Refer also to ordering examples for orders with order codes.
1) Applies to shielded motor cable lengths ?100 m. 2) The stopping requirements must be taken into account with this option. Additional braking units may be required. 3) If there is no 230 V AC power supply in the customer installation, it is essential to select option K74 in order to ensure proper functioning of the option. 4) If there is no 230 V AC power supply in the customer installation, it is essential to select option K74 in order to ensure power supply to the fan for frame sizes HX and JX. 5) The order code Y.. requires data in plain text.
Option selection matrixCertain options are mutually exclusive. The tables below only provide an overview. Please refer to the descriptions of the individual options for a precise description of options and other exclusions.
Interdependencies of mechanical and electrical options
1) The options L57 and L60 always require option L13. 2) Option L60 requires a braking unit for rapid standstill of the motor (option L62). Ordering examplesExample 1 Task: Solution: K96-K98 (selection of a fieldbus option on the CU) – required option The information to be stated on the order is therefore (taking PROFINET as an example): Example 2 Task: Solution: K97 (CU230P?2 DP Control Unit), The information to be stated on the order is therefore: Description of optionsD02 This option can be used to order documents such as circuit diagrams, terminal diagrams, layout diagrams, and dimension drawings in DXF format, in order to process them further in CAD systems, for example. They are supplied on the documentation CD in the desired language (standard is English/German, for other languages, see options D58, D60, D80, D91, D94). D04 Equipment documentation is supplied electronically on DVD-ROM as standard. If the customer also requires a hard copy of the documentation and selects option D04, the following documents will be shipped in a folder with the inverter:
Regardless of whether option D04 is selected, a hard copy of the safety and transportation guidelines and a registration form are always supplied. D14 If documents such as circuit diagrams, terminal diagrams, layout diagrams and dimensional drawings are required in advance for system engineering, a preliminary copy of the relevant documentation can be ordered with the inverter. These documents are then supplied electronically a few working days after the order has been recorded. The system-specific documentation is supplied to the customer via e-mail in the desired language (standard is English/German, for other languages, see options D58, D60, D80, D91, D94). The recipient's e-mail address must be provided with the order for this purpose. If option D02 is selected at the same time, the documents are provided in the DXF format, otherwise they are sent in PDF format. In the e-mail, the recipient is also provided with a link for downloading general preliminary documentation. D58, D60, D80, D91, D94
Note: If option D91 is selected, in the factory, an IOP containing the Chinese, English and German languages is integrated into the cabinet door of the inverter. F03, F71, F75, F77, F97 F72, F74, F76
K69 With this option, the supply voltage range is adjusted to all relevant loads in the control cabinet to 110 V AC to 120 V AC, e.g. for fans and monitoring devices. If the supply voltage is made available in the cabinet via the option K74, the voltage range is also adjusted to110 V to 120 V. K74 If there is no 230 V AC power supply in the customer installation, option K74 can be used to provide a cabinet-internal auxiliary power supply for the required auxiliary voltages of the external control circuits of the cabinet unit. The auxiliary voltages are generated by a transformer. Note: If there is no 230 V AC power supply in the customer installation, it is essential to select option K74 in order to ensure proper functioning of the options L01, L13, L19, L57, L60, L83, L84 and L86 and for the options M23, M43 and M54 for cabinet version A and for the option M21 for cabinet version A, frame size HX! Options L50 and L55 always require an external supply voltage and must not be supplied via option K74. K96 The inverter is shipped with a CU230P?2 PN Control Unit (PROFINET). For further information about the CU230P?2 PN Control Unit, refer to SINAMICS G120P built-in and wall-mounted units. K97 The inverter is shipped with a CU230P?2 DP Control Unit (PROFIBUS). For further information about the CU230P?2 DP Control Unit, refer to SINAMICS G120P built-in and wall-mounted units. K98 The inverter is shipped with a CU230P?2 HVAC Control Unit (USS, Modbus RTU, BACnet MS/TP, FLN P1). For further information about the CU230P?2 HVAC Control Unit, refer to SINAMICS G120P built-in and wall-mounted units. L00 To limit the emitted interference, the inverters are equipped as standard with a radio interference suppression filter that conforms to the limits defined in Category C3. SINAMICS G120P Cabinet units equipped with the line filter also meet the limits for use in the first environment (Category C2) as specified in EN 61800?3. 1) SINAMICS G120P Cabinet units comply with the noise immunity requirements defined in EN 61800?3 as standard for the first and second environments. In conjunction with line reactors, line filters also limit the conducted interference emitted by the Power Modules to the limit values of Category C2 defined in product standard EN 61800?3. To allow the power cable shield to be connected in conformance with EMC requirements, an additional EMC shield bus (M70 option) is installed in the cabinet. A separate order is not required in this case. 1) Applies to shielded motor cable lengths ?100 m. Note: Option L00 increases the cabinet width for frame size JX by 200 mm (7.87 in). L01 Instead of the line reactor, an innovative Line Harmonics Filter is integrated in the control cabinet; this minimizes the harmonics that occur due to the principle of operation. As a consequence, the unit fully complies with the limit values stipulated in standard IEEE 519?1992 without any exceptions (precondition: RSC ? 20). SINAMICS G120P Cabinet with integrated Line Harmonics Filter is available for power ratings up to 560 kW (751 hp) at 380 V to 415 V AC in all available degrees of protection up to IP54 (see options M21 to M54). Notice: If there is no 230 V AC power supply in the customer installation, it is essential to select option K74 in order to ensure proper functioning of option L01. Notice: 1) For the option L01, the line voltage is limited to 380 to 415 V AC ±10 %. The table below specifies the widths and weights of supplementary cabinets for the Clean Power version of SINAMICS G120P Cabinet units (Option L01).
To allow the power cable shield to be connected in conformance with EMC requirements, an EMC shield bus is installed in the cabinet at the factory. L07 dv/dt filters compact plus VPL (Voltage Peak Limiter) limit the voltage rate-of-rise dv/dt to values of <1600 V/?s and the typical voltage peaks to the following values according to the limit value curve A to IEC 60034?25: 2007:
The dv/dt filter compact plus VPL functionally consists of two components, the dv/dt reactor and the voltage limiting network (VPL), which limits voltage peaks and feeds the energy back to the DC link. Its dimensions are so compact that it can be completely integrated in the cabinet – even for high power ratings. A supplementary cabinet is not required. By using a dv/dt filter compact plus VPL, standard motors with a standard insulation and without insulated bearings can be used for inverter operation. dv/dt filters compact plus VPL are designed for the following maximum motor cable lengths:
Longer cable lengths (> 100 m (328 ft) shielded, > 150 m (492 ft) unshielded) are available on request. Notice: Operation with output frequencies < 10 Hz is permissible for max. 5 min. Note: Option L07 cannot be combined with the following options:
L08 Motor reactors reduce the voltage load on the motor windings by reducing the voltage gradients at the motor terminals that occur during inverter operation. At the same time, the capacitive charge/discharge currents that occur at the inverter output when long motor cables are used are reduced. For this reason, the maximum possible motor cable length can be increased through installation of motor reactors. Max. connectable motor cable lengths:
These values are guide values only; the actual values depend on the cable type and routing. Note: Option L08 cannot be combined with the following options:
L13 The SINAMICS G120P Cabinet inverter units are provided as standard without a line contactor. Option L13 is needed if a switching element is required for disconnecting the cabinet from the supply (required for EMERGENCY OFF). The contactor is controlled internally in the inverter. Option L13 always also covers the installation of a SITOP 24 V DC power module. Notice: If there is no 230 V AC power supply in the customer installation, it is essential to select option K74 in order to ensure proper functioning of option L13. L19 This is an outgoing, controlled feeder fused with max. 10 A for external auxiliary equipment (for example, separately driven motor fan). The voltage is tapped at the inverter input upstream of the main contactor and, therefore, has the same level as the supply voltage. The outgoing feeder can be controlled internally by the inverter or externally. Caution: If there is no 230 V AC power supply in the customer installation, it is essential to select option K74 in order to ensure proper functioning of option L19.
L26 A switch disconnector with fuses is available as main switch. L45 The EMERGENCY OFF button with protective collar is installed in the inverter cabinet door and its contacts are connected to the terminal block. The EMERGENCY OFF functions of category 0 or 1 can be activated in conjunction with options L57 and L60. Notice: By pressing the EMERGENCY OFF pushbutton, in compliance with EN 60204?1, the motor is stopped – either uncontrolled or controlled depending on the selected Category 0 or 1 – and the inverter isolated from the line supply. Auxiliary voltages, such as the cabinet-internal 230 V AC auxiliary power supply (option K74), may still be present. Certain areas within the inverter also remain live, e.g. the control or auxiliaries. If complete disconnection of all voltages is required, the EMERGENCY OFF button must be incorporated into a protective system to be implemented by the customer. For this purpose, an NC contact is provided at terminal –X120. The EMERGENCY OFF button is preconfigured at the factory only when one of the options L57 or L60 is selected simultaneously. Other circuit arrangements must be implemented in the customer installation. L50 One handheld lamp and one service socket are installed for each cabinet section. The power supply (at terminal block –X390) for the cabinet lighting and the socket must be provided externally via a 230 V AC power supply and fused with max. 10 A. The cabinet lighting is switched on manually using a switch.
L55 The anti-condensation heating is recommended at low ambient temperatures and high levels of humidity to prevent condensation. A 100 W electrical cabinet heater is installed for each cabinet section (two heaters are installed for each section for cabinet section widths from 800 mm to 1200 mm). The power supply for the anti-condensation heating (110 V to 230 V AC, at terminal block –X240) must be provided externally from a 230 V AC power supply and fused with max. 16 A.
L57 EMERGENCY OFF Category 0 for uncontrolled stopping in accordance with EN 60204?1. The function includes interrupting the power feed for the converter via the line contactor and bypassing the microprocessor controller using a safety combination according to EN 60204?1. The motor coasts down. Notice: If there is no 230 V AC power supply in the customer installation, it is essential to select option K74 in order to ensure proper functioning of option L57. Notice: Option L57 always requires the electrical separation from the line supply, i.e. option L13.
L60 EMERGENCY STOP Category 1 for controlled stopping in accordance with EN 60204?1. The function stops the drive using a fast stop along a down ramp that is parameterized by the user. The power feed to the inverter is then interrupted as described for EMERGENCY OFF Category 0. Notice: If there is no 230 V AC power supply in the customer installation, it is essential to select option K74 in order to ensure proper functioning of option L60. In order to maintain the specified stopping times, it may be necessary to use a braking unit (option L62). Notice: Option L60 always requires the electrical separation from the line supply, i.e. option L13.
L62 A braking unit must be installed for applications which require controlled braking or shutdown of the drive. This typically applies in the case of large fans which are caused to rotate by air flow. In such instances, it is important to consider operating states which could result in speeds in excess of the desired maximum speed but also the possibility of reversal of rotational direction during restart from standstill. A braking unit is also necessary when the fan must come to a standstill in a specified time, as is normally required for EMERGENCY STOP Category 1 (option L60). The braking unit comprises two components:
The braking unit functions as an autonomous unit, and does not require an external power supply. The braking energy is converted into heat in the braking resistor that must be mounted externally. A max. cable length of 100 m (328 ft) is permissible between the Braking Module and the braking resistor. This allows the braking resistor to be mounted externally so that heat losses can be dissipated outside the inverter enclosure. Characteristic curves Load diagram for Braking Module and braking resistor The following braking units are available for SINAMICS G120P Cabinet:
PDB: Rated power (continuous braking power). P20: 20 s power referred to a braking interval of 90 s. L83 Thermistor motor protection device for single-channel PTC temperature sensors (PTC resistors, type A) for alarm. The thermistor motor protection unit is supplied with power and evaluated internally in the inverter. There is galvanic isolation between the supply voltage and the temperature measuring circuit. Note: The Control Unit has a monitoring channel to monitor the motor temperature as standard. This single-channel input supports PTC, KTY84, Pt1000 (from firmware V4.7.6) and also thermoclick sensors. The warning and fault thresholds are parameterizable. The temperature values acquired are automatically used for high-precision motor control. Caution: If there is no 230 V AC power supply in the customer installation, it is essential to select option K74 in order to ensure proper functioning of option L83. L84 Thermistor motor protection device for single-channel PTC temperature sensors (PTC resistors, type A) for trip. The thermistor motor protection unit is supplied with power and evaluated internally in the inverter. There is galvanic isolation between the supply voltage and the temperature measuring circuit. Note: The Control Unit has a monitoring channel to monitor the motor temperature as standard. This single-channel input supports PTC, KTY84, Pt1000 (from firmware V4.7.6) and also thermoclick sensors. The warning and fault thresholds are parameterizable. The temperature values acquired are automatically used for high-precision motor control. Caution: If there is no 230 V AC power supply in the customer installation, it is essential to select option K74 in order to ensure proper functioning of option L84. L86 The Pt100 evaluation unit can monitor up to 6 temperature sensors. The following sensor types are supported: Pt100, Pt1000, KTY84, NTC and thermocouples. The sensors can be connected in a two- or three-wire system. The limit values can be freely programmed for each channel. In the factory setting, the measuring channels are subdivided into two groups, each with 3 channels. With motors, for example, this means that three Pt100s in the stator windings and two Pt100s in the motor bearings can be monitored. Unused channels can be suppressed via parameters. The output relays are integrated into the internal fault and shutdown sequence of the inverter. There is galvanic isolation between the supply voltage and the temperature measuring circuit. The Control Unit has a monitoring channel to monitor the motor temperature as standard. This single-channel input supports PTC, KTY84, Pt1000 (from firmware V4.7.6) and also thermoclick sensors. The warning and fault thresholds are parameterizable. The temperature values acquired are automatically used for high-precision motor control. Caution: If there is no 230 V AC power supply in the customer installation, it is essential to select option K74 in order to ensure proper functioning of option L86. M06 The additional cabinet base allows larger bending radii for cables (cable entry from below) and enables them to be routed within the cabinet base. It is delivered completely assembled with the cabinet. The mounting height of the operator panel changes accordingly. Note: The cabinet base is coated as standard in RAL 7035. M07 The cable compartment is made of strong sheet steel and allows cables to be connected more flexibly (entry from below). It also allows routing of cables within the compartment. It is delivered completely assembled with the cabinet. The mounting height of the operator panel changes accordingly. Note: The cable compartment is coated as standard in RAL 7035. M21 Cabinet version in IP20, although with additional top cover or canopy. This increases the cabinet height by 300 mm. For transport reasons, the top or drip protection covers are delivered separately and must be fitted on site. Note: The top or drip protection covers are painted in RAL 7035 as standard. Caution: If there is no 230 V AC power supply in the customer installation, it is essential to select option K74 in order to ensure a power supply to the fan for frame sizes HX and JX. M23, M43, M54 When M23, M43 or M54 is selected, the inverter is equipped with a hood. This increases the cabinet height by 400 mm. For transport reasons, the hoods are delivered separately and must be fitted by the customer. Note: The roof sections are colored RAL 7035 as standard. The molded plastic parts (e.g. ventilation grilles) have color RAL 7035 and cannot be coated. Notice: If there is no 230 V AC power supply in the customer installation for version A, it is essential to select option K74 in order to provide a power supply to the fan. Q80 to Q85 It is possible to extend the liability for defect periods beyond the standard liability for defects period. The standard liability for defects period as listed in the standard conditions for the supply of services and products is 12 months. The following extension periods are available:
The currently valid conditions for extending the period of liability for defects can be found at T58, T60, T80, T85, T91 As standard, the rating plate is in English/German. A rating plate in another language can be selected using the following order code for the option.
Y31 Resopal labels (white with black lettering) for identifying the control cabinets are available. The labels are stuck to the cabinet door. Dimensions H ? W: 40 ? 80 mm (1.57 x 3.15 in) The text must be specified in plain text when ordering. Field 1: Max. 9 characters, font size 10 mm (0.39 in) Y32 Resopal labels (white with black lettering) for identifying the control cabinets are available. The labels are stuck to the cabinet door. Dimensions H ? W: 40 ? 180 mm (1.57 x 7.09 in) The text must be specified in plain text when ordering. Field 1: Max. 9 characters, font size 10 mm (0.39 in) Y33 Resopal labels (white with black lettering) for identifying the control cabinets are available. The labels are stuck to the cabinet door. Dimensions H ? W: 40 ? 180 mm (1.57 x 7.09 in) The text must be specified in plain text when ordering. Field 1: Max. 9 characters, font size 10 mm (0.39 in) |
skener.ru Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Àðìàòóðà DENDOR Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Äàò÷èêè è èçìåðèòåëè Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Ðåãóëÿòîðû è ðåãèñòðàòîðû Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Ïíåâìàòè÷åñêîå îáîðóäîâàíèå Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Êðàíû è Êëàïàíû Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Èçìåðèòåëüíûå ïðèáîðû Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Ñèñòåìû áåñïðîâîäíîãî óïðàâëåíèÿ «óìíûé äîì» Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Áåñêîíòàêòíûå âûêëþ÷àòåëè Êîíå÷íûå âûêëþ÷àòåëè Îïòè÷åñêèå äàò÷èêè Ýíêîäåðû Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 SKW-FS - Óñòàíîâêà óìÿã÷åíèÿ Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 SKW-FK - Óñòàíîâêà îáåçæåëåçèâàíèÿ |