (amended version) | 2014/30/EU | EMC directive: Directive of the European Parliament and Council of February 26, 2014 for the harmonization of the laws of the member states relating to electromagnetic compatibility (amended version) | 2006/42/EC | Machinery directive: The directive of the European Parliament and Council of May 17, 2006 on machinery and for changing Directive 95/16/EC (amendment) | European standards | EN 60146‑1‑1 | Semiconductor converters – General requirements and line-commutated converters Part 1‑1: Specification of basic requirements | EN 60204‑1 | Electrical equipment of machines Part 1: General requirements | EN 60529 | Degrees of protection provided by enclosures (IP code) | EN 61800‑2 | Adjustable speed electrical power drive systems Part 2: General requirements – Rating specifications for low-voltage adjustable frequency a.c. power drive systems | EN 61800‑3 | Adjustable speed electrical power drive systems Part 3: EMC product standard including specific test methods | EN 61800-5-1 | Adjustable speed electrical power drive systems Part 5: Safety requirements Main section 1: Electrical and thermal requirements |
General technical specifications |
---|
Electrical specifications | Line voltages and power ranges | 380 ... 480 V 3 AC ±10 %, 75 ... 560 kW1) 500 ... 690 V 3 AC ±10 %, 315 ... 630 kW | Line system configurations | Grounded TN/TT systems or ungrounded IT systems, a grounded line conductor is not permissible in 690 V line supplies | Line frequency | 47 ... 63 Hz | Output frequency | 0 ... 150 Hz | Offset factor cos φ | 0.96 | Power factor λ | 0.75 ... 0.93 | Efficiency | >98 % | Overvoltage category | III according to EN 61800‑5‑1 | Closed-loop control modes | Vector control without sensor or U/f control | Fixed speeds | 15 fixed speeds plus 1 minimum speed, parameterizable (in the default setting, 3 fixed setpoints plus 1 minimum speed are selectable using terminal block/fieldbus system) | Skipped speed ranges | 4, parameterizable | Setpoint resolution of the Control Unit | 0.01 Hz 12 bit analog | Braking operation | DC braking, dynamic braking with optional Braking Module | Mechanical specifications | Degree of protection | IP20 (higher degrees of protection up to IP54 optional) | Protection class | I according according to EN 61800‑5‑1 | Touch protection | According to EN 50274 and DGUV Regulation 3 when used for the intended purpose | Cabinet system | Industry-compatible control cabinet, doors with double-barb lock, base plate with cable entry options, crane transport aid | Paint finish | RAL 7035 (indoor requirements) | Type of cooling | Forced air cooling AF according to EN 60146 | Ambient conditions | Storage | Transport | Operation | Ambient temperature | -25 ... +55 °C (-13 ... 131 °F) | -25 ... +70 °C (-13 ... 158 °F) above -40 °C (-40 °F) for 24 hours | 0 ... 40 °C (32 ... 104 °F) up to 50 °C (122 °F) see derating data | Relative humidity (condensation not permissible) | 5 ... 95 % Class 1K4 acc. to EN 60721‑3‑1 | 5 ... 95 % Class 2K3 acc. to EN 60721‑3‑2 | 5 ... 95 % Class 3K3 to EN 60721‑3‑3 | Environmental class/harmful chemical substances | Class 1C2 acc. to EN 60721‑3‑1 | Class 2C2 acc. to EN 60721‑3‑2 | Class 3C2 acc. to EN 60721‑3‑3 | Organic/biological influences | Class 1B1 acc. to EN 60721‑3‑1 | Class 2B1 acc. to EN 60721‑3‑2 | Class 3B1 according to EN 60721‑3‑3 Restriction: No conductive dust particles permitted | Degree of pollution | 2 according to EN 61800‑5‑1 | Installation altitude | Up to 1000 m (3281 ft) above sea level without derating > 1000 m (3281 ft) see derating data | Mechanical strength | Storage | Transport 2) | Operation | Vibratory load | Class 1M2 acc. to EN 60721‑3‑1 | Class 2M2 acc. to EN 60721‑3‑2 | Class 3M2 acc. to EN 60721‑3‑3 | | 1.5 mm at 5 ... 9 Hz | 3.5 mm at 2 ... 9 Hz | 0.075 mm at 10 ... 58 Hz | | 5 m/s2 at > 9 ... 200 Hz | 10 m/s2 at > 9 ... 200 Hz | 10 m/s2 at > 58 ... 200 Hz | Shock load | Class 1M2 acc. to EN 60721‑3‑1 | Class 2M2 acc. to EN 60721‑3‑2 | Class 3M2 acc. to EN 60721‑3‑3 | | 40 m/s2 at 22 ms | 150 m/s2 at 11 ms | 50 m/s2 (5 × g)/30 ms 150 m/s2 (15 × g)/11 ms | Standards | Compliance with standards | cULus, CE, RCM, EAC, KC, SEMI F47 3) | CE marking | According to EMC Directive 2014/30/EU, Low Voltage Directive 2014/35/EU, Machinery Directive 2006/42/EC | Radio interference suppression | The SINAMICS G120P Cabinet converter systems are not designed for connection to the public power network ("first environment"). Radio interference suppression is compliant with the EMC product standard for variable-speed drives EN 61800-3 "Second environment" (industrial line supplies). The equipment can cause electromagnetic interference when it is connected to the public network. However, if supplementary measures are taken (e.g. line filter, see option L00) operation in the "first environment" is possible. |
Deviations from the specified classes are underlined. 1) For the option L01, the line voltage is limited to 380 to 415 V AC ± 10%. 2) In transport packaging. 3) SEMI F47 for frame size HX (500 V to 690 V) and frame size JX available soon Line voltage 380 ... 480 V 3 AC | SINAMICS G120P Cabinet converter cabinet units |
---|
| 6SL3710-1PE31-5AB0-Z | 6SL3710-1PE31-8AB0-Z | 6SL3710-1PE32-1AB0-Z | 6SL3710-1PE32-5AB0-Z |
---|
Rated power | | | | | | | kW | 75 | 90 | 110 | 132 | | hp | 75 | 100 | 125 | 150 | | kW | 55 | 75 | 90 | 110 | | hp | 60 | 75 | 100 | 125 | Output current | | | | | | - Rated current Irated (400 V ±10 %)
| A | 145 | 178 | 205 | 250 | - Rated current Irated (480 V ±10 %)
| A | 120 | 148 | 170 | 207 | - Base-load current IL (400 V ±10 %) 3)
| A | 145 | 178 | 205 | 250 | - Base-load current IL (480 V ±10 %) 3)
| A | 120 | 148 | 170 | 207 | - Base-load current IH (400 V ±10 %) 4)
| A | 110 | 145 | 178 | 205 | - Base-load current IH (480 V ±10 %) 4)
| A | 91 | 120 | 148 | 170 | | A | 196 | 241 | 277 | 338 | Input current | | | | | | - Rated current Irated (400 V ±10 %) 5)
| A | 140 | 172 | 198 | 242 | - Rated current Irated (480 V ±10 %) 5)
| A | 117 | 143 | 165 | 202 | - Base-load current IL (400 V ±10 %) 3)
| A | 140 | 172 | 198 | 242 | - Base-load current IL (480 V ±10 %) 3)
| A | 117 | 143 | 165 | 202 | - Base-load current IH (400 V ±10 %) 4)
| A | 117 | 154 | 189 | 218 | - Base-load current IH (480 V ±10 %) 4)
| A | 97.5 | 128 | 157.5 | 182 | | A | 189 | 232 | 267 | 327 | Current requirement, 24 V DC auxiliary power supply 6) | A | 1 | 1 | 1 | 1 | Short-circuit current rating acc. to IEC in conjunction with the specified fuses without/with option L26 | kA | 65 | 65 | 65 | 65 | Minimum short-circuit current 7) | | | | | | | A | 1800 | 2400 | 3000 | 3000 | | A | 4400 | 5000 | 7000 | 7000 | Power loss, max. at Irated (400 V/40 °C), without options | kW | 1.68 | 2.17 | 2.38 | 3.07 | Coolant | | Air | Air | Air | Air | Coolant requirements | m3/s (ft3/s) | 0.16 (5.65) | 0.16 (5.65) | 0.16 (5.65) | 0.16 (5.65) | Sound pressure level LpA (1 m) at 50/60 Hz | dB | 66/66 | 66/66 | 66/66 | 66/66 | Cable length, max. 8) between Power Module and motor | | | | | | - When compliant with Categories C2 and C3 according to EN 61800‑3
shielded
| m (ft) | 150 (492) | 150 (492) | 150 (492) | 150 (492) | - When non-compliant with the limit values for RI suppression and without output reactor
unshielded
| m (ft) | 450 (1476) | 450 (1476) | 450 (1476) | 450 (1476) | Dimensions | | | | | | | mm (in) | 400 (15.75) | 400 (15.75) | 400 (15.75) | 400 (15.75) | | mm (in) | 2000 (78.74) | 2000 (78.74) | 2000 (78.74) | 2000 (78.74) | | mm (in) | 600 (23.62) | 600 (23.62) | 600 (23.62) | 600 (23.62) | Frame size | | F | F | F | F | Weight (degree of protection IP20, without options) | kg (lb) | 165 (364) | 165 (364) | 165 (364) | 165 (364) |
1) Rated power of a typ. 4-pole standard induction motor based on base-load current IL or IH at 400 V 3 AC/50 Hz. 2) Rated power of a typ. 4-pole standard induction motor based on base-load current IL or IH at 460 V 3 AC/60 Hz. 3) The base-load current IL is based on a duty cycle of 110 % for 60 s or 135 % for 3 s with a duty cycle duration of 300 s (see overload capability characteristics). 4) The base-load current IH is based on a duty cycle of 150 % for 60 s with a duty cycle duration of 300 s (see overload capability characteristics). 5) The current values given here are based on the rated output current. 6) If the drive closed-loop control is still to remain active when the main line supply fails, then the converter must be provided with an external 24 V DC supply. 7) 10 ms value from current-time characteristic for reliable tripping of installed protection devices. If the minimum short-circuit current is not reached, the tripping time of the fuses is increased, which can lead to damage. 8) Longer cable lengths are available on request. Note: The power data in hp units are based on the NEC/CEC standards for the North American market. Information on the line connection, motor connection and cabinet grounding can be found in section Cable cross-sections and connections. Line voltage 380 ... 480 V 3 AC | SINAMICS G120P Cabinet converter cabinet units |
---|
| 6SL3710-1PE33‑0.A0-Z | 6SL3710-1PE33‑7.A0-Z | 6SL3710-1PE34‑6.A0-Z | 6SL3710-1PE35‑8.A0-Z | 6SL3710-1PE36‑6.A0-Z | 6SL3710-1PE37‑4.A0-Z |
---|
Rated power | | | | | | | | | kW | 160 | 200 | 250 | 315 | 355 | 400 | | hp | 200 | 250 | 300 | 400 | 450 | 500 | | kW | 132 | 160 | 200 | 250 | 250 | 315 | | hp | 150 | 200 | 200 | 300 | 300 | 350 | Output current | | | | | | | | - Rated current Irated (400 V ±10 %)
| A | 300 | 370 | 460 | 585 | 655 | 735 | - Rated current Irated (480 V ±10 %)
| A | 245 | 308 | 369 | 487 | 526 | 602 | - Base-load current IL (400 V ±10 %) 3)
| A | 290 | 360 | 450 | 570 | 640 | 720 | - Base-load current IL (480 V ±10 %) 3)
| A | 240 | 302 | 361 | 477 | 515 | 590 | - Base-load current IH (400 V ±10 %) 4)
| A | 240 | 296 | 368 | 468 | 491 | 551 | - Base-load current IH (480 V ±10 %) 4)
| A | 196 | 247 | 295 | 390 | 394 | 452 | | A | 392 | 486 | 608 | 770 | 864 | 972 | Input current | | | | | | | | - Rated current Irated (400 V ±10 %) 5)
| A | 317 | 375 | 469 | 597 | 668 | 750 | - Rated current Irated (480 V ±10 %) 5)
| A | 262 | 314 | 376 | 497 | 536 | 614 | - Base-load current IL (400 V ±10 %) 3)
| A | 307 | 365 | 459 | 585 | 654 | 735 | - Base-load current IL (480 V ±10 %) 3)
| A | 257 | 308 | 368 | 486 | 525 | 602 | - Base-load current IH (400 V ±10 %) 4)
| A | 254 | 300 | 375 | 477 | 501 | 562 | - Base-load current IH (480 V ±10 %) 4)
| A | 210 | 251 | 301 | 397 | 402 | 461 | | A | 415 | 493 | 620 | 785 | 881 | 992 | Current requirement, 24 V DC auxiliary power supply 6) | | | | | | | | | A | 1 | 1 | 1 | 1 | 1 | 1 | | A | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | Short-circuit current rating acc. to IEC in conjunction with the specified fuses without/with option L26 | kA | 65/65 | 65/65 | 65/50 | 65/50 | 65/50 | 65/50 | Minimum short-circuit current 7) | | | | | | | | | A | 3500 | 4500 | 7000 | 10000 | 11000 | 13000 | | A | 9500 | 14000 | 20000 | 20000 | 30000 | 30000 | Power loss, max. at Irated (400 V/40 °C), without options | kW | 4.01 | 4.871 | 5.683 | 7.358 | 8.287 | 9.101 | Coolant | | Air | Air | Air | Air | Air | Air | Coolant requirements | m3/s (ft3/s) | 0.21 (7.42) | 0.21 (7.42) | 0.21 (7.42) | 0.6 (21.2) | 0.6 (21.2) | 0.6 (21.2) | Sound pressure level LpA (1 m) at 50/60 Hz | | | | | | | | | dB | 66/66 | 66/66 | 66/66 | 69/69 | 69/69 | 69/69 | | dB | 63/63 | 63/63 | 63/63 | 66/66 | 66/66 | 66/66 | Cable length, max. between Power Module and motor | | | | | | | | - When compliant with Categories C2 and C3 according to EN 61800‑3
shielded
| m (ft) | 150 (492) | 150 (492) | 150 (492) | 150 (492) | 150 (492) | 150 (492) | - When non-compliant with the limit values for RI suppression and without output reactor
unshielded
| m (ft) | 200 (656) | 200 (656) | 200 (656) | 200 (656) | 200 (656) | 200 (656) | - When non-compliant with the limit values for RI suppression with output reactor
shielded/unshielded
| m (ft) | 300/450 (984/1476) | 300/450 (984/1476) | 300/450 (984/1476) | 300/450 (984/1476) | 300/450 (984/1476) | 300/450 (984/1476) | Dimensions | | | | | | | | | mm (in) | 1000/600 (39.37/23.62) | 1000/600 (39.37/23.62) | 1000/600 (39.37/23.62) | 1200 9)/800 (47.24 9)/31.50) | 1200 9)/800 (47.24 9)/31.50) | 1200 9)/800 (47.24 9)/31.50) | | mm (in) | 2000 (78.74) | 2000 (78.74) | 2000 (78.74) | 2000 (78.74) | 2000 (78.74) | 2000 (78.74) | | mm (in) | 600 (23.62) | 600 (23.62) | 600 (23.62) | 600 (23.62) | 600 (23.62) | 600 (23.62) | Frame size | | GX | GX | GX | HX | HX | HX | Weight Versions A/C (degree of protection IP20, without options) | kg (lb) | 370/290 (816/639) | 380/300 (838/661) | 400/300 (882/661) | 500/430 (1102/948) | 500/440 (1102/970) | 530/440 (1169/970) |
1) Rated power of a typ. 4-pole standard induction motor based on base-load current IL or IH at 400 V 3 AC/50 Hz. 2) Rated power of a typ. 4-pole standard induction motor based on base-load current IL or IH at 460 V 3 AC/60 Hz. 3) The base-load current IL is based on a duty cycle of 110 % for 60 s or 135 % for 3 s with a duty cycle duration of 300 s (see overload capability characteristics). 4) The base-load current IH is based on a duty cycle of 150 % for 60 s with a duty cycle duration of 300 s (see overload capability characteristics). 5) The current values given here are based on the rated output current. 6) If the drive closed-loop control is still to remain active when the main line supply fails, then the converter must be provided with an external 24 V DC supply. 7) 10 ms value from current-time characteristic for reliable tripping of installed protection devices. If the minimum short-circuit current is not reached, the tripping time of the fuses is increased, which can lead to damage. 8) The cabinet height increases by 300 mm (11.81 in) for IP21 degree of protection, and by 400 mm (15.75 in) for IP23, IP43 and IP54 degrees of protection. 9) The specified cabinet widths increase depending on the options selected. For details, see description of option L01. Note: The power data in hp units are based on the NEC/CEC standards for the North American market. Information on the line connection, motor connection and cabinet grounding can be found in section Cable cross-sections and connections. Line voltage 380 ... 480 V 3 AC | SINAMICS G120P Cabinet converter cabinet units |
---|
| 6SL3710-1PE38-4AA0-Z | 6SL3710-1PE38-8AA0-Z | 6SL3710-1PE41-0AA0-Z |
---|
Rated power | | | | | | kW | 450 | 500 | 560 | | hp | 500 | 600 | 700 | | kW | 355 | 400 | 450 | | hp | 450 | 500 | 500 | Output current | | | | | - Rated current Irated (400 V ±10 %)
| A | 840 | 910 | 1021 | - Rated current Irated (480 V ±10 %)
| A | 677 | 739 | 847 | - Base-load current IL (400 V ±10 %) 3)
| A | 820 | 890 | 1000 | - Base-load current IL (480 V ±10 %) 3)
| A | 663 | 724 | 830 | - Base-load current IH (400 V ±10 %) 4)
| A | 672 | 728 | 786 | - Base-load current IH (480 V ±10 %) 4)
| A | 542 | 591 | 652 | | A | 1107 | 1202 | 1350 | Input current | | | | | - Rated current Irated (400 V ±10 %) 5)
| A | 870 | 945 | 1061 | - Rated current Irated (480 V ±10 %) 5)
| A | 702 | 767 | 880 | - Base-load current IL (400 V ±10 %) 3)
| A | 850 | 925 | 1039 | - Base-load current IL (480 V ±10 %) 3)
| A | 687 | 751 | 862 | - Base-load current IH (400 V ±10 %) 4)
| A | 696 | 756 | 816 | - Base-load current IH (480 V ±10 %) 4)
| A | 561 | 614 | 677 | | A | 1147 | 1248 | 1402 | Current requirement, 24 V DC auxiliary power supply 6) | A | 1 | 1 | 1 | Short-circuit current rating acc. to IEC in conjunction with the specified fuses without/with option L26 | kA | 65/65 | 65/65 | 65/65 | Minimum short-circuit current 7) | | | | | | A | 10400 | 14000 | 16000 | | A | 40000 | 40000 | 52000 | Power loss, max. at Irated (400 V/40 °C), without options | kW | 11.098 | 11.605 | 13.348 | Coolant | | Air | Air | Air | Coolant requirements | m3/s (ft3/s) | 0.7 (24.7) | 0.7 (24.7) | 0.7 (24.7) | Sound pressure level LpA (1 m) at 50/60 Hz | dB | 69/69 | 69/69 | 69/69 | Cable length, max. between Power Module and motor | | | | | - When compliant with Categories C2 and C3 according to EN 61800‑3
shielded
| m (ft) | 150 (492) | 150 (492) | 150 (492) | - When non-compliant with the limit values for RI suppression and without output reactor
unshielded
| m (ft) | 200 (656) | 200 (656) | 200 (656) | - When non-compliant with the limit values for RI suppression with output reactor
shielded/unshielded
| m (ft) | 300/450 (984/1476) | 300/450 (984/1476) | 300/450 (984/1476) | Dimensions | | | | | | mm (in) | 1200 (47.24) 9) | 1200 (47.24) 9) | 1200 (47.24) 9) | | mm (in) | 2000 (78.74) | 2000 (78.74) | 2000 (78.74) | | mm (in) | 600 (23.62) | 600 (23.62) | 600 (23.62) | Frame size | | JX | JX | JX | Weight (degree of protection IP20, without options) | kg (lb) | 655 (1444) | 676 (1490) | 681 (1501) |
1) Rated power of a typ. 4-pole standard induction motor based on base-load current IL or IH at 400 V 3 AC/50 Hz. 2) Rated power of a typ. 4-pole standard induction motor based on base-load current IL or IH at 460 V 3 AC/60 Hz. 3) The base-load current IL is based on a duty cycle of 110 % for 60 s or 135 % for 3 s with a duty cycle duration of 300 s (see overload capability characteristics). 4) The base-load current IH is based on a duty cycle of 150 % for 60 s with a duty cycle duration of 300 s (see overload capability characteristics). 5) The current values given here are based on the rated output current. 6) If the drive closed-loop control is still to remain active when the main line supply fails, then the converter must be provided with an external 24 V DC supply. 7) 10 ms value from current-time characteristic for reliable tripping of installed protection devices. If the minimum short-circuit current is not reached, the tripping time of the fuses is increased, which can lead to damage. 8) The cabinet height increases by 300 mm (11.8 in) for degree of protection IP21, and by 400 mm (15.7 in) for degrees of protection IP23, IP43 and IP54. 9) The specified cabinet widths increase depending on the options selected. For details, see description of options L00 and L01. Note: The power data in hp units are based on the NEC/CEC standards for the North American market. Information on the line connection, motor connection and cabinet grounding can be found in section Cable cross-sections and connections. Line voltage 500 ... 690 V 3 AC | SINAMICS G120P Cabinet converter cabinet units |
---|
| 6SL3710-1PG33-7 . A0-Z | 6SL3710-1PG34-0 . A0-Z | 6SL3710-1PG34-5 . A0-Z | 6SL3710-1PG35-2 . A0-Z |
---|
Rated power | | | | | | | kW | 315 | 355 | 400 | 450 | | hp | 350 | 400 | 450 | 450 | | kW | 250 | 315 | 355 | 400 | | hp | 250 | 300 | 350 | 450 | Output current | | | | | | - Rated current Irated (500 V ±10 %)
| A | 368 | 400 | 453 | 516 | - Rated current Irated (600 V ±10 %)
| A | 353 | 396 | 441 | 497 | - Rated current Irated (690 V ±10 %)
| A | 340 | 393 | 430 | 480 | - Base-load current IL (500 V ±10 %) 3)
| A | 361 | 392 | 443 | 505 | - Base-load current IL (690 V ±10 %) 3)
| A | 330 | 385 | 420 | 470 | - Base-load current IH (500 V ±10 %) 4)
| A | 295 | 320 | 367 | 423 | - Base-load current IH (690 V ±10 %) 4)
| A | 272 | 314 | 348 | 394 | | A | 487 | 529 | 598 | 682 | Input current | | | | | | - Rated current Irated (500 V ±10 %) 5)
| A | 383 | 416 | 471 | 537 | - Rated current Irated (600 V ±10 %) 5)
| A | 367 | 412 | 459 | 517 | - Rated current Irated (690 V ±10 %) 5)
| A | 354 | 409 | 447 | 499 | - Base-load current IL (500 V ±10 %) 3)
| A | 375 | 408 | 461 | 526 | - Base-load current IL (690 V ±10 %) 3)
| A | 343 | 401 | 437 | 489 | - Base-load current IH (500 V ±10 %) 4)
| A | 307 | 333 | 381 | 440 | - Base-load current IH (690 V ±10 %) 4)
| A | 283 | 327 | 362 | 410 | | A | 507 | 550 | 623 | 710 | Current requirement, 24 V DC auxiliary power supply 6) | | | | | | | A | 1.0 | 1.0 | 1.0 | 1.0 | | A | 0.5 | 0.5 | 0.5 | 0.5 | Short-circuit current rating acc. to IEC in conjunction with the specified fuses without/with Option L26 | kA | 65/65 | 65/50 | 65/50 | 65/50 | Minimum short-circuit current 7) | | | | | | | A | 3500 | 4500 | 7000 | 8500 | | A | 10000 | 10500 | 13000 | 14600 | Power loss, max. at Irated (500 V/40 °C), without options | kW | 5.838 | 6.665 | 7.429 | 8.259 | Coolant | | Air | Air | Air | Air | Coolant requirements | m3/s (ft3/s) | 0.6 (21.2) | 0.6 (21.2) | 0.6 (21.2) | 0.6 (21.2) | Sound pressure level LpA (1 m) at 50/60 Hz | | | | | | | dB | 69/69 | 69/69 | 69/69 | 69/69 | Cable length, max. between Power Module and motor | | | | | | - When compliant with Categories C2 and C3 according to EN 61800‑3
shielded
| m (ft) | 150 (492) | 150 (492) | 150 (492) | 150 (492) | - When non-compliant with the limit values for RI suppression and without output reactor
unshielded
| m (ft) | 200 (656) | 200 (656) | 200 (656) | 200 (656) | - When non-compliant with the limit values for RI suppression with output reactor
shielded/unshielded
| m (ft) | 300/450 (984/1476) | 300/450 (984/1476) | 300/450 (984/1476) | 300/450 (984/1476) | Dimensions | | | | | | | mm (in) | 1200 (47.24) | 1200 (47.24) | 1200 (47.24) | 1200 (47.24) | | mm (in) | 2000 (78.74) | 2000 (78.74) | 2000 (78.74) | 2000 (78.74) | | mm (in) | 600 (23.62) | 600 (23.62) | 600 (23.62) | 600 (23.62) | Frame size | | HX | HX | HX | HX | Weight Versions A/C (degree of protection IP20, without options) | kg (lb) | 515/435 (1135/959) | 522/442 (1151/974) | 522/442 (1151/974) | 535/455 (1179/1003) |
1) Rated power of a typ. 4-pole standard induction motor based on base-load current IL or IH at 690 V 3 AC/50 Hz. 2) Rated power of a typ. 4-pole standard induction motor based on base-load current IL or IH at 575 V 3 AC/60 Hz. 3) The base-load current IL is based on a duty cycle of 110 % for 60 s or 135 % for 3 s with a duty cycle duration of 300 s (see overload capability characteristics). 4) The base-load current IH is based on a duty cycle of 150 % for 60 s with a duty cycle duration of 300 s (see overload capability characteristics). 5) The current values given here are based on the rated output current. 6) If the drive closed-loop control is still to remain active when the main line supply fails, then the converter must be provided with an external 24 V DC supply. 7) 10 ms value from current-time characteristic for reliable tripping of installed protection devices. If the minimum short-circuit current is not reached, the tripping time of the fuses is increased, which can lead to damage. 8) The cabinet height increases by 300 mm (11.8 in) for degrees of protection IP20 and IP21, and by 400 mm (15.7 in) for degrees of protection IP23, IP43 and IP54. Line voltage 500 ... 690 V 3 AC | SINAMICS G120P Cabinet converter cabinet units |
---|
| 6SL3710-1PG35-8AA0-Z | 6SL3710-1PG36-5AA0-Z | 6SL3710-1PG37-2AA0-Z |
---|
Rated power | | | | | | kW | 500 | 560 | 630 | | hp | 500 | 600 | 700 | | kW | 450 | 500 | 560 | | hp | 450 | 500 | 500 | Output current | | | | | - Rated current Irated (500 V ±10 %)
| A | 581 | 654 | 725 | - Rated current Irated (600 V ±10 %)
| A | 557 | 623 | 693 | - Rated current Irated (690 V ±10 %)
| A | 535 | 595 | 665 | - Base-load current IL (500 V ±10 %) 3)
| A | 569 | 640 | 710 | - Base-load current IL (690 V ±10 %) 3)
| A | 520 | 580 | 650 | - Base-load current IH (500 V ±10 %) 4)
| A | 482 | 523 | 580 | - Base-load current IH (690 V ±10 %) 4)
| A | 444 | 476 | 532 | | A | 768 | 864 | 959 | Input current | | | | | - Rated current Irated (500 V ±10 %) 5)
| A | 596 | 679 | 753 | - Rated current Irated (600 V ±10 %) 5)
| A | 578 | 647 | 720 | - Rated current Irated (690 V ±10 %) 5)
| A | 555 | 618 | 690 | - Base-load current IL (500 V ±10 %) 3)
| A | 591 | 665 | 737 | - Base-load current IL (690 V ±10 %) 3)
| A | 540 | 602 | 675 | - Base-load current IH (500 V ±10 %) 4)
| A | 501 | 543 | 602 | - Base-load current IH (690 V ±10 %) 4)
| A | 461 | 494 | 552 | | A | 798 | 897 | 995 | Current requirement, 24 V DC auxiliary power supply 6) | A | 1 | 1 | 1 | Short-circuit current rating acc. to IEC in conjunction with the specified fuses | kA | 65 | 65 | 65 | Minimum short-circuit current 7) | | | | | | A | 10000 | 11000 | 13000 | | A | 16000 | 20000 | 21000 | Power loss, max. at Irated (500 V/40 °C), without options | kW | 8.688 | 9.468 | 10.688 | Coolant | | Air | Air | Air | Coolant requirements | m3/s (ft3/s) | 0.7 (24.7) | 0.7 (24.7) | 0.7 (24.7) | Sound pressure level LpA (1 m) at 50/60 Hz | dB | 69/69 | 69/69 | 69/69 | Cable length, max. between Power Module and motor | | | | | - When compliant with Categories C2 and C3 according to EN 61800‑3
shielded
| m (ft) | 150 (492) | 150 (492) | 150 (492) | - When non-compliant with the limit values for RI suppression and without output reactor
unshielded
| m (ft) | 200 (656) | 200 (656) | 200 (656) | - When non-compliant with the limit values for RI suppression with output reactor
shielded/unshielded
| m (ft) | 300/450 (984/1476) | 300/450 (984/1476) | 300/450 (984/1476) | Dimensions | | | | | | mm (in) | 1200 (47.24) 9) | 1200 (47.24) 9) | 1200 (47.24) 9) | | mm (in) | 2000 (78.74) | 2000 (78.74) | 2000 (78.74) | | mm (in) | 600 (23.62) | 600 (23.62) | 600 (23.62) | Frame size | | JX | JX | JX | Weight (degree of protection IP20, without options) | kg (lb) | 654 (1442) | 697 (1537) | 716 (1579) |
1) Rated power of a typ. 4-pole standard induction motor based on base-load current IL or IH at 690 V 3 AC/50 Hz. 2) Rated power of a typ. 4-pole standard induction motor based on base-load current IL or IH at 575 V 3 AC/60 Hz. 3) The base-load current IL is based on a duty cycle of 110 % for 60 s or 135 % for 3 s with a duty cycle duration of 300 s (see overload capability characteristics). 4) The base-load current IH is based on a duty cycle of 150 % for 60 s with a duty cycle duration of 300 s (see overload capability characteristics). 5) The current values given here are based on the rated output current. 6) If the drive closed-loop control is still to remain active when the main line supply fails, then the converter must be provided with an external 24 V DC supply. 7) 10 ms value from current-time characteristic for reliable tripping of installed protection devices. If the minimum short-circuit current is not reached, the tripping time of the fuses is increased, which can lead to damage. 8) The cabinet height increases by 300 mm (11.8 in) for degree of protection IP21, and by 400 mm (15.7 in) for degrees of protection IP23, IP43 and IP54. 9) The specified cabinet widths increase depending on the options selected. For details, see description of option L00. Note: The power data in hp units are based on the NEC/CEC standards for the North American market. Information on the line connection, motor connection and cabinet grounding can be found in section Cable cross-sections and connections.
|
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Àðìàòóðà DENDOR
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Äàò÷èêè è èçìåðèòåëè
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ðåãóëÿòîðû è ðåãèñòðàòîðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ïíåâìàòè÷åñêîå îáîðóäîâàíèå
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Êðàíû è Êëàïàíû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Èçìåðèòåëüíûå ïðèáîðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ñèñòåìû áåñïðîâîäíîãî óïðàâëåíèÿ «óìíûé äîì»
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Áåñêîíòàêòíûå âûêëþ÷àòåëè Êîíå÷íûå âûêëþ÷àòåëè Îïòè÷åñêèå äàò÷èêè Ýíêîäåðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Óñòàíîâêà óìÿã÷åíèÿ
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Óñòàíîâêà îáåçæåëåçèâàíèÿ
|