Measuring principle | Analog to digital conversion |
Measuring points | |
Input | |
Measuring range | |
• Current | |
• Voltage | - 0 V DC ... +10 V DC, 1 ... 5 V,
0 ... 5 V
|
Output signal
| |
Output | |
| |
Relays | 2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A) external; rated 3 A at 30 VDC and 125/250 VAC resistive load; 1/14 HP (50 W) at 125/250 V AC for inductive loads (optional) |
Communications | |
| - RS 422/485 with Modbus RTU
|
Accuracy
| |
4 ... 20 mA optional output | ± 0.1 % FS ± 0.004 mA |
Process input | ± 0.05 % of span ± 1 count, square root: 10 ... 100 % FS |
Rated operating conditions
| |
Ambient conditions | |
Storage temperature range | -40 ... +85 °C (-40 ... +185 °F) |
Operating temperature range | 0 ... 65 °C (32 ... 149 ?F) |
Design
| |
Weight | 269 g (9.5 oz) (including options) |
Material (enclosure) | - 1/8 DIN, high impact plastic,
UL94V-0, color: gray
|
| - Optional plastic, steel and stainless
steel (Type 304, EN 1.4301) NEMA 4 enclosures
|
Degree of protection | Type 4X, NEMA 4X, IP65 (front cover); panel gasket provided |
Electrical connection
| |
mA output signal | 2-core copper conductor, twisted, shielded, 0.82 ... 3.30 mm? (18 ... 12 AWG), Belden 8 760 or equivalent is acceptable |
Electrical connection and relay connection | Copper conductor according to local requirements, rated 3A at 250 V AC |
Power supply
| |
Input voltage option | 85 ... 265 V AC, 50/60 Hz; 90 ... 265 V DC, 20 W max. or jumper selectable 12/24 V DC ± 10 %, 15 W max |
Transmitter power supply | Terminals P+ & P-: 24 V DC ± 10 %, 12/24 V DC powered models selectable for 24, 10, or 5 V DC supply (internal jumper J4), 85 ... 265 V AC models rated at 200 mA max, 12/24 V DC powered models rated at 100 mA max, at 50 mA max for 5 or 10 VDC supply. |
External loop power supply | 35 V DC max. |
Output loop resistance | - 24 V DC, 10 ... 700 ? max.
|
| - 35 V DC (external), 100 ... 1 200 ? max.
|
Displays and controls
| |
Main display | 0.6 inch (15 mm) high, red LEDs |
Second display | 0.46 inch (12 mm) high, red LEDs, 6-digits: each (-99 999 ... 999 999) |
Memory | |
| - Stores settings for minimum of
10 years if power is lost
|
Programming | |
| - Secondary: Meter Copy or PC
with SITRANS RD Software
|
Certificates and approvals
| CE, UL, CUL |
Options | |
Enclosures | Plastic, steel and stainless steel (Type 304, EN 1.4301) NEMA 4 and 4X enclosures |