Determine the pulley shaft rotation on the end of the pulley shaft to which the WS300 is attached.
If the pulley shaft is rotating clockwise, connect the appropriate wire to terminal 2. If the pulley shaft is rotating counterclockwise, connect the appropriate wire to terminal 3.
Do not connect terminals 2 and 3 at the same time.
Connection between the WS300 standard unit and the integrator should be made with three-wire shielded, 0.82 mm2 (18 AWG) cable.
Ground shield of cable at integrator only.
Connect shield to appropriate terminal at the integrator.
Terminal Connections to integrator
WS300
1
+V
2
CW
3
CCW
4
Cmn
GND
Milltronics BW500
19
16
16
17
N/C
SIWAREX FTC
CI+, 1L+
CI-
CI-
1M
N/C
SIWAREX WP241
1L+
DI.0
DI.0
2M, 1M
N/C
Connections (IS)
Description
Terminal
5 ... 16 V DC, 25 mA max. (from IS Switch Isolator)
1
Speed out
2
Ground
GND
Only terminals 1 and 2 are required; rotation in a clockwise or counter-clockwise direction is not required.
To connect the switch isolator, use two-wire shielded 0.324 mm2 (22 AWG) cable. Use the same cable to connect the switch isolator to the integrator.
Ground shield of cable at integrator only.
Connect shield to appropriate terminal at the integrator.