Siemens
01 2018
(4872) 700-366
skenergo@mail.ru

Article number

6ES7522-1BH01-0AB0

6ES7522-1BL01-0AB0

6ES7522-1BF00-0AB0

6ES7522-5EH00-0AB0

S7-1500, DQ 16X24V DC/0.5A HF

S7-1500, DQ 32X24VDC/0.5A HF

S7-1500, DQ 8X24VDC/2A HF

S7-1500, DQ 16X24...48VUC/125VDC/0.5A ST

General information

Product type designation

DQ 16x24VDC/0.5A HF

DQ 32x24VDC/0.5A HF

DQ 8x24VDC/2A HF

DQ 16x24 ... 48 V UC/125 V DC/0.5 A ST

HW functional status

FS01

FS01

FS01

FS01

Firmware version

V1.0.0

V1.0.0

V2.1.0

V1.0.0

  • FW update possible

Yes

Yes

Yes

Product function

  • I&M data

Yes; I&M0 to I&M3

Yes; I&M0 to I&M3

Yes; I&M0 to I&M3

Yes; I&M0 to I&M3

Engineering with

  • STEP 7 TIA Portal configurable/integrated as of version

V13 SP1 / -

V13 SP1 / -

V13 SP1 / -

V13 SP1 / -

  • STEP 7 configurable/integrated as of version

V5.5 SP3 / -

V5.5 SP3 / -

  • PROFIBUS as of GSD version/GSD revision

V1.0 / V5.1

V1.0 / V5.1

V1.0 / V5.1

V1.0 / V5.1

  • PROFINET as of GSD version/GSD revision

V2.3 / -

V2.3 / -

V2.3 / -

V2.3 / -

Operating mode

  • DQ

Yes

Yes

Yes

Yes

  • DQ with energy-saving function

No

No

Yes; with an application

No

  • PWM

No

No

Yes

No

  • Oversampling

No

No

No

No

  • MSO

Yes

Yes

Yes

Yes

Supply voltage

Rated value (DC)

24V

24V

24V

permissible range, lower limit (DC)

20.4V

20.4V

20.4V

permissible range, upper limit (DC)

28.8V

28.8V

28.8V

Reverse polarity protection

Yes; through internal protection with 7 A per group

Yes; through internal protection with 7 A per group

Yes; through internal protection with 10 A per group

Input current

Current consumption, max.

30mA

60mA

40mA; 20 mA per group, no output is activated.

Output voltage

Rated value (DC)

24V

24V

24V

24V; 48 V, 125 V

Rated value (AC)

24V; 48 V (50 - 60 Hz)

Power

Power available from the backplane bus

1.1W

1.1W

0.9W

2W

Power loss

Power loss, typ.

2W

3.5W

5.6W; 6.8 W for PWM operation

3.8W

Digital outputs

Type of digital output

Transistor

Transistor

Transistor

Transistor

Number of digital outputs

16

32

8

16

Current-sinking

Yes

Current-sourcing

Yes

Yes

Yes

Yes

Short-circuit protection

Yes; Clocked electronically

Yes; Clocked electronically

Yes

  • Response threshold, typ.

1A

1A

3A

Limitation of inductive shutdown voltage to

L+ (-53 V)

L+ (-53 V)

-17 V

200 V (suppressor diode)

Controlling a digital input

Yes

Yes

Yes

Yes

Digital output functions, parameterizable

  • Freely usable digital output

Yes

  • PWM output

Yes

  • Number, max.

2

  • Cycle duration, parameterizable

Yes; 2 ... 100 ms continuous

  • ON period, min.

0%

  • ON period, max.

100%

  • Resolution of the duty cycle

0.1%

  • Minimum pulse duration

300s

Switching capacity of the outputs

  • with resistive load, max.

0.5A

0.5A

0.5A

  • on lamp load, max.

5W

5W

10W

40W; At 125 V DC, 10 W at 48 V UC, 5 W at 24 V UC

Load resistance range

  • lower limit

48Ω

48Ω

12Ω

  • upper limit

12kΩ

12kΩ

4kΩ

Output voltage

  • for signal "1", min.

L+ (-0.8 V)

L+ (-0.8 V)

L+ (-0.8 V)

L+ (-1.0 V)

Output current

  • for signal "1" rated value

0.5A

0.5A

2A

0.5A

  • for signal "1" permissible range, max.

0.5A

0.5A

2.4A; Note derating specification for PWM operation

0.6A

  • for signal "0" residual current, max.

0.5mA

0.5mA

0.5mA

Output delay with resistive load

  • "0" to "1", typ.

80s

  • "0" to "1", max.

100s

100s

100s

5ms

  • "1" to "0", typ.

300s

  • "1" to "0", max.

500s

500s

500s

5ms

Parallel switching of two outputs

  • for logic links

Yes

Yes

Yes

Yes

  • for uprating

No

No

No

No

  • for redundant control of a load

Yes

Yes

Yes

Yes

Switching frequency

  • with resistive load, max.

100Hz

100Hz

100Hz; With PWM operation: 500 Hz

25Hz

  • with inductive load, max.

0.5Hz; According to IEC 60947-5-1, DC-13

0.5Hz; According to IEC 60947-5-1, DC-13

0.5Hz; According to IEC 60947-5-1, DC-13; max. 500 Hz with PWM operation only with external circuit; see additional description in the manual

0.5Hz

  • on lamp load, max.

10Hz

10Hz

10Hz

10Hz

Total current of the outputs

  • Current per channel, max.

0.5A; see additional description in the manual

0.5A; see additional description in the manual

2A; see additional description in the manual

0.5A

  • Current per group, max.

4A; see additional description in the manual

4A; see additional description in the manual

8A; see additional description in the manual

0.5A

  • Current per module, max.

8A; see additional description in the manual

16A; see additional description in the manual

16A; see additional description in the manual

8A

Cable length

  • shielded, max.

1000m

1000m

1000m

1000m

  • unshielded, max.

600m

600m

600m

600m

Isochronous mode

Isochronous operation (application synchronized up to terminal)

Yes

Yes

No

No

Execution and activation time (TCO), min.

70s

70s

Bus cycle time (TDP), min.

250s

250s

Interrupts/diagnostics/status information

Diagnostics function

Yes

Yes

Yes

No

Substitute values connectable

Yes

Yes

Yes

Yes

Alarms

  • Diagnostic alarm

Yes

Yes

Yes

No

Diagnostic messages

  • Monitoring the supply voltage

Yes

Yes

Yes

No

  • Wire-break

Yes

Yes

No

No

  • Short-circuit

Yes

Yes

Yes

No

  • Group error

Yes

Yes

Yes

Diagnostics indication LED

  • RUN LED

Yes; Green LED

Yes; Green LED

Yes; Green LED

Yes; Green LED

  • ERROR LED

Yes; Red LED

Yes; Red LED

Yes; Red LED

Yes; Red LED

  • Monitoring of the supply voltage (PWR-LED)

Yes; Green LED

Yes; Green LED

Yes; Green LED

No

  • Channel status display

Yes; Green LED

Yes; Green LED

Yes; Green LED

Yes; Green LED

  • for channel diagnostics

Yes; Red LED

Yes; Red LED

Yes; Red LED

No

  • for module diagnostics

Yes; Red LED

Yes; Red LED

Yes; Red LED

Yes; Red LED

Potential separation

Potential separation channels

  • between the channels

No

No

No

Yes

  • between the channels, in groups of

8

8

4

1

  • between the channels and backplane bus

Yes

Yes

Yes

Yes

Permissible potential difference

between different circuits

125 V DC/48 V AC

Isolation

Isolation tested with

707 V DC (type test)

707 V DC (type test)

707 V DC (type test)

2 000 V DC

Ambient conditions

Ambient temperature during operation

  • horizontal installation, min.

0C

0C

  • horizontal installation, max.

60C

60C

  • vertical installation, min.

0C

0C

  • vertical installation, max.

60C

40C

Decentralized operation

Prioritized startup

Yes

Yes

Yes

Yes

Dimensions

Width

35mm

35mm

35mm

35mm

Height

147mm

147mm

147mm

147mm

Depth

129mm

129mm

129mm

129mm

Weights

Weight, approx.

230g

280g

240g

230g


Article number

6ES7522-5HF00-0AB0

6ES7522-5HH00-0AB0

6ES7522-5FF00-0AB0

6ES7522-5FH00-0AB0

S7-1500, DQ 8X230VAC/5A ST (RELAY)

S7-1500, DQ 16X230VAC/2A ST (RELAY)

S7-1500, DQ 8X230VAC/2A ST (TRIAC)

S7-1500, DQ 16X230VAC/1A ST (TRIAC)

General information

Product type designation

DQ 8x230 V AC/5 A ST (relay)

DQ 16x 230 V AC/2 A ST (relay)

DQ 8x230 V AC/2A ST (triac)

DQ 16x230VAC/1A ST (Triac)

HW functional status

FS01

FS01

FS01

FS01

Firmware version

V2.0.0

V1.0.0

V2.0.0

V1.0.0

  • FW update possible

Yes

Yes

Yes

Yes

Product function

  • I&M data

Yes; I&M0 to I&M3

Yes; I&M0 to I&M3

Yes; I&M0 to I&M3

Yes; I&M0 to I&M3

Engineering with

  • STEP 7 TIA Portal configurable/integrated as of version

V12 / V12

V13 SP1 / -

V12 / V12

V13 SP1 / -

  • STEP 7 configurable/integrated as of version

V5.5 SP3 / -

V5.5 SP3 / -

V5.5 SP3 / -

V5.5 SP3 / -

  • PROFIBUS as of GSD version/GSD revision

V1.0 / V5.1

V1.0 / V5.1

V1.0 / V5.1

V1.0 / V5.1

  • PROFINET as of GSD version/GSD revision

V2.3 / -

V2.3 / -

V2.3 / -

V2.3 / -

Operating mode

  • DQ

Yes

Yes

Yes

Yes

  • DQ with energy-saving function

No

No

No

No

  • PWM

No

No

No

No

  • Oversampling

No

No

No

No

  • MSO

Yes

Yes

Yes

Yes

Supply voltage

Rated value (DC)

24V

24V

permissible range, lower limit (DC)

20.4V

20.4V

permissible range, upper limit (DC)

28.8V

28.8V

Reverse polarity protection

Yes

Yes

Input current

Current consumption, max.

80mA

150mA

Output voltage

Rated value (AC)

230V; 24 V DC to 120 V DC / 24 V AC to 230 V AC

230V; 24 V DC to 120 V DC / 24 V AC to 230 V AC

230V; 120/230 V AC, 50/60 Hz

230V; 120/230 V AC, 50/60 Hz

Power

Power available from the backplane bus

0.8W

0.8W

0.9W

1.2W

Power loss

Power loss, typ.

5W

5W

10.8W

11.1W

Digital outputs

Type of digital output

Relays

Relays

Triac

Triac

Number of digital outputs

8

16

8

16

Current-sinking

Yes

Yes

Yes

Current-sourcing

Yes

Yes

Yes

Yes

Short-circuit protection

No

No

No

No

Controlling a digital input

possible

Yes

Switching capacity of the outputs

  • with resistive load, max.

2A

1A

  • on lamp load, max.

1500W; 10 000 operating cycles

50 W (230 V AC), 5 W (24 V DC)

50W

50W

  • Low energy/fluorescent lamps with electronic control gear

10x 58 W (25 000 operating cycles)

  • Fluorescent tubes, conventionally compensated

1x 58 W (25 000 operating cycles)

  • Fluorescent tubes, uncompensated

10x 58 W (25 000 operating cycles)

Output voltage

  • for signal "1", min.

L1 (-1.5 V) at maximum output current; L1 (-8.5 V) at minimum output current

L1 (-1.5 V) at maximum output current; L1 (-8.5 V) at minimum output current

Output current

  • for signal "1" rated value

5A

2A

2A

1A

  • for signal "1" permissible range, min.

5mA; 10 V

10mA; 10 V

10mA

10mA

  • for signal "1" permissible range, max.

8A; thermal continuous current

2A; thermal continuous current

15A; max. 1 AC cycle

15A; max. 1 AC cycle

  • for signal "0" residual current, max.

0A

0A

2mA

2mA

Output delay with resistive load

  • "0" to "1", max.

1 AC cycle

1 AC cycle

  • "1" to "0", max.

1 AC cycle

1 AC cycle

Parallel switching of two outputs

  • for logic links

Yes

Yes

No

No

  • for uprating

No

No

No

No

  • for redundant control of a load

Yes

Yes

Yes

Yes

Switching frequency

  • with resistive load, max.

2Hz

1Hz

10Hz

10Hz

  • with inductive load, max.

0.5Hz

0.5Hz

0.5Hz

0.5Hz

  • on lamp load, max.

2Hz

1Hz

1Hz

1Hz

Total current of the outputs

  • Current per channel, max.

8A; see additional description in the manual

2A; see additional description in the manual

2A; see additional description in the manual

1A; see additional description in the manual

  • Current per group, max.

8A; see additional description in the manual

4A; see additional description in the manual

2A; see additional description in the manual

2A; see additional description in the manual

  • Current per module, max.

64A; see additional description in the manual

32A; see additional description in the manual

10A; see additional description in the manual

10A; see additional description in the manual

Relay outputs

  • Number of relay outputs

8

16

  • Rated supply voltage of relay coil L+ (DC)

24V

24V

  • Current consumption of relays (coil current of all relays), typ.

80mA

150mA

  • external protection for relay outputs

With miniature circuit breaker with characteristic B for: cos φ 1.0: 600 A cos φ 0.5 ... 0.7: 900 A with 8 A Diazed fuse: 1000 A

Miniature circuit breaker B10 / B16

  • Contact connection (internal)

No

No

  • Size of motor starters according to NEMA, max.

5

5

  • Number of operating cycles, max.

4000000; see additional description in the manual

see additional description in the manual

  • Relay approved acc. to UL 508

Yes; 250 V AC/5 A g.p.; 120 V AC TV-4 tungsten; A300, R300

No

Switching capacity of contacts

  • with inductive load, max.

see additional description in the manual

2A; see additional description in the manual

  • with resistive load, max.

see additional description in the manual

2A; see additional description in the manual

Triac outputs

  • Size of motor starters according to NEMA, max.

5

4

Cable length

  • shielded, max.

1000m

1000m

1000m

1000m

  • unshielded, max.

600m

600m

600m

600m

Isochronous mode

Isochronous operation (application synchronized up to terminal)

No

No

No

No

Interrupts/diagnostics/status information

Diagnostics function

Yes

Yes

No

No

Substitute values connectable

Yes

Yes

Yes

Yes

Alarms

  • Diagnostic alarm

Yes

Yes

No

No

Diagnostic messages

  • Monitoring the supply voltage

Yes

Yes

No

No

  • Wire-break

No

No

No

No

  • Short-circuit

No

No

No

No

Diagnostics indication LED

  • RUN LED

Yes; Green LED

Yes; Green LED

Yes; Green LED

Yes; Green LED

  • ERROR LED

Yes; Red LED

Yes; Red LED

Yes; Red LED

Yes; Red LED

  • Monitoring of the supply voltage (PWR-LED)

Yes; Green LED

Yes; Green LED

No

No

  • Channel status display

Yes; Green LED

Yes; Green LED

Yes; Green LED

Yes; Green LED

  • for channel diagnostics

No

No

No

No

  • for module diagnostics

Yes; Red LED

Yes; Red LED

Yes; Red LED

Yes; Red LED

Potential separation

Potential separation channels

  • between the channels

Yes; Switching of different phases permitted

No

Yes

No

  • between the channels, in groups of

1

2

1

2

  • between the channels and backplane bus

Yes

Yes

Yes

Yes

  • Between the channels and load voltage L+

Yes

Yes

  • Between the channels and load voltage L1

Yes

Permissible potential difference

between different circuits

250 V AC between the channels and the supply voltage L+; 250 V AC between the channels and the backplane bus; 500 V AC between the channels

250 V AC between the channels and the supply voltage L+; 250 V AC between the channels and the backplane bus; 500 V AC between the channels

250 V AC between the channels and the backplane bus; 500 V AC between the channels

250 V AC between the channels and the backplane bus; 500 V AC between the channels

Isolation

Isolation tested with

Between channels: 3 100 V DC; between channels backplane bus: 3 100 V DC; between L+ and backplane bus: 707 V DC (type test)

Between channels: 3 100 V DC; between channels backplane bus: 3 100 V DC; between L+ and backplane bus: 707 V DC (type test)

3 100 V DC

3 100 V DC

Ambient conditions

Ambient temperature during operation

  • horizontal installation, min.

0C

0C

0C

0C

  • horizontal installation, max.

60C

60C

60C

60C

  • vertical installation, min.

0C

0C

0C

0C

  • vertical installation, max.

40C

40C

40C

60C

Decentralized operation

Prioritized startup

Yes

Yes

Yes

Yes

Dimensions

Width

35mm

35mm

35mm

35mm

Height

147mm

147mm

147mm

147mm

Depth

129mm

129mm

129mm

129mm

Weights

Weight, approx.

350g

350g

290g

310g


Article number

6ES7522-1BH10-0AA0

6ES7522-1BL10-0AA0

S7-1500, DQ 16X24VDC/0.5A BA

S7-1500, DQ 32X24VDC/0.5A BA

General information

Product type designation

DQ 16x24VDC/0.5A BA

DQ 32x24VDC/0.5A BA

HW functional status

FS01

FS01

Firmware version

V1.0.0

V1.0.0

  • FW update possible

Yes

Yes

Product function

  • I&M data

Yes; I&M0 to I&M3

Yes; I&M0 to I&M3

Engineering with

  • STEP 7 TIA Portal configurable/integrated as of version

V13 / V13

V13 / V13

  • STEP 7 configurable/integrated as of version

V5.5 SP3 / -

V5.5 SP3 / -

  • PROFIBUS as of GSD version/GSD revision

V1.0 / V5.1

V1.0 / V5.1

  • PROFINET as of GSD version/GSD revision

V2.3 / -

V2.3 / -

Operating mode

  • DQ

Yes

Yes

  • DQ with energy-saving function

No

No

  • PWM

No

No

  • Oversampling

No

No

  • MSO

Yes

Yes

Supply voltage

Rated value (DC)

24V

24V

permissible range, lower limit (DC)

20.4V

20.4V

permissible range, upper limit (DC)

28.8V

28.8V

Reverse polarity protection

Yes; through internal protection with 7 A per group

Yes; through internal protection with 7 A per group

Input current

Current consumption, max.

30mA

60mA

Output voltage

Rated value (DC)

24V

24V

Power

Power available from the backplane bus

1.15W

1.15W

Power loss

Power loss, typ.

2.2W

3.8W

Digital outputs

Type of digital output

Transistor

Transistor

Number of digital outputs

16

32

Current-sourcing

Yes

Yes

Short-circuit protection

Yes

Yes

  • Response threshold, typ.

1A

1A

Limitation of inductive shutdown voltage to

L+ (-53 V)

L+ (-53 V)

Controlling a digital input

Yes

Yes

Switching capacity of the outputs

  • with resistive load, max.

0.5A

0.5A

  • on lamp load, max.

5W

5W

Load resistance range

  • lower limit

48Ω

48Ω

  • upper limit

12kΩ

12kΩ

Output voltage

  • for signal "1", min.

L+ (-0.8 V)

L+ (-0.8 V)

Output current

  • for signal "1" rated value

0.5A

0.5A

  • for signal "1" permissible range, max.

0.5A

0.5A

  • for signal "0" residual current, max.

0.5mA

0.5mA

Output delay with resistive load

  • "0" to "1", max.

100s

100s

  • "1" to "0", max.

500s

500s

Parallel switching of two outputs

  • for logic links

Yes

Yes

  • for uprating

No

No

  • for redundant control of a load

Yes

Yes

Switching frequency

  • with resistive load, max.

100Hz

100Hz

  • with inductive load, max.

0.5Hz; According to IEC 60947-5-1, DC-13

0.5Hz; According to IEC 60947-5-1, DC-13

  • on lamp load, max.

10Hz

10Hz

Total current of the outputs

  • Current per channel, max.

0.5A; see additional description in the manual

0.5A; see additional description in the manual

  • Current per group, max.

4A; see additional description in the manual

4A; see additional description in the manual

  • Current per module, max.

8A; see additional description in the manual

16A; see additional description in the manual

Cable length

  • shielded, max.

1000m

1000m

  • unshielded, max.

600m

600m

Isochronous mode

Isochronous operation (application synchronized up to terminal)

No

No

Interrupts/diagnostics/status information

Diagnostics function

No

No

Substitute values connectable

No

No

Alarms

  • Diagnostic alarm

No

No

Diagnostic messages

  • Monitoring the supply voltage

No

No

  • Wire-break

No

No

  • Short-circuit

No

No

  • Group error

No

No

Diagnostics indication LED

  • RUN LED

Yes; Green LED

Yes; Green LED

  • ERROR LED

Yes; Red LED

Yes; Red LED

  • Monitoring of the supply voltage (PWR-LED)

Yes; Green LED

Yes; Green LED

  • Channel status display

Yes; Green LED

Yes; Green LED

  • for channel diagnostics

No

No

  • for module diagnostics

No

No

Potential separation

Potential separation channels

  • between the channels

No

No

  • between the channels, in groups of

8

8

  • between the channels and backplane bus

Yes

Yes

Isolation

Isolation tested with

707 V DC (type test)

707 V DC (type test)

Decentralized operation

Prioritized startup

Yes

Yes

Dimensions

Width

25mm

25mm

Height

147mm

147mm

Depth

129mm

129mm

Weights

Weight, approx.

230g

280g

Other

Note:

Supplied incl. 40-pole push-in front connectors

Supplied incl. 40-pole push-in front connectors



















  © " " 2007-2022