The most important directives and standards are listed below. These are used as basis for the SINAMICS G120P Cabinet drive inverter cabinet units and they must be carefully observed to achieve an EMC-compliant configuration that is safe both functionally and in operation.
European directives
2014/35/EU
Low-voltage directive:
Directive of the European Parliament and Council of February 26, 2014 for the harmonization of the laws of the member states relating to the provision of electrical equipment designed for use within certain voltage limits on the market (amended version)
2014/30/EU
EMC directive:
Directive of the European Parliament and Council of February 26, 2014 for the harmonization of the laws of the member states relating to electromagnetic compatibility (amended version)
2006/42/EC
Machinery directive:
The directive of the European Parliament and Council of May 17, 2006 on machinery and for changing Directive 95/16/EC (amendment)
European standards
EN 60146?1?1
Semiconductor converters – General requirements and line-commutated converters
Part 1?1: Specification of basic requirements
EN 60204?1
Electrical equipment of machines
Part 1: General requirements
EN 60529
Degrees of protection provided by enclosures (IP code)
EN 61800?2
Adjustable speed electrical power drive systems
Part 2: General requirements – Rating specifications for low-voltage adjustable frequency a.c. power drive systems
EN 61800?3
Adjustable speed electrical power drive systems
Part 3: EMC product standard including specific test methods
EN 61800-5-1
Adjustable speed electrical power drive systems
Part 5: Safety requirements
Main section 1: Electrical and thermal requirements
General technical specifications
Electrical specifications
Line voltages and power ranges
380 ... 480 V 3 AC ±10 %, 110 ... 560 kW (148 ... 751 hp)
500 ... 690 V 3 AC ±10 %, 500 ... 630 kW (671 ... 845 hp)
Output ranges
110 ... 560 kW (148 ... 751 hp)
Line system configurations
Grounded TN/TT systems and non-grounded IT systems
Line frequency
47 ... 63 Hz
Output frequency
0 ... 100 Hz
Offset factor cos ?
0.96
Power factor ?
0.75 ... 0.93
Efficiency
>98%
Overvoltage category
III to EN 61800?5?1
Closed-loop control modes
Vector control without sensor or U/f control
Fixed speeds
15 fixed speeds plus 1 minimum speed, parameterizable (in the default setting, 3 fixed setpoints plus 1 minimum speed are selectable using terminal block/fieldbus system)
Skipped speed ranges
4, parameterizable
Setpoint resolution of the Control Unit
0.01 Hz
12 bit analog
Braking operation
DC braking, dynamic braking with optional Braking Module
Mechanical specifications
Degree of protection
IP20 (higher degrees of protection up to IP54 optional)
Protection class
I acc. to EN 61800?5?1
Touch protection
According to EN 50274 and BGV A3 when used as intended
Cabinet system
Schafer IS?1, doors with double-barb lock, base plates with cable entry possibilities, crane transport aid
Paint finish
RAL 7035 (indoor requirements)
Type of cooling
Forced air cooling AF to EN 60146
Ambient conditions
Storage
Transport
Operation
Ambient temperature
-25 ... +55 °C
-25 ... +70 °C above -40 °C for 24 hours
0 ... 40 °C (32 ... 104 °F) up to 50 °C (122 °F) see derating data
Relative humidity
(condensation not permissible)
5 ... 95 %
Class 1K4 to EN 60721?3?1
5 ... 95 %
Class 2K3 to EN 60721?3?2
5 ... 95 %
Class 3K3 to EN 60721?3?3
Environmental class/harmful chemical substances
Class 1C2 acc. to EN 60721?3?1
Class 2C2 acc. to EN 60721?3?2
Class 3C2 acc. to EN 60721?3?3
Organic/biological influences
Class 1B1 acc. to EN 60721?3?1
Class 2B1 acc. to EN 60721?3?2
Class 3B1 according to EN 60721?3?3 Restriction: No conductive dust particles permitted
Degree of pollution
2 acc. to EN 61800?5?1
Installation altitude
Up to 1000 m (3281 ft) above sea level without derating > 1000 m (3281 ft) see derating data
Mechanical strength
Storage
Transport 2)
Operation
Vibratory load
Class 1M2 acc. to EN 60721?3?1
Class 2M2 acc. to EN 60721?3?2
Class 3M2 acc. to EN 60721?3?3
Deflection
1.5 mm at 5 ... 9 Hz
3.5 mm at 2 ... 9 Hz
0.075 mm at 10 ... 58 Hz
Acceleration
5 m/s2 at > 9 ... 200 Hz
10 m/s2 at > 9 ... 200 Hz
10 m/s2 at > 58 ... 200 Hz
Shock load
Class 1M2 acc. to EN 60721?3?1
Class 2M2 acc. to EN 60721?3?2
Class 3M2 acc. to EN 60721?3?3
Acceleration
40 m/s2 at 22 ms
150 m/s2 at 11 ms
50 m/s2 (5 ? g)/30 ms 150 m/s2 (15 ? g)/11 ms
Standards
Compliance with standards
cULus, CE, RCM, EAC, KC, SEMI F47 3)
CE marking
According to EMC Directive 2014/30/EU, Low Voltage Directive 2014/35/EU, Machinery Directive 2006/42/EC
Radio interference suppression
The SINAMICS G120P Cabinet inverter systems are not designed for connection to the public power network ("first environment"). Radio interference suppression is compliant with the EMC product standard for variable-speed drives EN 61800-3 "Second environment" (industrial line supplies). The equipment can cause electromagnetic interference when it is connected to the public network. However, if supplementary measures are taken (e.g. line filter, see option L00) operation in the "first environment" is possible.
Deviations from the specified classes are underlined.
1) For the option L01, the line voltage is limited to 380 to 415 V AC ± 10%.
2) In transport packaging.
3) SEMI F47 for frame size JX available soon
Line voltage 380 ... 480 V 3 AC
SINAMICS G120P Cabinet drive inverter cabinet units
6SL3710-1PE32?1.A0-Z
6SL3710-1PE32?5.A0-Z
6SL3710-1PE33?0.A0-Z
6SL3710-1PE33?7.A0-Z
6SL3710-1PE34?6.A0-Z
Rated power
At IL 400 V/50 Hz 1)
kW
110
132
160
200
250
At IL 460 V/60 Hz 2)
hp
125
150
200
250
300
At IH 400 V/50 Hz 1)
kW
90
110
132
160
200
At IH 460 V/60 Hz 2)
hp
100
100
150
200
200
Output current
Rated current Irated (400 V ±10 %)
A
205
245
300
370
460
Rated current Irated (480 V ±10 %)
A
160
184
245
308
369
Base-load current IL (400 V ±10 %) 3)
A
200
240
290
360
450
Base-load current IL (480 V ±10 %) 3)
A
156
180
240
302
361
Base-load current IH (400 V ±10 %) 4)
A
164
196
240
296
368
Base-load current IH (480 V ±10 %) 4)
A
128
147
196
247
295
Output current, max.
A
270
324
392
486
608
Input current
Rated current Irated (400 V ±10 %) 5)
A
218
262
317
375
469
Rated current Irated (480 V ±10 %) 5)
A
171
197
262
314
376
Base-load current IL (400 V ±10 %) 3)
A
213
257
307
365
459
Base-load current IL (480 V ±10 %) 3)
A
167
193
257
308
368
Base-load current IH (400 V ±10 %) 4)
A
175
210
254
300
375
Base-load current IH (480 V ±10 %) 4)
A
137
157
210
251
301
Input current, max.
A
288
347
415
493
620
Current requirement, 24 V DC auxiliary power supply 6)
Version A
A
1
1
1
1
1
Version C
A
0.5
0.5
0.5
0.5
0.5
Short-circuit current rating acc. to IEC
in conjunction with the specified fuses without/with Option L26
kA
65/65
65/65
65/65
65/65
65/50
Minimum short-circuit current 7)
For 3NE1 fuses
A
3000
3600
4400
5200
7000
For 3NA3 fuses
A
5800
7300
9500
14000
20000
Power loss, max.
at Irated (400 V/40 °C)
Version A
kW
3.377
3.939
4.543
5.681
6.376
Version C
kW
2.831
3.255
3.901
4.777
5.482
Coolant
of air
of air
of air
of air
of air
Coolant requirements
m3/s (ft3/s)
0.21 (7.4)
0.21 (7.4)
0.21 (7.4)
0.21 (7.4)
0.21 (7.4)
Sound pressure level LpA(1 m) at 50/60 Hz
Version A
dB
66/66
66/66
66/66
66/66
66/66
Version C
dB
63/63
63/63
63/63
63/63
63/63
Cable length, max.
between Power Module and motor
When compliant with Categories C2 and C3 according to EN 61800?3 shielded
m (ft)
100 (328.10)
100 (328.10)
100 (328.10)
100 (328.10)
100 (328.10)
When non-compliant with the limit values for RI suppression and without output reactor unshielded
m (ft)
200 (656)
200 (656)
200 (656)
200 (656)
200 (656)
When non-compliant with the limit values for RI suppression with output reactor shielded/unshielded
m (ft)
300/450 (984.30/1476.45)
300/450 (984.30/1476.45)
300/450 (984.30/1476.45)
300/450 (984.30/1476.45)
300/450 (984.30/1476.45)
Dimensions
Width for version A/C
mm (in)
1000/600 (39.37/23.62)
1000/600 (39.37/23.62)
1000/600 (39.37/23.62)
1000/600 (39.37/23.62)
1000/600 (39.37/23.62)
Height8)
mm (in)
2000 (78.7)
2000 (78.7)
2000 (78.7)
2000 (78.7)
2000 (78.7)
Depth
mm (in)
600 (23.62)
600 (23.62)
600 (23.62)
600 (23.62)
600 (23.62)
Frame size
GX
GX
GX
GX
GX
Weight
Versions A/C (degree of protection IP20, without options)
kg (lb)
360/290 (794/639)
360/290 (794/639)
370/290 (816/639)
380/300 (838/661)
400/300 (882/661)
1) Rated power of a typ. 4-pole standard induction motor based on base-load current IL or IH at 400 V 3 AC/50 Hz.
2) Rated power of a typ. 4-pole standard induction motor based on base-load current IL or IH at 460 V 3 AC/60 Hz.
3) The base-load current IL is based on a duty cycle of 110% for 60 s or 135 % for 3 s with a duty cycle duration of 300 s (see overload capability characteristics).
4) The base-load current IH is based on a duty cycle of 150% for 60 s with a duty cycle duration of 300 s (see overload capability characteristics).
5) The current values given here are based on the rated output current.
6)If the drive closed-loop control is still to remain active when the main line supply fails, then the equipment must be provided with an external 24 V DC supply.
7) 10 ms value from current-time characteristic for reliable tripping of installed protection devices. If the minimum short circuit current is not reached, the tripping time of the fuses is increased, which can lead to damage.
8)Version A: The cabinet height increases by 300 mm with IP20 and IP21 degrees of protection, and by 400 mm with IP23, IP43 and IP54 degrees of protection.Version C: The cabinet height increases by 300 mm for IP21 degree of protection, and by 400 mm for IP23, IP43 and IP54 degrees of protection.
Note:
The power data in hp units are based on the NEC/CEC standards for the North American market.
Information on the line connection, motor connection and cabinet grounding can be found in section Cable cross-sections and connections.
Line voltage 380 ... 480 V 3 AC
SINAMICS G120P Cabinet drive inverter cabinet units
6SL3710-1PE35?8.A0-Z
6SL3710-1PE36?6.A0-Z
6SL3710-1PE37?4.A0-Z
Rated power
At IL 400 V/50 Hz 1)
kW
315
355
400
At IL 460 V/60 Hz 2)
hp
400
450
500
At IH 400 V/50 Hz 1)
kW
250
250
315
At IH 460 V/60 Hz 2)
hp
300
300
350
Output current
Rated current Irated (400 V ±10 %)
A
585
655
735
Rated current Irated (480 V ±10 %)
A
487
526
602
Base-load current IL (400 V ±10 %) 3)
A
570
640
720
Base-load current IL (480 V ±10 %) 3)
A
477
515
590
Base-load current IH (400 V ±10 %) 4)
A
468
491
551
Base-load current IH (480 V ±10 %) 4)
A
390
394
452
Output current, max.
A
770
864
972
Input current
Rated current Irated (400 V ±10 %) 5)
A
597
668
750
Rated current Irated (480 V ±10 %) 5)
A
497
536
614
Base-load current IL (400 V ±10 %) 3)
A
585
654
735
Base-load current IL (480 V ±10 %) 3)
A
486
525
602
Base-load current IH (400 V ±10 %) 4)
A
477
501
562
Base-load current IH (480 V ±10 %) 4)
A
397
402
461
Input current, max.
A
785
881
992
Current requirement, 24 V DC auxiliary power supply 6)
Version A
A
1
1
1
Version C
A
0.5
0.5
0.5
Short-circuit current rating acc. to IEC
in conjunction with the specified fuses without/with Option L26
kA
65/50
65/50
65/50
Minimum short-circuit current 7)
For 3NE1 fuses
A
10000
11000
13000
For 3NA3 fuses
A
20000
30000
30000
Power loss, max.
at Irated (400 V/40 °C)
Version A
kW
8.478
9.443
9.907
Version C
kW
7.143
8.026
8.824
Coolant
of air
of air
of air
Coolant requirements
m3/s (ft3/s)
0.6 (21.2)
0.6 (21.2)
0.6 (21.2)
Sound pressure level LpA(1 m) at 50/60 Hz
Version A
dB
69/69
69/69
69/69
Version C
dB
66/66
66/66
66/66
Cable length, max.
between Power Module and motor
When compliant with Categories C2 and C3 according to EN 61800?3 shielded
m (ft)
100 (328.10)
100 (328.10)
100 (328.10)
When non-compliant with the limit values for RI suppression and without output reactor unshielded
m (ft)
200 (656.20)
200 (656.20)
200 (656.20)
When non-compliant with the limit values for RI suppression with output reactor shielded/unshielded
m (ft)
300/450 (984.30/1476.45)
300/450 (984.30/1476.45)
300/450 (984.30/1476.45)
Dimensions
Width for version A/C
mm (in)
1200 9)/800
1200 9)/800
1200 9)/800
Height8)
mm (in)
2000 (78.7)
2000 (78.7)
2000 (78.7)
Depth
mm (in)
600 (23.62)
600 (23.62)
600 (23.62)
Frame size
HX
HX
HX
Weight
Versions A/C (degree of protection IP20, without options)
kg (lb)
500/430 (1102/948)
500/440 (1102/970)
530/440 (1169/970)
1) Rated power of a typ. 4-pole standard induction motor based on base-load current IL or IH at 400 V 3 AC/50 Hz.
2) Rated power of a typ. 4-pole standard induction motor based on base-load current IL or IH at 460 V 3 AC/60 Hz.
3) The base-load current IL is based on a duty cycle of 110% for 60 s or 135 % for 3 s with a duty cycle duration of 300 s (see overload capability characteristics).
4) The base-load current IH is based on a duty cycle of 150% for 60 s with a duty cycle duration of 300 s (see overload capability characteristics).
5) The current values given here are based on the rated output current.
6)If the drive closed-loop control is still to remain active when the main line supply fails, then the equipment must be provided with an external 24 V DC supply.
7) 10 ms value from current-time characteristic for reliable tripping of installed protection devices. If the minimum short circuit current is not reached, the tripping time of the fuses is increased, which can lead to damage.
8) The cabinet height increases by 300 mm (11.81 in) for IP21 degree of protection, and by 400 mm (15.75 in) for IP23, IP43 and IP54 degrees of protection.
9) The specified cabinet widths increase depending on the options selected. For details, see description of option L01.
Note:
The power data in hp units are based on the NEC/CEC standards for the North American market.
Information on the line connection, motor connection and cabinet grounding can be found in section Cable cross-sections and connections.
Line voltage 380 ... 480 V 3 AC
SINAMICS G120P Cabinet drive inverter cabinet units
6SL3710-1PE38-4AA0-Z
6SL3710-1PE38-8AA0-Z
6SL3710-1PE41-0AA0-Z
Rated power
At IL 400 V/50 Hz 1)
kW
450
500
560
At IL 460 V/60 Hz 2)
hp
500
600
700
At IH 400 V/50 Hz 1)
kW
355
400
450
At IH 460 V/60 Hz 2)
hp
450
500
500
Output current
Rated current Irated (400 V ±10 %)
A
840
910
1021
Rated current Irated (480 V ±10 %)
A
677
739
847
Base-load current IL (400 V ±10 %) 3)
A
820
890
1000
Base-load current IL (480 V ±10 %) 3)
A
663
724
830
Base-load current IH (400 V ±10 %) 4)
A
672
728
786
Base-load current IH (480 V ±10 %) 4)
A
542
591
652
Output current, max.
A
1107
1202
1350
Input current
Rated current Irated (400 V ±10 %) 5)
A
870
945
1061
Rated current Irated (480 V ±10 %) 5)
A
702
767
880
Base-load current IL (400 V ±10 %) 3)
A
850
925
1039
Base-load current IL (480 V ±10 %) 3)
A
687
751
862
Base-load current IH (400 V ±10 %) 4)
A
696
756
816
Base-load current IH (480 V ±10 %) 4)
A
561
614
677
Input current, max.
A
1147
1248
1402
Current requirement, 24 V DC auxiliary power supply 6)
A
1
1
1
Short-circuit current rating acc. to IEC
in conjunction with the specified fuses without/with option L26
kA
65/65
65/65
65/65
Minimum short-circuit current 7)
For 3NE1 fuses
A
10400
14000
16000
For 3NA3 fuses
A
40000
40000
52000
Power loss, max.
At Irated (400 V/40 °C)
kW
10.95
11.354
12.997
Coolant
Air
Air
Air
Coolant requirements
m3/s (ft3/s)
0.7 (24.7)
0.7 (24.7)
0.7 (24.7)
Sound pressure level LpA(1 m) at 50/60 Hz
dB
69/69
69/69
69/69
Cable length, max.
between Power Module and motor
When compliant with Categories C2 and C3 according to EN 61800?3 shielded
m (ft)
100 (328)
100 (328)
100 (328)
When non-compliant with the limit values for RI suppression and without output reactor unshielded
m (ft)
200 (656)
200 (656)
200 (656)
When non-compliant with the limit values for RI suppression with output reactor shielded/unshielded
m (ft)
300/450 (984/1476)
300/450 (984/1476)
300/450 (984/1476)
Dimensions
Width
mm (in)
1200 (47.2) 9)
1200 (47.2) 9)
1200 (47.2) 9)
Height8)
mm (in)
2000 (78.7)
2000 (78.7)
2000 (78.7)
Depth
mm (in)
600 (23.6)
600 (23.6)
600 (23.6)
Frame size
JX
JX
JX
Weight
(degree of protection IP20, without options)
kg (lb)
655 (1444)
676 (1490)
681 (1501)
1) Rated power of a typ. 4-pole standard induction motor based on base-load current IL or IH at 400 V 3 AC/50 Hz.
2) Rated power of a typ. 4-pole standard induction motor based on base-load current IL or IH at 460 V 3 AC/60 Hz.
3) The base-load current IL is based on a duty cycle of 110 % for 60 s or 135 % for 3 s with a duty cycle duration of 300 s (see overload capability characteristics).
4) The base-load current IH is based on a duty cycle of 150 % for 60 s with a duty cycle duration of 300 s (see overload capability characteristics).
5) The current values given here are based on the rated output current.
6) If the drive closed-loop control is still to remain active when the main line supply fails, then the inverter must be provided with an external 24 V DC supply.
7) 10 ms value from current-time characteristic for reliable tripping of installed protection devices. If the minimum short circuit current is not reached, the tripping time of the fuses is increased, which can lead to damage.
8) The cabinet height increases by 300 mm for degree of protection IP21, and by 400 mm (15.7 in) for degrees of protection IP23, IP43 and IP54.
9) The specified cabinet widths increase depending on the options selected. For details, see description of options L00 and L01.
Note:
The power data in hp units are based on the NEC/CEC standards for the North American market.
Information on the line connection, motor connection and cabinet grounding can be found in section Cable cross-sections and connections.
Line voltage 500 ... 690 V 3 AC
SINAMICS G120P Cabinet drive inverter cabinet units
6SL3710-1PG35-8AA0-Z
6SL3710-1PG36-5AA0-Z
6SL3710-1PG37-2AA0-Z
Rated power
At IL 690 V/50 Hz 1)
kW
500
560
630
At IL 575 V/60 Hz 2)
hp
500
600
700
At IH 690 V/50 Hz 1)
kW
450
500
560
At IH 575 V/60 Hz 2)
hp
450
500
500
Output current
Rated current Irated (500 V ±10 %)
A
581
654
725
Rated current Irated (600 V ±10 %)
A
557
623
693
Rated current Irated (690 V ±10 %)
A
535
595
665
Base-load current IL (500 V ±10 %) 3)
A
569
640
710
Base-load current IL (690 V ±10 %) 3)
A
520
580
650
Base-load current IH (500 V ±10 %) 4)
A
482
523
580
Base-load current IH (690 V ±10 %) 4)
A
444
476
532
Output current, max.
A
768
864
959
Input current
Rated current Irated (500 V ±10 %) 5)
A
596
679
753
Rated current Irated (600 V ±10 %) 5)
A
578
647
720
Rated current Irated (690 V ±10 %) 5)
A
555
618
690
Base-load current IL (500 V ±10 %) 3)
A
591
665
737
Base-load current IL (690 V ±10 %) 3)
A
540
602
675
Base-load current IH (500 V ±10 %) 4)
A
501
543
602
Base-load current IH (690 V ±10 %) 4)
A
461
494
552
Input current, max.
A
798
897
995
Current requirement, 24 V DC auxiliary power supply 6)
A
1
1
1
Short-circuit current rating acc. to IEC
in conjunction with the specified fuses
kA
65
65
65
Minimum short-circuit current 7)
For 3NE1 fuses
A
10000
11000
13000
For 3NA3 fuses
A
16000
20000
21000
Power loss, max.
At Irated (500 V/40 °C)
kW
9.122
9.972
11.221
Coolant
Air
Air
Air
Coolant requirements
m3/s (ft3/s)
0.7 (24.7)
0.7 (24.7)
0.7 (24.7)
Sound pressure level LpA(1 m) at 50/60 Hz
dB
69/69
69/69
69/69
Cable length, max.
between Power Module and motor
When compliant with Categories C2 and C3 according to EN 61800?3 shielded
m (ft)
100 (328)
100 (328)
100 (328)
When non-compliant with the limit values for RI suppression and without output reactor unshielded
m (ft)
200 (656)
200 (656)
200 (656)
When non-compliant with the limit values for RI suppression with output reactor shielded/unshielded
m (ft)
300/450 (984/1476)
300/450 (984/1476)
300/450 (984/1476)
Dimensions
Width
mm (in)
1200 (47.2) 9)
1200 (47.2) 9)
1200 (47.2) 9)
Height8)
mm (in)
2000 (78.7)
2000 (78.7)
2000 (78.7)
Depth
mm (in)
600 (23.6)
600 (23.6)
600 (23.6)
Frame size
JX
JX
JX
Weight
(degree of protection IP20, without options)
kg (lb)
654 (1442)
697 (1537)
716 (1579)
1) Rated power of a typ. 4-pole standard induction motor based on base-load current IL or IH at 690 V 3 AC/50 Hz.
2) Rated power of a typ. 4-pole standard induction motor based on base-load current IL or IH at 575 V 3 AC/60 Hz.
3) The base-load current IL is based on a duty cycle of 110 % for 60 s or 135 % for 3 s with a duty cycle duration of 300 s (see overload capability characteristics).
4) The base-load current IH is based on a duty cycle of 150 % for 60 s with a duty cycle duration of 300 s (see overload capability characteristics).
5) The current values given here are based on the rated output current.
6)If the drive closed-loop control is still to remain active when the main line supply fails, then the inverter must be provided with an external 24 V DC supply.
7) 10 ms value from current-time characteristic for reliable tripping of installed protection devices. If the minimum short circuit current is not reached, the tripping time of the fuses is increased, which can lead to damage.
8) The cabinet height increases by 300 mm for degree of protection IP21, and by 400 mm for degrees of protection IP23, IP43 and IP54.
9) The specified cabinet widths increase depending on the options selected. For details, see description of option L00.
Note:
The power data in hp units are based on the NEC/CEC standards for the North American market.
Information on the line connection, motor connection and cabinet grounding can be found in section Cable cross-sections and connections.
skener.ru
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Àðìàòóðà DENDOR
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Äàò÷èêè è èçìåðèòåëè
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ðåãóëÿòîðû è ðåãèñòðàòîðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ïíåâìàòè÷åñêîå îáîðóäîâàíèå
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Êðàíû è Êëàïàíû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Èçìåðèòåëüíûå ïðèáîðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ñèñòåìû áåñïðîâîäíîãî óïðàâëåíèÿ «óìíûé äîì»
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Áåñêîíòàêòíûå âûêëþ÷àòåëè Êîíå÷íûå âûêëþ÷àòåëè Îïòè÷åñêèå äàò÷èêè Ýíêîäåðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Óñòàíîâêà óìÿã÷åíèÿ
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Óñòàíîâêà îáåçæåëåçèâàíèÿ