Siemens
СРЕДСТВА ПРОМЫШЛЕННОЙ АВТОМАТИЗАЦИИ
официальный партнер Сименс
Каталог СА01 2018
(4872) 700-366
skenergo@mail.ru

Article number

6AG1134-6HD00-7BA1

6AG1134-6GD00-7BA1

6AG1134-6TD00-2CA1

SIPLUS ET 200SP AI 4xU/I 2-wire ST

SIPLUS ET 200SP AI 4xI 2-/4-wire ST

SIPLUS ET 200SP AI 4XI 2-WIRE 4...20MA H

General information

 

 

 

Product type designation

AI 4xU/I 2-wire ST

AI 4xI 2-/4-wire ST

AI 4xI 2-wire HART

Firmware version

  • в—Џ FW update possible

Yes

usable BaseUnits

BU type A0, A1

Color code for module-specific color identification plate

CC03

Product function

 

 

 

  • в—Џ I&M data

Yes

Yes; I&M0 to I&M3

  • в—Џ Measuring range scalable

No

Engineering with

 

 

 

  • в—Џ STEP 7 TIA Portal configurable/integrated as of version

V11 SP2 with HSP 0024 / -

  • в—Џ STEP 7 configurable/integrated as of version

V5.5 SP2 with GSD file / -

  • в—Џ PROFIBUS as of GSD version/GSD revision

GSD Revision 5

  • в—Џ PROFINET as of GSD version/GSD revision

GSDML V2.3

Operating mode

 

 

 

  • в—Џ Oversampling

No

  • в—Џ MSI

No

CiR – Configuration in RUN

 

 

 

Reparameterization possible in RUN

Yes

Yes

Calibration possible in RUN

No

Supply voltage

 

 

 

Rated value (DC)

24 V

24 V

24 V

permissible range, lower limit (DC)

19.2 V

19.2 V

19.2 V

permissible range, upper limit (DC)

28.8 V

28.8 V

28.8 V

Reverse polarity protection

Yes

Yes

Input current

 

 

 

Current consumption, max.

37 mA; without sensor supply

25 mA; without sensor supply

24 V encoder supply

 

 

 

  • в—Џ 24 V

Yes

Yes

  • в—Џ Short-circuit protection

Yes

Yes

  • в—Џ Output current, max.

20 mA; max. 50 mA per channel for a duration < 10 s

20 mA; max. 50 mA per channel for a duration < 10 s

Power loss

 

 

 

Power loss, typ.

0.85 W; without sensor supply

0.85 W; Without encoder supply voltage

0.65 W; without sensor supply

Address area

 

 

 

Address space per module

 

 

 

  • в—Џ Address space per module, max.

8 byte

32 byte

8 byte; + 1 byte for QI information

  • в—Џ Address space per module with HART, max.

28 byte; + 1 byte for QI information

Analog inputs

 

 

 

Number of analog inputs

4; > 60 °C max. 1x ±20 mA or 4x ±10 V permissible

4; > 60 °C max. 1x ±20 mA permissible

4; Differential inputs

permissible input voltage for voltage input (destruction limit), max.

30 V

permissible input current for current input (destruction limit), max.

50 mA

50 mA

50 mA

Cycle time (all channels), min.

Sum of the basic conversion times and additional processing times (depending on the parameterization of the active channels)

Input ranges (rated values), voltages

 

 

 

  • в—Џ 0 to +10 V

Yes; 15 bit

  • в—Џ Input resistance (0 to 10 V)

120 kΩ

  • в—Џ 1 V to 5 V

Yes; 15 bit

  • в—Џ Input resistance (1 V to 5 V)

120 kΩ

  • в—Џ -10 V to +10 V

Yes; 16 bit incl. sign

  • в—Џ Input resistance (-10 V to +10 V)

120 kΩ

  • в—Џ -5 V to +5 V

Yes; 16 bit incl. sign

  • в—Џ Input resistance (-5 V to +5 V)

120 kΩ

Input ranges (rated values), currents

 

 

 

  • в—Џ 0 to 20 mA

Yes; 15 bit

Yes

No

  • в—Џ Input resistance (0 to 20 mA)

100 в„¦; + approx. 0.7 V diode forward voltage

100 в„¦; + approx. 0.7 V diode forward voltage in 2-wire operation

  • в—Џ -20 mA to +20 mA

Yes

No

  • в—Џ Input resistance (-20 mA to +20 mA)

100 в„¦

  • в—Џ 4 mA to 20 mA

Yes; 15 bit

Yes

Yes; 15 bit + sign

  • в—Џ Input resistance (4 mA to 20 mA)

100 в„¦; + approx. 0.7 V diode forward voltage

100 в„¦; + approx. 0.7 V diode forward voltage in 2-wire operation

280 в„¦; + approx. 0.35 V diode forward voltage

Cable length

 

 

 

  • в—Џ shielded, max.

200 m

800 m

Analog value generation for the inputs

 

 

 

Measurement principle

integrating (Sigma-Delta)

integrating (Sigma-Delta)

Integration and conversion time/resolution per channel

 

 

 

  • в—Џ Resolution with overrange (bit including sign), max.

16 bit

16 bit

  • в—Џ Integration time, parameterizable

Yes

Yes; channel by channel

  • в—Џ Interference voltage suppression for interference frequency f1 in Hz

16.6 / 50 / 60 Hz

10 / 50 / 60 Hz

  • в—Џ Conversion time (per channel)

180 / 60 / 50 ms

Smoothing of measured values

 

 

 

  • в—Џ Number of smoothing levels

4; None; 4/8/16 times

  • в—Џ parameterizable

Yes

Yes

  • в—Џ Step: None

Yes

  • в—Џ Step: low

Yes

  • в—Џ Step: Medium

Yes

  • в—Џ Step: High

Yes

Encoder

 

 

 

Connection of signal encoders

 

 

 

  • в—Џ for voltage measurement

Yes

No

  • в—Џ for current measurement as 2-wire transducer

Yes

Yes

  • — Burden of 2-wire transmitter, max.

650 в„¦

Errors/accuracies

 

 

 

Linearity error (relative to input range), (+/-)

0.01 %

0.01 %

0.01 %

Temperature error (relative to input range), (+/-)

0.005 %/K

0.005 %/K

0.005 %/K

Crosstalk between the inputs, min.

-50 dB

50 dB; Applies to up to ±5 V overvoltage in other channels

60 dB

Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)

0.05 %

0.05 %

0.05 %

Operational error limit in overall temperature range

 

 

 

  • в—Џ Voltage, relative to input range, (+/-)

0.5 %

  • в—Џ Current, relative to input range, (+/-)

0.5 %

0.7 %

1 %

Basic error limit (operational limit at 25 °C)

 

 

 

  • в—Џ Voltage, relative to input range, (+/-)

0.3 %

  • в—Џ Current, relative to input range, (+/-)

0.3 %

0.3 %

0.3 %

Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency

 

 

 

  • в—Џ Series mode interference (peak value of interference < rated value of input range), min.

70 dB

70 dB

60 dB

  • в—Џ Common mode voltage, max.

10 V

10 V

  • в—Џ Common mode interference, min.

90 dB

90 dB

Isochronous mode

 

 

 

Isochronous operation (application synchronized up to terminal)

No

Interrupts/diagnostics/status information

 

 

 

Diagnostics function

Yes

Yes

Yes

Alarms

 

 

 

  • в—Џ Diagnostic alarm

Yes

Yes

  • в—Џ Limit value alarm

Yes

Diagnostic messages

 

 

 

  • в—Џ Monitoring the supply voltage

Yes

Yes

Yes

  • в—Џ Wire-break

Yes; at 4 to 20 mA

Yes; at 4 to 20 mA

Yes; channel by channel

  • в—Џ Short-circuit

Yes; with 1 to 5 V or 2-wire mode: Short-circuit of the encoder supply to ground or of an input to the encoder supply

Yes; 2-wire mode: Short-circuit of the encoder supply to ground or of an input to the encoder supply

Yes; Channel-by-channel, short-circuit of the encoder supply to ground or of an input to the encoder supply

  • в—Џ Group error

Yes

Yes

  • в—Џ Overflow/underflow

Yes

Yes; channel by channel

Diagnostics indication LED

 

 

 

  • в—Џ Monitoring of the supply voltage (PWR-LED)

Yes; Green LED

Yes; green PWR LED

  • в—Џ Channel status display

Yes; Green LED

Yes; Green LED

  • в—Џ for channel diagnostics

Yes; Red LED

  • в—Џ for module diagnostics

Yes; Green/red LED

Yes; green/red DIAG LED

Potential separation

 

 

 

Potential separation channels

 

 

 

  • в—Џ between the channels

Yes; channel group-specific between 2-wire current input group and voltage input group

No

  • в—Џ between the channels and backplane bus

Yes

Yes

  • в—Џ between the channels and the power supply of the electronics

Yes; only for voltage inputs

No

Permissible potential difference

 

 

 

between different circuits

75 V DC/60 V AC

between the inputs (UCM)

10 V DC

10 V DC

Isolation

 

 

 

Isolation tested with

707 V DC

707 V DC (type test)

Ambient conditions

 

 

 

Ambient temperature during operation

 

 

 

  • в—Џ horizontal installation, min.

-40 °C; = Tmin; Startup @ -25 °C

-40 °C; = Tmin

-40 °C; = Tmin; Startup @ -25 °C

  • в—Џ horizontal installation, max.

70 °C; = Tmax; > 60 °C max. 1x ±20 mA or 4x ±10 V permissible

70 °C; = Tmax; > 60 °C max. 1x ±20 mA permissible

60 °C

  • в—Џ vertical installation, min.

-40 °C; = Tmin; Startup @ -25 °C

-40 °C; = Tmin

-40 °C; = Tmin; Startup @ -25 °C

  • в—Џ vertical installation, max.

50 °C; = Tmax

50 °C; = Tmax

50 °C

Altitude during operation relating to sea level

 

 

 

  • в—Џ Ambient air temperature-barometric pressure-altitude

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Relative humidity

 

 

 

  • в—Џ With condensation, tested in accordance with IEC 60068-2-38, max.

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

Use in stationary industrial systems

 

 

 

  • — to biologically active substances according to EN 60721-3-3

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

  • — to chemically active substances according to EN 60721-3-3

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

  • — to mechanically active substances according to EN 60721-3-3

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Dimensions

 

 

 

Width

15 mm

15 mm

15 mm

Height

73 mm

73 mm

73 mm

Depth

58 mm

58 mm

58 mm

Weights

 

 

 

Weight, approx.

31 g

31 g


Article number

6AG1134-6HB00-2CA1

6AG1134-6HB00-2DA1

6AG1134-6JF00-2CA1

6AG1134-6JD00-2CA1

SIPLUS ET 200SP AI 2 X U/I 2-, 4-WIRE HF

SIPLUS ET 200SP AI 2 X U/I 2-, 4-WIRE HS

SIPLUS ET 200SP AI 8XRTD/TC 2-WIRE HF

SIPLUS ET 200SP AI 4xRTD/TC HF

General information

 

 

 

 

Product type designation

AI 2xU/I 2-/4-wire HF

AI 2xU/I 2-/4-wire HS

AI 8xRTD/TC 2-wire HF

AI 4xRTD/TC 2-/3-/4-wire HF

Firmware version

V1.0

V2.0

  • в—Џ FW update possible

Yes

Yes

Yes

usable BaseUnits

BU type A0, A1

BU type A0, A1

BU type A0, A1

Color code for module-specific color identification plate

CC03

CC00

CC00

Product function

 

 

 

 

  • в—Џ I&M data

Yes; I&M0 to I&M3

Yes; I&M0 to I&M3

Yes; I&M0 to I&M3

Yes

  • в—Џ Measuring range scalable

No

No

Engineering with

 

 

 

 

  • в—Џ PROFIBUS as of GSD version/GSD revision

GSD Revision 5

GSD Revision 5

GSD Revision 5

  • в—Џ PROFINET as of GSD version/GSD revision

GSDML V2.3

GSDML V2.3

GSDML V2.3

Operating mode

 

 

 

 

  • в—Џ Oversampling

No

Yes; 2 channels per module

No

  • в—Џ MSI

No

No

No

CiR – Configuration in RUN

 

 

 

 

Reparameterization possible in RUN

Yes

Yes

Yes

Calibration possible in RUN

Yes

No

Yes

Supply voltage

 

 

 

 

Rated value (DC)

24 V

24 V

24 V

24 V

permissible range, lower limit (DC)

19.2 V

19.2 V

19.2 V

19.2 V

permissible range, upper limit (DC)

28.8 V

28.8 V

28.8 V

28.8 V

Reverse polarity protection

Yes

Yes

Yes

Yes

Input current

 

 

 

 

Current consumption (rated value)

39 mA; without sensor supply

39 mA; without sensor supply

Current consumption, max.

35 mA

35 mA

24 V encoder supply

 

 

 

 

  • в—Џ 24 V

Yes

Yes

  • в—Џ Short-circuit protection

Yes

Yes

  • в—Џ Output current, max.

20 mA; max. 50 mA per channel for a duration < 10 s (two-wire)

20 mA; max. 50 mA per channel for a duration < 10 s

Additional 24 V encoder supply

 

 

 

 

  • в—Џ Output current, max.

100 mA; max. 150 mA for a duration of < 10 s (four-wire)

Power loss

 

 

 

 

Power loss, typ.

0.95 W; without sensor supply

0.95 W; without sensor supply

0.75 W

0.75 W

Address area

 

 

 

 

Address space per module

 

 

 

 

  • в—Џ Address space per module, max.

4 byte; + 1 byte for QI information

4 byte; + 1 byte for QI information (32 bytes in the oversampling operating mode)

16 byte; + 1 byte for QI information

8 byte

Analog inputs

 

 

 

 

Number of analog inputs

2; Differential inputs

2; Differential inputs

8

4

permissible input voltage for voltage input (destruction limit), max.

30 V

30 V

30 V

30 V

permissible input current for current input (destruction limit), max.

50 mA

50 mA

Constant measurement current for resistance-type transmitter, typ.

2 mA

2 mA

Cycle time (all channels), min.

125 µs

Sum of the basic conversion times and additional processing times (depending on the parameterization of the active channels)

Sum of the basic conversion times and additional processing times (depending on the parameterization of the active channels); for line compensation in case of a three-wire connection, an additional cycle is necessary

Technical unit for temperature measurement adjustable

Yes; °C/°F/K

Yes; °C/°F/K

Analog input with oversampling

Yes

  • в—Џ Values per cycle, max.

16

  • в—Џ Resolution, min.

50 µs

Input ranges (rated values), voltages

 

 

 

 

  • в—Џ 0 to +10 V

Yes; 15 bit

Yes; 15 bit

  • в—Џ Input resistance (0 to 10 V)

75 kΩ

75 kΩ

  • в—Џ 1 V to 5 V

Yes; 15 bit

Yes; 13 bit

  • в—Џ Input resistance (1 V to 5 V)

75 kΩ

75 kΩ

  • в—Џ -1 V to +1 V

Yes; 16 bit incl. sign

Yes; 16 bit incl. sign

  • в—Џ Input resistance (-1 V to +1 V)

1 MΩ

10 MΩ

  • в—Џ -10 V to +10 V

Yes; 16 bit incl. sign

Yes; 16 bit incl. sign

  • в—Џ Input resistance (-10 V to +10 V)

75 kΩ

75 kΩ

  • в—Џ -250 mV to +250 mV

Yes; 16 bit incl. sign

Yes; 16 bit incl. sign

  • в—Џ Input resistance (-250 mV to +250 mV)

1 MΩ

10 MΩ

  • в—Џ -5 V to +5 V

Yes; 16 bit incl. sign

Yes; 15 bit incl. sign

  • в—Џ Input resistance (-5 V to +5 V)

75 kΩ

75 kΩ

  • в—Џ -50 mV to +50 mV

Yes; 16 bit incl. sign

Yes; 16 bit incl. sign

  • в—Џ Input resistance (-50 mV to +50 mV)

1 MΩ

10 MΩ

  • в—Џ -80 mV to +80 mV

Yes; 16 bit incl. sign

Yes; 16 bit incl. sign

  • в—Џ Input resistance (-80 mV to +80 mV)

1 MΩ

10 MΩ

Input ranges (rated values), currents

 

 

 

 

  • в—Џ 0 to 20 mA

Yes; 15 bit

Yes; 15 bit

  • в—Џ Input resistance (0 to 20 mA)

130 в„¦

130 в„¦

  • в—Џ -20 mA to +20 mA

Yes; 16 bit incl. sign

Yes; 16 bit incl. sign

  • в—Џ Input resistance (-20 mA to +20 mA)

130 в„¦

130 в„¦

  • в—Џ 4 mA to 20 mA

Yes; 15 bit

Yes; 14 bit

  • в—Џ Input resistance (4 mA to 20 mA)

130 в„¦

130 в„¦

Input ranges (rated values), thermocouples

 

 

 

 

  • в—Џ Type B

Yes; 16 bit incl. sign

Yes; 16 bit incl. sign

  • в—Џ Input resistance (Type B)

1 MΩ

1 MΩ

  • в—Џ Type C

Yes; 16 bit incl. sign

Yes; 16 bit incl. sign

  • в—Џ Input resistance (Type C)

1 MΩ

1 MΩ

  • в—Џ Type E

Yes; 16 bit incl. sign

Yes; 16 bit incl. sign

  • в—Џ Input resistance (Type E)

1 MΩ

1 MΩ

  • в—Џ Type J

Yes; 16 bit incl. sign

Yes; 16 bit incl. sign

  • в—Џ Input resistance (type J)

1 MΩ

1 MΩ

  • в—Џ Type K

Yes; 16 bit incl. sign

Yes; 16 bit incl. sign

  • в—Џ Input resistance (Type K)

1 MΩ

1 MΩ

  • в—Џ Type L

Yes; 16 bit incl. sign

Yes; 16 bit incl. sign

  • в—Џ Input resistance (Type L)

1 MΩ

1 MΩ

  • в—Џ Type N

Yes; 16 bit incl. sign

Yes; 16 bit incl. sign

  • в—Џ Input resistance (Type N)

1 MΩ

1 MΩ

  • в—Џ Type R

Yes; 16 bit incl. sign

Yes; 16 bit incl. sign

  • в—Џ Input resistance (Type R)

1 MΩ

1 MΩ

  • в—Џ Type S

Yes; 16 bit incl. sign

Yes; 16 bit incl. sign

  • в—Џ Input resistance (Type S)

1 MΩ

1 MΩ

  • в—Џ Type T

Yes; 16 bit incl. sign

Yes; 16 bit incl. sign

  • в—Џ Input resistance (Type T)

1 MΩ

1 MΩ

  • в—Џ Type U

Yes; 16 bit incl. sign

Yes; 16 bit incl. sign

  • в—Џ Input resistance (Type U)

1 MΩ

1 MΩ

  • в—Џ Type TXK/TXK(L) to GOST

Yes; 16 bit incl. sign

Yes; 16 bit incl. sign

  • в—Џ Input resistance (Type TXK/TXK(L) to GOST)

1 MΩ

1 MΩ

Input ranges (rated values), resistance thermometer

 

 

 

 

  • в—Џ Cu 10

Yes; 16 bit incl. sign

  • в—Џ Input resistance (Cu 10)

1 MΩ

  • в—Џ Ni 100

Yes; 16 bit incl. sign

Yes; 16 bit incl. sign

  • в—Џ Input resistance (Ni 100)

1 MΩ

1 MΩ

  • в—Џ Ni 1000

Yes; 16 bit incl. sign

Yes; 16 bit incl. sign

  • в—Џ Input resistance (Ni 1000)

1 MΩ

1 MΩ

  • в—Џ LG-Ni 1000

Yes; 16 bit incl. sign

Yes; 16 bit incl. sign

  • в—Џ Input resistance (LG-Ni 1000)

1 MΩ

1 MΩ

  • в—Џ Ni 120

Yes; 16 bit incl. sign

Yes; 16 bit incl. sign

  • в—Џ Input resistance (Ni 120)

1 MΩ

1 MΩ

  • в—Џ Ni 200

Yes; 16 bit incl. sign

Yes; 16 bit incl. sign

  • в—Џ Input resistance (Ni 200)

1 MΩ

1 MΩ

  • в—Џ Ni 500

Yes; 16 bit incl. sign

Yes; 16 bit incl. sign

  • в—Џ Input resistance (Ni 500)

1 MΩ

1 MΩ

  • в—Џ Pt 100

Yes; 16 bit incl. sign

Yes; 16 bit incl. sign

  • в—Џ Input resistance (Pt 100)

1 MΩ

1 MΩ

  • в—Џ Pt 1000

Yes; 16 bit incl. sign

Yes; 16 bit incl. sign

  • в—Џ Input resistance (Pt 1000)

1 MΩ

1 MΩ

  • в—Џ Pt 200

Yes; 16 bit incl. sign

Yes; 16 bit incl. sign

  • в—Џ Input resistance (Pt 200)

1 MΩ

1 MΩ

  • в—Џ Pt 500

Yes; 16 bit incl. sign

Yes; 16 bit incl. sign

  • в—Џ Input resistance (Pt 500)

1 MΩ

1 MΩ

Input ranges (rated values), resistors

 

 

 

 

  • в—Џ 0 to 150 ohms

Yes; 15 bit

Yes; 15 bit

  • в—Џ Input resistance (0 to 150 ohms)

1 MΩ

1 MΩ

  • в—Џ 0 to 300 ohms

Yes; 15 bit

Yes; 15 bit

  • в—Џ Input resistance (0 to 300 ohms)

1 MΩ

1 MΩ

  • в—Џ 0 to 600 ohms

Yes; 15 bit

Yes; 15 bit

  • в—Џ Input resistance (0 to 600 ohms)

1 MΩ

1 MΩ

  • в—Џ 0 to 3000 ohms

Yes; 15 bit

Yes; 15 bit

  • в—Џ Input resistance (0 to 3000 ohms)

1 MΩ

1 MΩ

  • в—Џ 0 to 6000 ohms

Yes; 15 bit

Yes; 15 bit

  • в—Џ Input resistance (0 to 6000 ohms)

1 MΩ

1 MΩ

  • в—Џ PTC

Yes; 15 bit

Yes; 15 bit

  • в—Џ Input resistance (PTC)

1 MΩ

1 MΩ

Thermocouple (TC)

 

 

 

 

Temperature compensation

 

 

 

 

  • — parameterizable

Yes

Yes

  • — Reference channel of the module

Yes

Yes

  • — internal comparison point

Yes; with BaseUnit type A1

Yes

  • — Reference channel of the group

Yes

Yes

  • — Number of reference channel groups

4; Group 0 to 3

  • — fixed reference temperature

Yes

Yes

Cable length

 

 

 

 

  • в—Џ shielded, max.

1 000 m; 200 m for voltage measurement

1 000 m; 200 m for voltage measurement

200 m; 50 m with thermocouples

200 m; 50 m with thermocouples

Analog value generation for the inputs

 

 

 

 

Measurement principle

Sigma Delta

Actual value encryption (successive approximation)

integrating (Sigma-Delta)

integrating (Sigma-Delta)

Integration and conversion time/resolution per channel

 

 

 

 

  • в—Џ Resolution with overrange (bit including sign), max.

16 bit

16 bit

16 bit

16 bit

  • в—Џ Integration time, parameterizable

Yes

Yes

Yes

  • в—Џ Basic conversion time, including integration time (ms)

  • — additional processing time for wire-break check

2 ms; In the ranges resistance thermometers, resistors and thermocouples

2 ms; In the ranges resistance thermometers, resistors and thermocouples

  • — additional power line wire-break check

2 ms; for 3/4 wire transducer (resistance thermometer and resistor)

  • в—Џ Interference voltage suppression for interference frequency f1 in Hz

16.6 / 50 / 60 / 300 / 600 / 1 200 / 2 400 / 4 800

No

16.6 / 50 / 60 Hz

16.6 / 50 / 60 Hz

  • в—Џ Conversion time (per channel)

10 µs

180 / 60 / 50 ms

180 / 60 / 50 ms

  • в—Џ Basic execution time of the module (all channels released)

1 ms

Smoothing of measured values

 

 

 

 

  • в—Џ Number of smoothing levels

6; none; 2-/4-/8-/16-/32-fold

7; none; 2-/4-/8-/16-/32-/64-fold

4; None; 4/8/16 times

  • в—Џ parameterizable

Yes

Yes

Yes

Yes

  • в—Џ Step: None

Yes

  • в—Џ Step: low

Yes

  • в—Џ Step: Medium

Yes

  • в—Џ Step: High

Yes

Encoder

 

 

 

 

Connection of signal encoders

 

 

 

 

  • в—Џ for voltage measurement

Yes

Yes

Yes

Yes

  • в—Џ for current measurement as 2-wire transducer

Yes

Yes

  • — Burden of 2-wire transmitter, max.

650 в„¦

650 в„¦

  • в—Џ for current measurement as 4-wire transducer

Yes

Yes

  • в—Џ for resistance measurement with two-wire connection

Yes

Yes

  • в—Џ for resistance measurement with three-wire connection

No

Yes

  • в—Џ for resistance measurement with four-wire connection

No

Yes

Errors/accuracies

 

 

 

 

Linearity error (relative to input range), (+/-)

0.02 %

0.03 %

0.01 %; ±0.1 % for resistance thermometers and resistance

0.01 %; ±0.1 % for resistance thermometers and resistance

Temperature error (relative to input range), (+/-)

0.005 %/K

0.01 %/K

0.0009 %/K; ±0.005 % / K at thermocouple

0.0009 %/K; ±0.005 % / K at thermocouple

Crosstalk between the inputs, min.

-50 dB

-50 dB

-50 dB

-50 dB

Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)

0.01 %

0.1 %

0.05 %

0.05 %

Operational error limit in overall temperature range

 

 

 

 

  • в—Џ Voltage, relative to input range, (+/-)

0.2 %

0.5 %

0.2 %

0.1 %

  • в—Џ Current, relative to input range, (+/-)

0.2 %

0.5 %

  • в—Џ Resistance, relative to input range, (+/-)

0.2 %

0.1 %

Basic error limit (operational limit at 25 °C)

 

 

 

 

  • в—Џ Voltage, relative to input range, (+/-)

0.05 %; 0.1 % at SFU 4.8 kHz

0.2 %

0.05 %

0.05 %

  • в—Џ Current, relative to input range, (+/-)

0.05 %; 0.1 % at SFU 4.8 kHz

0.2 %

  • в—Џ Resistance, relative to input range, (+/-)

0.05 %

0.05 %

Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency

 

 

 

 

  • в—Џ Series mode interference (peak value of interference < rated value of input range), min.

70 dB

70 dB

  • в—Џ Common mode voltage, max.

35 V

35 V

10 V

10 V

  • в—Џ Common mode interference, min.

90 dB

90 dB

90 dB

90 dB

Isochronous mode

 

 

 

 

Isochronous operation (application synchronized up to terminal)

Yes

Yes

No

Filtering and processing time (TCI), min.

800 µs

80 µs

Bus cycle time (TDP), min.

1 ms

125 µs

Jitter, max.

5 µs

Interrupts/diagnostics/status information

 

 

 

 

Diagnostics function

Yes

Yes

Yes

Alarms

 

 

 

 

  • в—Џ Diagnostic alarm

Yes

Yes

Yes

Yes

  • в—Џ Limit value alarm

Yes; two upper and two lower limit values in each case

Yes; two upper and two lower limit values in each case

Yes; two upper and two lower limit values in each case

Yes; two upper and two lower limit values in each case

Diagnostic messages

 

 

 

 

  • в—Џ Monitoring the supply voltage

Yes

Yes

Yes

  • в—Џ Wire-break

Yes; Measuring range 4 to 20 mA only

Yes; channel-by-channel, at 4 to 20 mA only

Yes; channel by channel

Yes

  • в—Џ Short-circuit

Yes; For 1 to 5 V or for current measuring ranges short-circuit in encoder supply

Yes; channel-by-channel, at 1 to 5 V or for current measuring ranges short-circuit in encoder supply

  • в—Џ Group error

Yes

Yes

Yes

  • в—Џ Overflow/underflow

Yes

Yes

Yes; channel by channel

Yes

Diagnostics indication LED

 

 

 

 

  • в—Џ Monitoring of the supply voltage (PWR-LED)

Yes; green PWR LED

Yes; green PWR LED

Yes; green PWR LED

Yes; Green LED

  • в—Џ Channel status display

Yes; Green LED

Yes; Green LED

Yes; Green LED

Yes; Green LED

  • в—Џ for channel diagnostics

Yes; Red LED

Yes; Red LED

Yes; Red LED

Yes; Red LED

  • в—Џ for module diagnostics

Yes; green/red DIAG LED

Yes; green/red DIAG LED

Yes; green/red DIAG LED

Yes; Green/red LED

Potential separation

 

 

 

 

Potential separation channels

 

 

 

 

  • в—Џ between the channels

Yes

Yes

No

No

  • в—Џ between the channels and backplane bus

Yes

Yes

Yes

Yes

  • в—Џ between the channels and the power supply of the electronics

Yes

Yes

Yes

Yes

Permissible potential difference

 

 

 

 

between different circuits

75 V DC/60 V AC (base isolation)

75 V DC/60 V AC (base isolation)

75 V DC/60 V AC (base isolation)

75 V DC/60 V AC

between the inputs (UCM)

75 V DC/60 V AC

75 V DC/60 V AC

10 V DC

10 V DC

Isolation

 

 

 

 

Isolation tested with

707 V DC (type test)

707 V DC (type test)

707 V DC (type test)

707 V DC

Ambient conditions

 

 

 

 

Ambient temperature during operation

 

 

 

 

  • в—Џ horizontal installation, min.

-40 °C; = Tmin; Startup @ -25 °C

-40 °C; = Tmin; Startup @ -25 °C

-40 °C; = Tmin; Startup @ -25 °C

-40 °C; = Tmin; Startup @ -25 °C

  • в—Џ horizontal installation, max.

60 °C; = Tmax

60 °C; = Tmax

60 °C

60 °C; = Tmax

  • в—Џ vertical installation, min.

-40 °C; = Tmin; Startup @ -25 °C

-40 °C; = Tmin; Startup @ -25 °C

  • в—Џ vertical installation, max.

50 °C

50 °C; = Tmax

Altitude during operation relating to sea level

 

 

 

 

  • в—Џ Ambient air temperature-barometric pressure-altitude

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Relative humidity

 

 

 

 

  • в—Џ With condensation, tested in accordance with IEC 60068-2-38, max.

100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation

100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

Use in stationary industrial systems

 

 

 

 

  • — to biologically active substances according to EN 60721-3-3

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

  • — to chemically active substances according to EN 60721-3-3

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

  • — to mechanically active substances according to EN 60721-3-3

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Dimensions

 

 

 

 

Width

15 mm

15 mm

15 mm

15 mm

Height

73 mm

73 mm

73 mm

Depth

58 mm

58 mm

58 mm

Weights

 

 

 

 

Weight, approx.

32 g

32 g

32 g

30 g


Article number

6AG1134-6PA20-7BD0

SIPLUS ET 200SP AI EMETER 480VAC ST

General information

 

Product type designation

ET 200SP, AI Energy Meter 480 V AC ST, PU 1

usable BaseUnits

BU type D0, BU20-P12+A0+0B

Product function

 

  • в—Џ Voltage measurement

Yes

  • в—Џ Voltage measurement with voltage transformers

Yes

  • в—Џ Current measurement

Yes

  • в—Џ Phase current measurement without current transformers

No

  • в—Џ Phase current measurement with current transformers

Yes

  • в—Џ Energy measurement

Yes

  • в—Џ Frequency measurement

Yes

  • в—Џ Power measurement

Yes

  • в—Џ Active power measurement

Yes

  • в—Џ Reactive power measurement

Yes

  • в—Џ I&M data

Yes; I&M0 to I&M3

  • в—Џ Isochronous mode

No

Operating mode

 

  • в—Џ cyclic measurement

Yes

  • в—Џ acyclic measurement

Yes

  • в—Џ Acyclic measured value access

Yes

  • в—Џ Fixed measured value sets

Yes

  • в—Џ Freely definable measured value sets

Yes

Configuration control

 

via dataset

Yes

CiR – Configuration in RUN

 

Reparameterization possible in RUN

Yes

Calibration possible in RUN

Yes

Installation type/mounting

 

Mounting position

Any

Supply voltage

 

Design of the power supply

Supply via voltage measurement channel L1

Type of supply voltage

AC 100 - 277 V

permissible range, lower limit (AC)

90 V

permissible range, upper limit (AC)

293 V

Line frequency

 

  • в—Џ permissible range, lower limit

47 Hz

  • в—Џ permissible range, upper limit

63 Hz

Power loss

 

Power loss, typ.

0.6 W

Address area

 

Address space per module

 

  • в—Џ Address space per module, max.

268 byte; 256 byte input / 12 byte output

Hardware configuration

 

Automatic encoding

  • в—Џ Mechanical coding element

Yes

Time of day

 

Operating hours counter

 

  • в—Џ present

Yes

Analog inputs

 

Cycle time (all channels), typ.

50 ms; Time for consistent update of all measured and calculated values (cyclic und acyclic data)

Interrupts/diagnostics/status information

 

Alarms

 

  • в—Џ Diagnostic alarm

Yes

  • в—Џ Limit value alarm

Yes

  • в—Џ Hardware interrupt

Yes; Monitoring of up to 16 freely selectable process values (exceeding or undershooting of value)

Diagnostics indication LED

 

  • в—Џ Monitoring of the supply voltage (PWR-LED)

Yes

  • в—Џ Channel status display

Yes; Green LED

  • в—Џ for channel diagnostics

Yes; red Fn LED

  • в—Џ for module diagnostics

Yes; green/red DIAG LED

Integrated Functions

 

Measuring functions

 

  • в—Џ Measuring procedure for voltage measurement

TRMS

  • в—Џ Measuring procedure for current measurement

TRMS

  • в—Џ Type of measured value acquisition

seamless

  • в—Џ Curve shape of voltage

Sinusoidal or distorted

  • в—Џ Buffering of measured variables

Yes

  • в—Џ Parameter length

74 byte

  • в—Џ Bandwidth of measured value acquisition

2 kHz; Harmonics: 39 / 50 Hz, 32 / 60 Hz

Operating mode for measured value acquisition

 

  • — automatic detection of line frequency

No; Parameterizable

Measuring range

 

  • — Frequency measurement, min.

45 Hz

  • — Frequency measurement, max.

65 Hz

Measuring inputs for voltage

 

  • — Measurable line voltage between phase and neutral conductor

277 V

  • — Measurable line voltage between the line conductors

480 V

  • — Measurable line voltage between phase and neutral conductor, min.

90 V

  • — Measurable line voltage between phase and neutral conductor, max.

293 V

  • — Measurable line voltage between the line conductors, min.

155 V

  • — Measurable line voltage between the line conductors, max.

508 V

  • — Measurement category for voltage measurement in accordance with IEC 61010-2-030

CAT II; CAT III in case of guaranteed protection level of 1.5 kV

  • — Internal resistance line conductor and neutral conductor

3.4 MΩ

  • — Power consumption per phase

20 mW

  • — Impulse voltage resistance 1,2/50µs

1 kV

Measuring inputs for current

 

  • — measurable relative current (AC), min.

1 %; Relative to the secondary rated current 5 A

  • — measurable relative current (AC), max.

100 %; Relative to the secondary rated current 5 A

  • — Continuous current with AC, maximum permissible

5 A; at > +60 °C max. permissible current 1 A per phase

  • — Apparent power consumption per phase for measuring range 5 A

0.6 V·A

  • — Rated value short-time withstand current restricted to 1 s

100 A

  • — Input resistance measuring range 0 to 5 A

25 mΩ; At the terminal

  • — Zero point suppression

Parameterizable: 2 ... 250 mA, default 50 mA

  • — Surge strength

10 A; for 1 minute

Accuracy class according to IEC 61557-12

 

  • — Measured variable voltage

0,2

  • — Measured variable current

0,2

  • — Measured variable apparent power

0.5

  • — Measured variable active power

0.5

  • — Measured variable reactive power

1

  • — Measured variable power factor

0.5

  • — Measured variable active energy

0.5

  • — Measured variable reactive energy

1

  • — Measured variable neutral current

0.5; calculated

  • — Measured variable phase angle

±1 °; not covered by IEC 61557-12

  • — Measured variable frequency

0.05

Potential separation

 

Potential separation channels

 

  • в—Џ between the channels and backplane bus

Yes; 3 700V AC (type test) CAT III

Isolation

 

Isolation tested with

2 300V AC for 1 min. (type test)

Ambient conditions

 

Ambient temperature during operation

 

  • в—Џ horizontal installation, min.

-40 °C; = Tmin; < -25 °C min. permissible supply voltage 110 V AC

  • в—Џ horizontal installation, max.

70 °C; = Tmax; > +60 °C max. permissible current 1 A per phase

  • в—Џ vertical installation, min.

-40 °C; = Tmin

  • в—Џ vertical installation, max.

50 °C; = Tmax

Altitude during operation relating to sea level

 

  • в—Џ Ambient air temperature-barometric pressure-altitude

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)

Relative humidity

 

  • в—Џ With condensation, tested in accordance with IEC 60068-2-38, max.

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

Use in stationary industrial systems

 

  • — to biologically active substances according to EN 60721-3-3

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

  • — to chemically active substances according to EN 60721-3-3

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

  • — to mechanically active substances according to EN 60721-3-3

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Dimensions

 

Width

20 mm

Height

73 mm

Depth

58 mm

Weights

 

Weight (without packaging)

45 g

Data for selecting a current transformer

 

  • в—Џ Burden power current transformer x/1A, min.

As a function of cable length and cross section, see device manual

  • в—Џ Burden power current transformer x/5A, min.

As a function of cable length and cross section, see device manual


















skener.ru

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Арматура DENDOR

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Датчики и измерители

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Регуляторы и регистраторы

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Пневматическое оборудование

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Краны и Клапаны

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Измерительные приборы

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Системы беспроводного управления «умный дом»

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Бесконтактные выключатели Конечные выключатели Оптические датчики Энкодеры

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Установка умягчения

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Установка обезжелезивания
Каталог оборудования 2018
Siemens Industry Catalog Drive technology Automation technology Automation systems Operator control and monitoring systems SIMATIC HMI Identification systems Industrial communication Industrial controls Industry software PC-based Automation Process control systems Process instrumentation Process analytics SITOP power supply Products for specific requirements Automation technology for extreme conditions SIMATIC industrial automation systems Controllers SIPLUS IO systems SIPLUS ET 200 systems for the control cabinet ET 200SP SIPLUS interface modules SIPLUS extreme RAIL interface modules SIPLUS I/O modules SIPLUS digital inputs SIPLUS digital outputs SIPLUS analog inputs SIPLUS analog outputs SIPLUS technology modules SIPLUS communication SIPLUS failsafe I/O modules SIPLUS extreme RAIL digital inputs SIPLUS extreme RAIL digital outputs SIPLUS extreme RAIL analog inputs SIPLUS extreme RAIL analog outputs SIPLUS extreme RAIL technology modules SIPLUS extreme RAIL communication SIPLUS failsafe I/O modules SIPLUS BaseUnits SIPLUS BusAdapters SIPLUS extreme RAIL BaseUnits SIPLUS extreme RAIL BusAdapter ET 200S ET 200MP ET 200M SIPLUS PROFIBUS components for ET 200 SIPLUS extreme RAIL gateways SIMOTION Motion Control System Process control systems Operator control and monitoring systems Industrial communication Industrial controls Power supplies SIPLUS add-ons Telecontrol systems for comprehensive applications IO systems for heating elements Automatic door controllers Condition Monitoring Systems Time synchronization Energy Building Technologies Low-Voltage controls and distribution Safety Systems - Safety Integrated Market-specific solutions Industry Services Software ... and everything else you need




  © ООО "СК ЭНЕРГО" 2007-2022
  (4872) 700-366  skenergo@mail.ru
Яндекс.Метрика