Mode of operation | |
Measuring principle | Analog to digital conversion |
Measuring points | 1 or 2 instruments |
Input | |
Measuring range | |
• Current | 4 ... 20 mA, 0 ... 20 mA |
• Voltage | 0 V DC ... +10 V DC, 1 ... 5 V, 0 ... 5 V |
Output signal | |
Output | - 4 ... 20 mA (optional)
- Modbus RTU
|
Relays | 2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A) external; rated 3 A at 30 V DC and 125/250 V AC resistive load; 1/14 HP (50 W) at 125/250 V AC for inductive loads (optional) |
Communications | - RS 232 with Modbus RTU
- RS 422/485 with Modbus RTU
- USB configuration and monitoring port
|
Accuracy | |
4 ... 20 mA optional output | ± 0.1 % FS ± 0.004 mA |
Process input | ± 0.05 % of span ± 1 count, square root: 10 ... 100 % FS |
Rated operating conditions | |
Ambient conditions | |
- Storage temperature range
| -40 ... +85 °C (-40 ... +185 °F) |
- Operating temperature range
| -40 ... +65 °C (-40 ... +149 єF) |
Design | |
Weight | 269 g (9.5 oz) (including options) |
Material (enclosure) | - 1/8 DIN, high impact plastic, UL94V-0, color: gray
- Optional plastic, steel and stainless steel (Type 304, EN 1.4301)
NEMA 4 enclosures
|
Degree of protection | Type 4X, NEMA 4X, IP65 (front cover); panel gasket provided |
Electrical connection | |
mA output signal | 2-core copper conductor, twisted, shielded, 0.82 ... 3.30 mmІ (18 ... 12 AWG), Belden 8 760 or equivalent is acceptable |
Electrical connection and relay connection | Copper conductor according to local requirements, rated 3A at 250 V AC |
Power supply | |
Input voltage option | 85 ... 265 V AC, 50/60 Hz; 90 ... 265 V DC, 20 W max. or jumper selectable 12/24 V DC ± 10 %, 15 W max |
Transmitter power supply | Terminals P+ & P-: 24 V DC ± 10 %, 12/24 V DC powered models selectable for 24, 10, or 5 V DC supply (internal jumper J4), 85 ... 265 V AC models rated at 200 mA max, 12/24 V DC powered models rated at 100 mA max, at 50 mA max for 5 or 10 VDC supply. |
External loop power supply | 35 V DC max. |
Output loop resistance | - 24 V DC, 10 ... 700 О© max.
- 35 V DC (external), 100 ... 1 200 О© max.
|
Displays and controls | |
Main display | 0.6 inch (15 mm) high, red LEDs |
Second display | 0.46 inch (12 mm) high, red LEDs, 6-digits: each (-99 999 ... 999 999) |
Memory | - Non-volatile
- Stores settings for minimum of 10 years if power is lost
|
Programming | - Primary: front panel
- Secondary: Meter Copy or PC with SITRANS RD Software
|
Certificates and approvals | CE, UL, CUL |
Options | |
Enclosures | Plastic, steel and stainless steel (Type 304, EN 1.4301) NEMA 4 and 4X enclosures |