Siemens
ÑÐÅÄÑÒÂÀ ÏÐÎÌÛØËÅÍÍÎÉ ÀÂÒÎÌÀÒÈÇÀÖÈÈ
îôèöèàëüíûé ïàðòíåð Ñèìåíñ
Êàòàëîã ÑÀ01 2017
àðõèâíûé
(4872) 700-366
skenergo@mail.ru

SM 522 digital output modules

Article number

6ES7522-1BH01-0AB0

6ES7522-1BL01-0AB0

6ES7522-1BF00-0AB0

6ES7522-5EH00-0AB0

S7-1500, DQ 16X24V DC/0.5A HF

S7-1500, DQ 32X24VDC/0.5A HF

S7-1500, DQ 8X24VDC/2A HF

S7-1500, DQ 16X24...48VUC/125VDC/0.5A ST

General information

 

 

 

 

Product type designation

DQ 16x24VDC/0.5A HF

DQ 32x24VDC/0.5A HF

DQ 8x24VDC/2A HF

DQ 16x24 ... 48VUC/125VDC/0.5A ST

Product function

 

 

 

 

  • ? I&M data

Yes; I&M0 to I&M3

Yes; I&M0 to I&M3

Yes; I&M0 to I&M3

Yes; I&M0 to I&M3

Engineering with

 

 

 

 

  • ? STEP 7 TIA Portal configurable/integrated as of version

V13 SP1 / -

V13 SP1 / -

V13 SP1 / -

V13 SP1 / -

  • ? STEP 7 configurable/integrated as of version

V5.5 SP3 / -

V5.5 SP3 / -

  • ? PROFIBUS as of GSD version/GSD revision

V1.0 / V5.1

V1.0 / V5.1

V1.0 / V5.1

V1.0 / V5.1

  • ? PROFINET as of GSD version/GSD revision

V2.3 / -

V2.3 / -

V2.3 / -

V2.3 / -

Operating mode

 

 

 

 

  • ? DQ

Yes

Yes

Yes

Yes

  • ? DQ with energy-saving function

No

No

Yes; with an application

No

  • ? PWM

No

No

Yes

No

  • ? Oversampling

No

No

No

No

  • ? MSO

Yes

Yes

Yes

Yes

Supply voltage

 

 

 

 

Type of supply voltage

DC

DC

DC

Rated value (DC)

24 V

24 V

24 V

Reverse polarity protection

Yes; through internal protection with 7 A per group

Yes; through internal protection with 7 A per group

Yes; through internal protection with 10 A per group

Digital outputs

 

 

 

 

Type of digital output

Transistor

Transistor

Transistor

Transistor

Number of digital outputs

16

32

8

16

Current-sinking

Yes

Current-sourcing

Yes

Yes

Yes

Yes

Digital outputs, parameterizable

Yes

Yes

Yes

Yes

Short-circuit protection

Yes; Clocked electronically

Yes; Clocked electronically

Yes

Limitation of inductive shutdown voltage to

L+ (-53 V)

L+ (-53 V)

-17 V

200 V (suppressor diode)

Controlling a digital input

Yes

Yes

Yes

Yes

Digital output functions, parameterizable

 

 

 

 

  • ? Freely usable digital output

Yes

  • ? PWM output

Yes

  • Number, max.

2

  • Cycle duration, parameterizable

Yes; 2 ... 100 ms continuous

Switching capacity of the outputs

 

 

 

 

  • ? with resistive load, max.

0.5 A

0.5 A

0.5 A

  • ? on lamp load, max.

5 W

5 W

10 W

40 W; At 125 V DC, 10 W at 48 V UC, 5 W at 24 V UC

Load resistance range

 

 

 

 

  • ? lower limit

48 ?

48 ?

12 ?

  • ? upper limit

12 k?

12 k?

4 k?

Output voltage

 

 

 

 

  • ? Type of output voltage

DC

DC

DC

UC

  • ? for signal "1", min.

L+ (-0.8 V)

L+ (-0.8 V)

L+ (-0.8 V)

L+ (-1.0 V)

Output current

 

 

 

 

  • ? for signal "1" rated value

0.5 A

0.5 A

2 A

0.5 A

  • ? for signal "0" residual current, max.

0.5 mA

0.5 mA

0.5 mA

Output delay with resistive load

 

 

 

 

  • ? "0" to "1", typ.

80 µs

  • ? "0" to "1", max.

100 µs

100 µs

100 µs

5 ms

  • ? "1" to "0", typ.

300 µs

  • ? "1" to "0", max.

500 µs

500 µs

500 µs

5 ms

Parallel switching of two outputs

 

 

 

 

  • ? for logic links

Yes

Yes

Yes

Yes

  • ? for uprating

No

No

No

No

  • ? for redundant control of a load

Yes

Yes

Yes

Yes

Switching frequency

 

 

 

 

  • ? with resistive load, max.

100 Hz

100 Hz

100 Hz; With PWM operation: 500 Hz

25 Hz

  • ? with inductive load, max.

0.5 Hz; According to IEC 60947-5-1, DC-13

0.5 Hz; According to IEC 60947-5-1, DC-13

0.5 Hz; According to IEC 60947-5-1, DC-13; max. 500 Hz with PWM operation only with external circuit; see additional description in the manual

0.5 Hz

  • ? on lamp load, max.

10 Hz

10 Hz

10 Hz

10 Hz

Total current of the outputs

 

 

 

 

  • ? Current per channel, max.

0.5 A; see additional description in the manual

0.5 A; see additional description in the manual

2 A; see additional description in the manual

0.5 A

  • ? Current per group, max.

4 A; see additional description in the manual

4 A; see additional description in the manual

8 A; see additional description in the manual

0.5 A

  • ? Current per module, max.

8 A; see additional description in the manual

16 A; see additional description in the manual

16 A; see additional description in the manual

8 A

Cable length

 

 

 

 

  • ? shielded, max.

1 000 m

1 000 m

1 000 m

1 000 m

  • ? unshielded, max.

600 m

600 m

600 m

600 m

Isochronous mode

 

 

 

 

Isochronous operation (application synchronized up to terminal)

Yes

Yes

No

No

Execution and activation time (TCO), min.

70 µs

70 µs

Bus cycle time (TDP), min.

250 µs

250 µs

Interrupts/diagnostics/status information

 

 

 

 

Diagnostics function

Yes

Yes

Yes

No

Substitute values connectable

Yes

Yes

Yes

Yes

Alarms

 

 

 

 

  • ? Diagnostic alarm

Yes

Yes

Yes

No

Diagnostic messages

 

 

 

 

  • ? Monitoring the supply voltage

Yes

Yes

Yes

No

  • ? Wire-break

Yes

Yes

No

No

  • ? Short-circuit

Yes

Yes

Yes

No

  • ? Group error

Yes

Yes

Yes

Diagnostics indication LED

 

 

 

 

  • ? RUN LED

Yes; Green LED

Yes; Green LED

Yes; Green LED

Yes; Green LED

  • ? ERROR LED

Yes; Red LED

Yes; Red LED

Yes; Red LED

Yes; Red LED

  • ? Monitoring of the supply voltage (PWR-LED)

Yes; Green LED

Yes; Green LED

Yes; Green LED

No

  • ? Channel status display

Yes; Green LED

Yes; Green LED

Yes; Green LED

Yes; Green LED

  • ? for channel diagnostics

Yes; Red LED

Yes; Red LED

Yes; Red LED

No

  • ? for module diagnostics

Yes; Red LED

Yes; Red LED

Yes; Red LED

Yes; Red LED

Potential separation

 

 

 

 

Potential separation channels

 

 

 

 

  • ? between the channels and backplane bus

Yes

Yes

Yes

Yes

Isolation

 

 

 

 

Isolation tested with

707 V DC (type test)

707 V DC (type test)

707 V DC (type test)

2 000 V DC

Standards, approvals, certificates

 

 

 

 

Suitable for safety functions

No

No

No

No

Ambient conditions

 

 

 

 

Ambient temperature during operation

 

 

 

 

  • ? horizontal installation, min.

0 °C

0 °C

  • ? horizontal installation, max.

60 °C

60 °C

  • ? vertical installation, min.

0 °C

0 °C

  • ? vertical installation, max.

60 °C

40 °C

Decentralized operation

 

 

 

 

Prioritized startup

Yes

Yes

Yes

Yes

Dimensions

 

 

 

 

Width

35 mm

35 mm

35 mm

35 mm

Height

147 mm

147 mm

147 mm

147 mm

Depth

129 mm

129 mm

129 mm

129 mm

Weights

 

 

 

 

Weight, approx.

230 g

280 g

240 g

230 g


Article number

6ES7522-5HF00-0AB0

6ES7522-5HH00-0AB0

6ES7522-5FF00-0AB0

6ES7522-5FH00-0AB0

S7-1500, DQ 8X230VAC/5A ST (RELAY)

S7-1500, DQ 16X230VAC/2A ST (RELAY)

S7-1500, DQ 8X230VAC/2A ST (TRIAC)

S7-1500, DQ 16X230VAC/1A ST (TRIAC)

General information

 

 

 

 

Product type designation

DQ 8x230 V AC/5 A ST (relay)

DQ 16x230VAC/2A ST (relay)

DQ 8x230 V AC/2A ST (triac)

DQ 16x230VAC/1A ST (Triac)

Product function

 

 

 

 

  • ? I&M data

Yes; I&M0 to I&M3

Yes; I&M0 to I&M3

Yes; I&M0 to I&M3

Yes; I&M0 to I&M3

Engineering with

 

 

 

 

  • ? STEP 7 TIA Portal configurable/integrated as of version

V12 / V12

V13 SP1 / -

V12 / V12

V13 SP1 / -

  • ? STEP 7 configurable/integrated as of version

V5.5 SP3 / -

V5.5 SP3 / -

V5.5 SP3 / -

V5.5 SP3 / -

  • ? PROFIBUS as of GSD version/GSD revision

V1.0 / V5.1

V1.0 / V5.1

V1.0 / V5.1

V1.0 / V5.1

  • ? PROFINET as of GSD version/GSD revision

V2.3 / -

V2.3 / -

V2.3 / -

V2.3 / -

Operating mode

 

 

 

 

  • ? DQ

Yes

Yes

Yes

Yes

  • ? DQ with energy-saving function

No

No

No

No

  • ? PWM

No

No

No

No

  • ? Oversampling

No

No

No

No

  • ? MSO

Yes

Yes

Yes

Yes

Supply voltage

 

 

 

 

Type of supply voltage

DC

DC

Rated value (DC)

24 V

24 V

Reverse polarity protection

Yes

Yes

Digital outputs

 

 

 

 

Type of digital output

Relays

Relays

Triac

Triac

Number of digital outputs

8

16

8

16

Current-sinking

Yes

Yes

Yes

Current-sourcing

Yes

Yes

Yes

Yes

Digital outputs, parameterizable

Yes

Yes

Yes

Yes

Short-circuit protection

No

No

No

No

Controlling a digital input

possible

Yes

Switching capacity of the outputs

 

 

 

 

  • ? with resistive load, max.

2 A

1 A

  • ? on lamp load, max.

1 500 W; 10 000 operating cycles

50 W (230 V AC), 5 W (24 V DC)

50 W

50 W

  • ? Low energy/fluorescent lamps with electronic control gear

10x 58 W (25 000 operating cycles)

  • ? Fluorescent tubes, conventionally compensated

1x 58 W (25 000 operating cycles)

  • ? Fluorescent tubes, uncompensated

10x 58 W (25 000 operating cycles)

Output voltage

 

 

 

 

  • ? Type of output voltage

AC

AC

  • ? for signal "1", min.

L1 (-1.5 V) at maximum output current; L1 (-8.5 V) at minimum output current

L1 (-1.5 V) at maximum output current; L1 (-8.5 V) at minimum output current

Output current

 

 

 

 

  • ? for signal "1" rated value

5 A

2 A

2 A

1 A

  • ? for signal "0" residual current, max.

0 A

0 A

2 mA

2 mA

Output delay with resistive load

 

 

 

 

  • ? "0" to "1", max.

1 AC cycle

1 AC cycle

  • ? "1" to "0", max.

1 AC cycle

1 AC cycle

Parallel switching of two outputs

 

 

 

 

  • ? for logic links

Yes

Yes

No

No

  • ? for uprating

No

No

No

No

  • ? for redundant control of a load

Yes

Yes

Yes

Yes

Switching frequency

 

 

 

 

  • ? with resistive load, max.

2 Hz

1 Hz

10 Hz

10 Hz

  • ? with inductive load, max.

0.5 Hz

0.5 Hz

0.5 Hz

0.5 Hz

  • ? on lamp load, max.

2 Hz

1 Hz

1 Hz

1 Hz

Total current of the outputs

 

 

 

 

  • ? Current per channel, max.

8 A; see additional description in the manual

2 A; see additional description in the manual

2 A; see additional description in the manual

1 A; see additional description in the manual

  • ? Current per group, max.

8 A; see additional description in the manual

2 A; see additional description in the manual

2 A; see additional description in the manual

2 A; see additional description in the manual

  • ? Current per module, max.

64 A; see additional description in the manual

32 A; see additional description in the manual

10 A; see additional description in the manual

10 A; see additional description in the manual

Relay outputs

 

 

 

 

  • ? Number of relay outputs

8

16

  • ? Rated supply voltage of relay coil L+ (DC)

24 V

24 V

  • ? Current consumption of relays (coil current of all relays), typ.

80 mA

150 mA

  • ? external protection for relay outputs

With miniature circuit breaker with characteristic B for: cos ? 1.0: 600 A cos ? 0.5 ... 0.7: 900 A with 8 A Diazed fuse: 1000 A

Miniature circuit breaker B10 / B16

  • ? Contact connection (internal)

No

No

  • ? Size of motor starters according to NEMA, max.

5

5

  • ? Number of operating cycles, max.

4 000 000; see additional description in the manual

see additional description in the manual

  • ? Relay approved acc. to UL 508

Yes; 250 V AC/5 A g.p.; 120 V AC TV-4 tungsten; A300, R300

No

Switching capacity of contacts

 

 

 

 

  • with inductive load, max.

see additional description in the manual

2 A; see additional description in the manual

  • with resistive load, max.

see additional description in the manual

2 A; see additional description in the manual

Triac outputs

 

 

 

 

  • ? Size of motor starters according to NEMA, max.

5

4

Cable length

 

 

 

 

  • ? shielded, max.

1 000 m

1 000 m

1 000 m

1 000 m

  • ? unshielded, max.

600 m

600 m

600 m

600 m

Isochronous mode

 

 

 

 

Isochronous operation (application synchronized up to terminal)

No

No

No

No

Interrupts/diagnostics/status information

 

 

 

 

Diagnostics function

Yes

Yes

No

No

Substitute values connectable

Yes

Yes

Yes

Yes

Alarms

 

 

 

 

  • ? Diagnostic alarm

Yes

Yes

No

No

Diagnostic messages

 

 

 

 

  • ? Monitoring the supply voltage

Yes

Yes

No

No

  • ? Wire-break

No

No

No

No

  • ? Short-circuit

No

No

No

No

Diagnostics indication LED

 

 

 

 

  • ? RUN LED

Yes; Green LED

Yes; Green LED

Yes; Green LED

Yes; Green LED

  • ? ERROR LED

Yes; Red LED

Yes; Red LED

Yes; Red LED

Yes; Red LED

  • ? Monitoring of the supply voltage (PWR-LED)

Yes; Green LED

Yes; Green LED

No

No

  • ? Channel status display

Yes; Green LED

Yes; Green LED

Yes; Green LED

Yes; Green LED

  • ? for channel diagnostics

No

No

No

No

  • ? for module diagnostics

Yes; Red LED

Yes; Red LED

Yes; Red LED

Yes; Red LED

Potential separation

 

 

 

 

Potential separation channels

 

 

 

 

  • ? between the channels and backplane bus

Yes

Yes

Yes

Yes

Isolation

 

 

 

 

Isolation tested with

Between channels: 3 100 V DC; between channels backplane bus: 3 100 V DC; between L+ and backplane bus: 707 V DC (type test)

Between channels: 3 100 V DC; between channels backplane bus: 3 100 V DC; between L+ and backplane bus: 707 V DC (type test)

3 100 V DC

3 100 V DC

Standards, approvals, certificates

 

 

 

 

Suitable for safety functions

No

No

No

No

Ambient conditions

 

 

 

 

Ambient temperature during operation

 

 

 

 

  • ? horizontal installation, min.

0 °C

0 °C

0 °C

0 °C

  • ? horizontal installation, max.

60 °C

60 °C

60 °C

60 °C

  • ? vertical installation, min.

0 °C

0 °C

0 °C

0 °C

  • ? vertical installation, max.

40 °C

40 °C

40 °C

60 °C

Decentralized operation

 

 

 

 

Prioritized startup

Yes

Yes

Yes

Yes

Dimensions

 

 

 

 

Width

35 mm

35 mm

35 mm

35 mm

Height

147 mm

147 mm

147 mm

147 mm

Depth

129 mm

129 mm

129 mm

129 mm

Weights

 

 

 

 

Weight, approx.

350 g

350 g

290 g

310 g


Article number

6ES7522-1BH10-0AA0

6ES7522-1BL10-0AA0

S7-1500, DQ 16X24VDC/0.5A BA

S7-1500, DQ 32X24VDC/0.5A BA

General information

 

 

Product type designation

DQ 16x24VDC/0.5A BA

DQ 32x24VDC/0.5A BA

Product function

 

 

  • ? I&M data

Yes; I&M0 to I&M3

Yes; I&M0 to I&M3

Engineering with

 

 

  • ? STEP 7 TIA Portal configurable/integrated as of version

V13 / V13

V13 / V13

  • ? STEP 7 configurable/integrated as of version

V5.5 SP3 / -

V5.5 SP3 / -

  • ? PROFIBUS as of GSD version/GSD revision

V1.0 / V5.1

V1.0 / V5.1

  • ? PROFINET as of GSD version/GSD revision

V2.3 / -

V2.3 / -

Operating mode

 

 

  • ? DQ

Yes

Yes

  • ? DQ with energy-saving function

No

No

  • ? PWM

No

No

  • ? Oversampling

No

No

  • ? MSO

Yes

Yes

Supply voltage

 

 

Type of supply voltage

DC

DC

Rated value (DC)

24 V

24 V

Reverse polarity protection

Yes; through internal protection with 7 A per group

Yes; through internal protection with 7 A per group

Digital outputs

 

 

Type of digital output

Transistor

Transistor

Number of digital outputs

16

32

Current-sourcing

Yes

Yes

Digital outputs, parameterizable

No

No

Short-circuit protection

Yes

Yes

Limitation of inductive shutdown voltage to

L+ (-53 V)

L+ (-53 V)

Controlling a digital input

Yes

Yes

Switching capacity of the outputs

 

 

  • ? with resistive load, max.

0.5 A

0.5 A

  • ? on lamp load, max.

5 W

5 W

Load resistance range

 

 

  • ? lower limit

48 ?

48 ?

  • ? upper limit

12 k?

12 k?

Output voltage

 

 

  • ? Type of output voltage

DC

DC

  • ? for signal "1", min.

L+ (-0.8 V)

L+ (-0.8 V)

Output current

 

 

  • ? for signal "1" rated value

0.5 A

0.5 A

  • ? for signal "0" residual current, max.

0.5 mA

0.5 mA

Output delay with resistive load

 

 

  • ? "0" to "1", max.

100 µs

100 µs

  • ? "1" to "0", max.

500 µs

500 µs

Parallel switching of two outputs

 

 

  • ? for logic links

Yes

Yes

  • ? for uprating

No

No

  • ? for redundant control of a load

Yes

Yes

Switching frequency

 

 

  • ? with resistive load, max.

100 Hz

100 Hz

  • ? with inductive load, max.

0.5 Hz; According to IEC 60947-5-1, DC-13

0.5 Hz; According to IEC 60947-5-1, DC-13

  • ? on lamp load, max.

10 Hz

10 Hz

Total current of the outputs

 

 

  • ? Current per channel, max.

0.5 A; see additional description in the manual

0.5 A; see additional description in the manual

  • ? Current per group, max.

4 A; see additional description in the manual

4 A; see additional description in the manual

  • ? Current per module, max.

8 A; see additional description in the manual

16 A; see additional description in the manual

Cable length

 

 

  • ? shielded, max.

1 000 m

1 000 m

  • ? unshielded, max.

600 m

600 m

Isochronous mode

 

 

Isochronous operation (application synchronized up to terminal)

No

No

Interrupts/diagnostics/status information

 

 

Diagnostics function

No

No

Substitute values connectable

No

No

Alarms

 

 

  • ? Diagnostic alarm

No

No

Diagnostic messages

 

 

  • ? Monitoring the supply voltage

No

No

  • ? Wire-break

No

No

  • ? Short-circuit

No

No

  • ? Group error

No

No

Diagnostics indication LED

 

 

  • ? RUN LED

Yes; Green LED

Yes; Green LED

  • ? ERROR LED

Yes; Red LED

Yes; Red LED

  • ? Monitoring of the supply voltage (PWR-LED)

Yes; Green LED

Yes; Green LED

  • ? Channel status display

Yes; Green LED

Yes; Green LED

  • ? for channel diagnostics

No

No

  • ? for module diagnostics

No

No

Potential separation

 

 

Potential separation channels

 

 

  • ? between the channels and backplane bus

Yes

Yes

Isolation

 

 

Isolation tested with

707 V DC (type test)

707 V DC (type test)

Standards, approvals, certificates

 

 

Suitable for safety functions

No

No

Decentralized operation

 

 

Prioritized startup

Yes

Yes

Dimensions

 

 

Width

25 mm

25 mm

Height

147 mm

147 mm

Depth

129 mm

129 mm

Weights

 

 

Weight, approx.

230 g

280 g

Other

 

 

Note:

Supplied incl. 40-pole push-in front connectors

Supplied incl. 40-pole push-in front connectors


















skener.ru

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Àðìàòóðà DENDOR

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Äàò÷èêè è èçìåðèòåëè

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ðåãóëÿòîðû è ðåãèñòðàòîðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ïíåâìàòè÷åñêîå îáîðóäîâàíèå

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Êðàíû è Êëàïàíû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Èçìåðèòåëüíûå ïðèáîðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ñèñòåìû áåñïðîâîäíîãî óïðàâëåíèÿ «óìíûé äîì»

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Áåñêîíòàêòíûå âûêëþ÷àòåëè Êîíå÷íûå âûêëþ÷àòåëè Îïòè÷åñêèå äàò÷èêè Ýíêîäåðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Óñòàíîâêà óìÿã÷åíèÿ

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Óñòàíîâêà îáåçæåëåçèâàíèÿ

  © ÎÎÎ "ÑÊ ÝÍÅÐÃÎ" 2007-2022
  (4872) 700-366  skenergo@mail.ru
ßíäåêñ.Ìåòðèêà