General information | | |
Product type designation | CP 341 | CP 341 |
Supply voltage | | |
Rated value (DC) | | |
| Yes | Yes |
Input current | | |
from supply voltage L+, max. | 100 mA | 100 mA |
from backplane bus 5 V DC, max. | 70 mA | 70 mA |
Power loss | | |
Power loss, typ. | 1.6 W | 1.6 W |
Power loss, max. | 2.4 W | 2.4 W |
Interfaces | | |
Number of interfaces | 1; Isolated | 1; Isolated |
Interface physics, RS 232C (V.24) | Yes | |
Interface (physical) RS 422/485 (X.27) | | Yes |
Transmission rate, min. | 0.3 kbit/s | 0.3 kbit/s |
Transmission rate, max. | 115.2 kbit/s | 115.2 kbit/s |
Point-to-point | | |
| 15 m | 1 200 m |
| Serial printers | Serial printers |
| 9-pin sub D connector | 15-pin sub D socket |
Integrated protocol driver | | |
| Yes | Yes; not with RS 485 |
| Yes | Yes |
| Yes | Yes; not with RS 485 |
Telegram length, max. | | |
| 4 096 byte | 4 096 byte |
| 4 096 byte | 4 096 byte |
| 4 096 byte | 4 096 byte |
Transmission rate, RS 422/485 | | |
| | 115.2 kbit/s |
| | 115.2 kbit/s |
| | 115.2 kbit/s |
| | 115.2 kbit/s |
Transmission speed, RS 232 | | |
| 115.2 kbit/s | |
| 115.2 kbit/s | |
| 115.2 kbit/s | |
| 115.2 kbit/s | |
Standards, approvals, certificates | | |
CE mark | Yes | Yes |
UL approval | Yes; File E239877 | Yes; File E239877 |
FM approval | Yes; CofC 3028431 | Yes; CofC 3028431 |
RCM (formerly C-TICK) | Yes | Yes |
KC approval | Yes | Yes |
EAC (formerly Gost-R) | Yes | Yes |
Ambient conditions | | |
Ambient temperature during operation | | |
| -25 °C; = Tmin | -25 °C; = Tmin |
| 70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use | 70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use |
Ambient temperature during storage/transportation | | |
| -40 °C | -40 °C |
| 70 °C | 70 °C |
Altitude during operation relating to sea level | | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
Relative humidity | | |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Resistance | | |
Use in stationary industrial systems | | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Software | | |
Block | | |
| 6 100 byte; Data communication, sending and receiving | 6 100 byte; Data communication, sending and receiving |
Connection method | | |
Power supply | 3 screw-type terminals: L+, M, GND | 3 screw-type terminals: L+, M, GND |
Dimensions | | |
Width | 40 mm | 40 mm |
Height | 125 mm | 125 mm |
Depth | 120 mm | 120 mm |
Weights | | |
Weight, approx. | 300 g | 300 g |