Siemens
01 2018
(4872) 700-366
skenergo@mail.ru

Article number

6ES7132-6BH00-0BA0

6ES7132-6BF60-0AA0

6ES7132-6BF00-0AA0

6ES7132-6BF00-0BA0

6ES7132-6BF00-0CA0

ET 200SP, DQ 16X24VDC/0,5A ST

ET 200SP, DQ 8X24VDC/0,5A SINK BASIC

ET 200SP, DQ 8X24VDC/0,5A BASIC, PU 1

ET 200SP, DQ 8X24VDC/0,5A ST

ET 200SP, DQ 8X24VDC/0,5A HF

General information

Product type designation

DQ 16x24 VDC/0.5 A ST

DQ 8x24VDC/0.5A SNK BA

DQ 8x24 VDC/0.5 A BA

DQ 8x24 VDC/0.5 A ST

DQ 8x24 V DC/0.5 A HF

Firmware version

V1.0

V1.0

V1.0

V1.1

V2.0

  • FW update possible

Yes

Yes

Yes

Yes

Yes

usable BaseUnits

BU type A0

BU type A0

BU type A0

BU type A0

BU type A0

Color code for module-specific color identification plate

CC00

CC01

CC02

CC02

CC02

Product function

  • I&M data

Yes; I&M0 to I&M3

Yes; I&M0 to I&M3

Yes; I&M0 to I&M3

Yes; I&M0 to I&M3

Yes; I&M0 to I&M3

Engineering with

  • STEP 7 TIA Portal configurable/integrated as of version

V11 SP2 / V13

V13 / V13

V13 SP1 / -

V11 SP2 / V13

V13 SP1 / -

  • STEP 7 configurable/integrated as of version

V5.5 SP3 / -

V5.5 SP3 / -

V5.5 SP3 / -

V5.5 SP3 / -

V5.5 / -

  • PCS 7 configurable/integrated as of version

V8.1 SP1

V8.1 SP1

V8.1 SP1

  • PROFIBUS as of GSD version/GSD revision

GSD Revision 5

GSD Revision 5

GSD Revision 5

GSD Revision 5

One GSD file each, Revision 3 and 5 and higher

  • PROFINET as of GSD version/GSD revision

GSDML V2.3

GSDML V2.3

GSDML V2.3

GSDML V2.3

GSDML V2.3

Operating mode

  • DQ

Yes

Yes

Yes

Yes

Yes

  • DQ with energy-saving function

No

No

No

No

No

  • PWM

No

No

No

No

No

  • Oversampling

No

No

No

No

No

  • MSO

No

No

No

No

Yes

Redundancy

  • Redundancy capability

Yes

Yes

Yes

Yes

Yes

Supply voltage

Rated value (DC)

24V

24V

24V

24V

24V

permissible range, lower limit (DC)

19.2V

19.2V

19.2V

19.2V

19.2V

permissible range, upper limit (DC)

28.8V

28.8V

28.8V

28.8V

28.8V

Reverse polarity protection

Yes

Yes

Yes

Yes

Input current

Current consumption, max.

60mA; without load

45mA; without load

35mA; without load

Output voltage

Rated value (DC)

24V

24V

24V

24V

24V

Power loss

Power loss, typ.

1W

1.5W

1W

1W

1W

Address area

Address space per module

  • Address space per module, max.

2byte

1byte

1byte

1byte; + 1 byte for QI information

8byte; 2 channels per submodule + QI information

  • Outputs

1byte

Hardware configuration

Automatic encoding

  • Mechanical coding element

Yes

Yes

Selection of BaseUnit for connection variants

  • 1-wire connection

BU type A0

BU type A0

  • 2-wire connection

BU type A0

BU type A0

  • 3-wire connection

BU type A0 with AUX terminals

BU type A0 with AUX terminals

  • 4-wire connection

No

No

Digital outputs

Type of digital output

Source output (PNP, current-sourcing)

Source output (PNP, current-sourcing)

Source output (PNP, current-sourcing)

Source output (PNP, current-sourcing)

Source output (PNP, current-sourcing)

Number of digital outputs

16

8

8

8

8

Current-sinking

No

Yes

No

No

No

Current-sourcing

Yes

No

Yes

Yes

Yes

Short-circuit protection

Yes

Yes

Yes; per channel, electronic

Yes

Yes

  • Response threshold, typ.

0.7 to 1.3 A

1.5A

0.7 to 1.3 A

0.7 to 1.3 A

0.7 to 1.3 A

Open-circuit detection

No

Limitation of inductive shutdown voltage to

Typ. L+ (-50 V)

Typ. 47 V

Typ. L+ (-53 V)

Typ. L+ (-50 V)

Typ. L+ (-50 V)

Controlling a digital input

Yes

Yes

Yes

Yes

Yes

Switching capacity of the outputs

  • with resistive load, max.

0.5A

0.5A

0.5A

0.5A

0.5A

  • on lamp load, max.

5W

5W

5W

5W

5W

Load resistance range

  • lower limit

48Ω

48Ω

48Ω

48Ω

48Ω

  • upper limit

12kΩ

3400Ω

100kΩ

12kΩ

12kΩ

Output current

  • for signal "1" rated value

0.5A

0.5A

0.5A

0.5A

0.5A

  • for signal "0" residual current, max.

0.1mA

5A

1mA

0.1mA

0.1mA

Output delay with resistive load

  • "0" to "1", typ.

50s

50s

  • "0" to "1", max.

300s

100s; at rated load

50s; at rated load

  • "1" to "0", typ.

100s

100s

  • "1" to "0", max.

600s

150s; at rated load

100s; at rated load

Parallel switching of two outputs

  • for uprating

No

No

No

No

No

  • for redundant control of a load

Yes

Yes

Yes; per module

Yes

Yes

Switching frequency

  • with resistive load, max.

100Hz

100Hz

100Hz

100Hz

100Hz

  • with inductive load, max.

2Hz

0.5Hz

2Hz

2Hz

2Hz

  • on lamp load, max.

10Hz

10Hz

10Hz

10Hz

10Hz

Total current of the outputs

  • Current per channel, max.

0.5A

0.5A

0.5A

0.5A

0.5A

  • Current per module, max.

8A

4A

4A

4A

4A

Total current of the outputs (per module)

horizontal installation

  • up to 30 C, max.

8A

  • up to 40 C, max.

8A

  • up to 50 C, max.

6A

  • up to 60 C, max.

4A

4A

4A

4A

4A

vertical installation

  • up to 30 C, max.

8A

  • up to 40 C, max.

6A

  • up to 50 C, max.

4A

4A

4A

4A; in all other mounting positions

  • up to 60 C, max.

4A

4A

Cable length

  • shielded, max.

1000m

1000m

1000m

1000m

1000m

  • unshielded, max.

600m

600m

600m

600m

600m

Isochronous mode

Isochronous operation (application synchronized up to terminal)

No

No

No

No

Yes

Execution and activation time (TCO), min.

48s

Bus cycle time (TDP), min.

500s

Interrupts/diagnostics/status information

Diagnostics function

Yes

Yes

Yes

Yes

Yes

Substitute values connectable

Yes

No

Yes

Yes

Yes

Alarms

  • Diagnostic alarm

Yes

Yes

Yes

Yes

Yes

Diagnostic messages

  • Monitoring the supply voltage

Yes

Yes

Yes

Yes

Yes

  • Wire-break

Yes; Module-wise

No

No

Yes; Module-wise

Yes; channel by channel

  • Short-circuit

No

No

Yes; Module-wise

Yes; channel by channel

  • Short-circuit to M

Yes; Module-wise

  • Short-circuit to L+

Yes; Module-wise

  • Group error

Yes

Yes

Yes

Yes

Diagnostics indication LED

  • Monitoring of the supply voltage (PWR-LED)

Yes; green PWR LED

Yes; green PWR LED

Yes; green PWR LED

Yes; green PWR LED

Yes; green PWR LED

  • Channel status display

Yes; Green LED

Yes; Green LED

Yes; Green LED

Yes; Green LED

Yes; Green LED

  • for channel diagnostics

No

No

No

No

Yes; Red LED

  • for module diagnostics

Yes; green/red DIAG LED

Yes; green/red DIAG LED

Yes; green/red DIAG LED

Yes; green/red DIAG LED

Yes; green/red DIAG LED

Potential separation

Potential separation channels

  • between the channels

No

No

No

No

No

  • between the channels and backplane bus

Yes

Yes

Yes

Yes

Yes

  • between the channels and the power supply of the electronics

No

Isolation

Isolation tested with

707 V DC (type test)

707 V DC (type test)

707 V DC (type test)

707 V DC (type test)

707 V DC (type test)

Altitude during operation relating to sea level

  • Ambient air temperature-barometric pressure-altitude

On request: Negative ambient temperature down to -30 C (without condensation), installation altitudes between 2 000 m and 5 000 m

Dimensions

Width

15mm

15mm

15mm

15mm

15mm

Height

73mm

73mm

73mm

73mm

73mm

Depth

58mm

58mm

58mm

58mm

58mm

Weights

Weight, approx.

28g

30g

28g

28g

30g


Article number

6ES7132-6BD20-0BA0

6ES7132-6BD20-0CA0

6ES7132-6BD20-0DA0

6ES7132-6FD00-0BB1

6ES7132-6GD50-0BA0

ET 200SP, DQ 4X24VDC/2A ST

ET 200SP, DQ 4X24VDC/2A HF

ET 200SP, DQ 4X24VDC/2A HIGH SPEED, PU 1

ET 200SP, DQ 4X24..230VAC/2A ST

ET 200SP, RQ 4X24VDC/2A CO ST

General information

Product type designation

DQ 4x24 V DC/2 A ST

DQ 4x24 V DC/2 A HF

DQ 4x24 V DC/2 A HS

DQ 4x24 ... 230 V AC/2 A ST

RQ 4x24VUC/2A CO ST

HW functional status

from FS04

Firmware version

V1.1

V1.0

V1.0.1

V1.0

V1.0

  • FW update possible

Yes

Yes

Yes

Yes

Yes

usable BaseUnits

BU type A0

BU type A0

BU type A0

BU type B1

BU type A0

Color code for module-specific color identification plate

CC02

CC02

CC00

CC41

CC00

Product function

  • I&M data

Yes; I&M0 to I&M3

Yes; I&M0 to I&M3

Yes; I&M0 to I&M3

Yes; I&M0 to I&M3

Yes; I&M0 to I&M3

Engineering with

  • STEP 7 TIA Portal configurable/integrated as of version

V11 SP2 / V13

V13 / V13

V13 SP1

V13 / V13

V13 / V13

  • STEP 7 configurable/integrated as of version

V5.5 SP3 / -

V5.5 SP3 / -

V5.5 SP3 / -

V5.5 SP3 / -

V5.5 SP3 / -

  • PCS 7 configurable/integrated as of version

V8.1 SP1

  • PROFIBUS as of GSD version/GSD revision

GSD Revision 5

GSD Revision 5

GSD Revision 5

GSD Revision 5

GSD Revision 5

  • PROFINET as of GSD version/GSD revision

GSDML V2.3

GSDML V2.3

GSDML V2.3

GSDML V2.3

GSDML V2.3

Operating mode

  • DQ

Yes

Yes

Yes

Yes

Yes

  • DQ with energy-saving function

No

No

Yes; Valve control

No

No

  • PWM

No

No

Yes

No

No

  • Oversampling

No

No

Yes

No

No

  • MSO

No

Yes

No

No

No

Redundancy

  • Redundancy capability

Yes

Supply voltage

Rated value (DC)

24V

24V

24V

24V

permissible range, lower limit (DC)

19.2V

19.2V

19.2V

19.2V

permissible range, upper limit (DC)

28.8V

28.8V

28.8V

28.8V

Rated value (AC)

230V

Reverse polarity protection

Yes

Yes

Yes

Input current

Current consumption (rated value)

11.5mA

50mA

Current consumption, max.

60mA; without load

60mA; without load

50mA; without load

Output voltage

Rated value (DC)

24V

24V

24V

Rated value (AC)

230V; 24V AC to 230V AC

Power loss

Power loss, typ.

1W

1W

2.5W; at 24 V, 25 C, DQ mode, 2 A per channel

9W; Active power, load voltage 230 V, all outputs loaded with 2 A, 50 Hz

1.2W

Address area

Address space per module

  • Address space per module, max.

1byte; + 1 byte for QI information

1byte; + 1 byte for QI information

1byte; + 1 byte for QI information

1byte; + 1 byte for QI information

1byte; + 1 byte for QI information

  • Inputs

1byte; With QI

1byte; With QI

1byte; With QI

  • Outputs

16byte; Max. in Oversampling mode

1byte

1byte

Digital outputs

Type of digital output

Source output (PNP, current-sourcing)

Source output (PNP, current-sourcing)

Source output (PNP, current-sourcing)

Triac with zero point detection

Relays

Number of digital outputs

4

4

4

4

4

Current-sinking

No

No

No

No

Current-sourcing

Yes

Yes

Yes; Push-pull output

Yes

Short-circuit protection

Yes

Yes

Yes

No; When using BU type B1, a miniature, quick-response fuse with 10 A tripping current must be provided

No

  • Response threshold, typ.

2.8 to 5.2 A

2.8 to 5.2 A

6A

Limitation of inductive shutdown voltage to

Typ. L+ (-50 V)

L+ -(37 to 41V)

M (-1 V)

Controlling a digital input

Yes

Yes; Minimum current consumption 7 mA

No

Yes

Digital output functions, parameterizable

  • PWM output

Yes

  • Number, max.

4

  • Cycle duration, parameterizable

Yes; 0 ms, 0.2 ms, 0.4 ms, 0.93 ms, 1.33 ms, 4.27 ms, 10.67 ms, 21.33 ms, 34.13 ms, 59.73 ms

  • Resolution of the duty cycle

0.1%

  • Digital output with oversampling

Yes

  • Number, max.

4

  • Values per cycle, max.

32

  • Resolution, min.

100s

Switching capacity of the outputs

  • with resistive load, max.

2A

2A

2A

2A

  • on lamp load, max.

10W

10W

10W

100W

Load resistance range

  • lower limit

12Ω

12Ω

12Ω

  • upper limit

3400Ω

3400Ω

3400Ω

Output voltage

  • for signal "1", min.

20.4V

Output current

  • for signal "1" rated value

2A

2A

2A

2A

  • for signal "1" permissible range, min.

10mA

  • for signal "1" permissible range, max.

2A

  • for signal "0" residual current, max.

0.1mA

0.1mA

0.1mA

460A

Output delay with resistive load

  • "0" to "1", typ.

50s

50s

  • "0" to "1", max.

50s

1s

10ms

  • "1" to "0", typ.

100s

100s

  • "1" to "0", max.

100s

1s

10ms

Parallel switching of two outputs

  • for logic links

No

  • for uprating

No

No

No

No

  • for redundant control of a load

Yes

Yes

Switching frequency

  • with resistive load, max.

100Hz

100Hz

5kHz

10Hz

2Hz

  • with inductive load, max.

2Hz

2Hz

5kHz

0.5Hz; Higher frequencies are possible, see Equipment Manual / Product Information

  • on lamp load, max.

10Hz

10Hz

5kHz

1Hz

Total current of the outputs

  • Current per channel, max.

2A

2A

2A

2A

2A

  • Current per module, max.

8A

8A

8A

8A

8A

Total current of the outputs (per module)

horizontal installation

  • up to 30 C, max.

8A

8A

8A; DQ mode

  • up to 40 C, max.

8A

8A

6.9A; DQ mode

8A

  • up to 50 C, max.

6A

6A

4.7A; DQ mode

6A

  • up to 60 C, max.

4A

4A

2.5A; DQ mode

4A

8A

vertical installation

  • up to 30 C, max.

8A

8A

7.2A; DQ mode

8A

  • up to 40 C, max.

6A

6A

5.6A; DQ mode

6A

  • up to 50 C, max.

4A

4A

4A; DQ mode

4A

  • up to 60 C, max.

4A

4A

4A; DQ mode

8A

Relay outputs

  • Number of relay outputs

4

  • Rated supply voltage of relay coil L+ (DC)

24V

  • Current consumption of relays (coil current of all relays), max.

40mA

Switching capacity of contacts

  • with resistive load, max.

2A

  • Thermal continuous current, max.

2A

  • Switching current, min.

1mA; 5 V DC

  • Rated switching voltage (DC)

24V

  • Rated switching voltage (AC)

24V

Triac outputs

  • Size of motor starters according to NEMA, max.

5

Cable length

  • shielded, max.

1000m

1000m

50m

1000m

1000m

  • unshielded, max.

600m

600m

50m

600m

200m

Isochronous mode

Isochronous operation (application synchronized up to terminal)

No

Yes

Yes; Operating modes DQ and OVS only

No

No

Bus cycle time (TDP), min.

500s

125s

Jitter, max.

8s

1s

Interrupts/diagnostics/status information

Diagnostics function

Yes

Yes

Yes

No

Yes

Substitute values connectable

Yes

Yes

Yes

Yes

Yes

Alarms

  • Diagnostic alarm

Yes

Yes

Yes

No

Yes

Diagnostic messages

  • Monitoring the supply voltage

Yes

Yes

Yes

No

Yes

  • Wire-break

Yes; Module-wise

Yes; channel by channel

No

No

No

  • Short-circuit

Yes; Module-wise

Yes; channel by channel

Yes; Module-wise

No

No

  • Group error

Yes

Yes

Yes

Yes

Yes

Diagnostics indication LED

  • Monitoring of the supply voltage (PWR-LED)

Yes; green PWR LED

Yes; green PWR LED

Yes; green PWR LED

Yes; green PWR LED

Yes; green PWR LED

  • Channel status display

Yes; Green LED

Yes; Green LED

Yes; Green LED

Yes; Green LED

Yes; Green LED

  • for channel diagnostics

No

Yes; Red LED

No

No

No

  • for module diagnostics

Yes; green/red DIAG LED

Yes; green/red DIAG LED

Yes; green/red DIAG LED

Yes; green/red DIAG LED

Yes; green/red DIAG LED

Potential separation

Potential separation channels

  • between the channels

No

No

No

No

Yes

  • between the channels and backplane bus

Yes

Yes

Yes

Yes

Yes

  • between the channels and the power supply of the electronics

No

Yes

Permissible potential difference

between different circuits

75 V DC/60 V AC (base isolation)

Isolation

Isolation tested with

707 V DC (type test)

707 V DC (type test)

707 V DC (type test)

2 545 V DC/2 s (routine test)

707 V DC (type test)

Dimensions

Width

15mm

15mm

15mm

20mm

15mm

Height

73mm

73mm

73mm

73mm

73mm

Depth

58mm

58mm

58mm

58mm

58mm

Weights

Weight, approx.

30g

30g

31g

50g

30g


Article number

6ES7132-6HD00-0BB1

6ES7132-6MD00-0BB1

ET 200SP, RQ NO 4X120VDC..230VAC/5A ST

ET 200SP,RQ NO-MA 4X120VDC..230VAC/5A ST

General information

Product type designation

RQ 4x120 VDC … 230 VAC/5 A NO ST

RQ 4x120 V DC ... 230 V AC/5 A NO MA ST

Firmware version

V1.1

V1.0

  • FW update possible

Yes

Yes

usable BaseUnits

BU type B0, B1

BU type B0, B1

Color code for module-specific color identification plate

CC00

CC40

Product function

  • I&M data

Yes; I&M0 to I&M3

Yes; I&M0 to I&M3

Engineering with

  • STEP 7 TIA Portal configurable/integrated as of version

V13 SP1

V13 SP1

  • STEP 7 configurable/integrated as of version

V5.5 SP3 / -

V5.5 SP3 / -

  • PROFIBUS as of GSD version/GSD revision

GSD Revision 5

GSD Revision 5

  • PROFINET as of GSD version/GSD revision

GSDML V2.3

GSDML V2.3

Operating mode

  • DQ

Yes

Yes

  • DQ with energy-saving function

No

No

  • PWM

No

No

  • Oversampling

No

No

  • MSO

No

No

Supply voltage

Rated value (DC)

24V

24V

permissible range, lower limit (DC)

19.2V

19.2V

permissible range, upper limit (DC)

28.8V

28.8V

Reverse polarity protection

Yes

Yes

Input current

Current consumption, max.

100mA; without load

100mA; without load

Power loss

Power loss, typ.

1.5W

1.5W

Address area

Address space per module

  • Address space per module, max.

1byte; + 1 byte for QI information

1byte; + 1 byte for QI information

  • Inputs

1byte; With QI

1byte; With QI

  • Outputs

1byte

1byte

Digital outputs

Type of digital output

Relays

Relays

Number of digital outputs

4

4

Short-circuit protection

No

No

Switching frequency

  • with resistive load, max.

2Hz

2Hz

  • with inductive load, max.

0.5Hz

0.5Hz

  • on lamp load, max.

2Hz

2Hz

Total current of the outputs

  • Current per channel, max.

5A

5A

  • Current per module, max.

20A

20A

Total current of the outputs (per module)

horizontal installation

  • up to 50 C, max.

20A

  • up to 60 C, max.

20A

16A

vertical installation

  • up to 40 C, max.

20A

  • up to 50 C, max.

16A

  • up to 60 C, max.

20A

Relay outputs

  • Number of relay outputs

4

4

  • Rated supply voltage of relay coil L+ (DC)

24V

24V

  • Current consumption of relays (coil current of all relays), max.

40mA

40mA

  • external protection for relay outputs

Yes, with 6A

Yes, with 6A

  • Number of operating cycles, max.

7000000; see additional description in the manual

7000000; see additional description in the manual

Switching capacity of contacts

  • with inductive load, max.

2A; see additional description in the manual

2A; see additional description in the manual

  • with resistive load, max.

5A; see additional description in the manual

5A; see additional description in the manual

  • Thermal continuous current, max.

5A; Max. 1 385 VA, 150 W

5A

  • Switching current, min.

100mA; 5 V DC

100mA; 5 V DC

  • Rated switching voltage (DC)

24 V DC to 120 V DC

24 V DC to 120 V DC

  • Rated switching voltage (AC)

24V AC to 230V AC

24V AC to 230V AC

Cable length

  • shielded, max.

1000m

1000m

  • unshielded, max.

200m

200m

Isochronous mode

Isochronous operation (application synchronized up to terminal)

No

No

Interrupts/diagnostics/status information

Diagnostics function

Yes

Yes

Substitute values connectable

Yes

Yes

Alarms

  • Diagnostic alarm

Yes

Yes

Diagnostic messages

  • Monitoring the supply voltage

Yes

Yes

  • Wire-break

No

No

  • Short-circuit

No

No

  • Group error

Yes

Yes

Diagnostics indication LED

  • Monitoring of the supply voltage (PWR-LED)

Yes; green PWR LED

Yes; green PWR LED

  • Channel status display

Yes; Green LED

Yes; Green LED

  • for channel diagnostics

No

No

  • for module diagnostics

Yes; green/red DIAG LED

Yes; green/red DIAG LED

Potential separation

Potential separation channels

  • between the channels

Yes

Yes

  • between the channels and backplane bus

Yes

Yes

  • between the channels and the power supply of the electronics

Yes

Yes

Permissible potential difference

between channels and backplane bus/supply voltage

240 V AC

240 V AC

between backplane bus and supply voltage

75 V DC/60 V AC

Isolation

Isolation tested with

2 500 V DC (type test)

2 500 V DC (type test)

tested with

  • between channels and backplane bus/supply voltage

2500 V DC

2500 V DC

  • between backplane bus and supply voltage

707 V DC (type test)

707 V DC (type test)

Dimensions

Width

20mm

20mm

Height

73mm

73mm

Depth

58mm

58mm

Weights

Weight, approx.

40g

45g



















  © " " 2007-2022