Connections (Standard)Description | Terminal |
|---|
10 ... 30 V DC | 1 | Speed out-CW | 2 | Speed out-CCW | 3 | Common | 4 | Ground | GND |
- Determine the pulley shaft rotation on the end of the pulley shaft to which the WS300 is attached.
- If the pulley shaft is rotating clockwise, connect the appropriate wire to terminal 2. If the pulley shaft is rotating counterclockwise, connect the appropriate wire to terminal 3.
- Do not connect terminals 2 and 3 at the same time.
- Connection between the WS300 standard unit and the integrator should be made with three-wire shielded, 0.82 mm2 (18 AWG) cable.
- Ground shield of cable at integrator only.
- Connect shield to appropriate terminal at the integrator.
Terminal Connections to integrator WS300 | 1 +V | 2 CW | 3 CCW | 4 Cmn | GND |
|---|
Milltronics BW500 | 19 | 16 | 16 | 17 | N/C | SIWAREX FTC | CI+, 1L+ | CI- | CI- | 1M | N/C | SIWAREX WP241 | 1L+ | DI.0 | DI.0 | 2M, 1M | N/C |
Connections (IS) Description | Terminal |
|---|
5 ... 16 V DC, 25 mA max. (from IS Switch Isolator) | 1 | Speed out | 2 | Ground | GND |
- Only terminals 1 and 2 are required; rotation in a clockwise or counter-clockwise direction is not required.
- To connect the switch isolator, use two-wire shielded 0.324 mm2 (22 AWG) cable. Use the same cable to connect the switch isolator to the integrator.
- Ground shield of cable at integrator only.
- Connect shield to appropriate terminal at the integrator.
Terminal Connections to integrator W300 IS | IS Switch Isolator Terminal | Milltronics BW500 | SIWAREX FTC | SIWAREX WP241 |
|---|
1 | 3 | | | | 2 | 1 | | | | | 7 | 16 | 1L+ | 1L+ | | 8 | 17 | CI+ | CI+ |
Connect CI- to Common
|
|