PLC and motion control performances |
Maximum number of axes | 16 | 32 | 64 |
Minimum PROFIBUS cycle clock | 2 ms | 1 ms | 1 ms |
Minimum PROFINET transmission cycle clock | 0.5 ms | 0.5 ms | 0.5 ms |
Minimum servo/interpolator cycle clock | 2.0 ms | 1.0 ms | 0.5 ms |
Integrated drive control |
Max. number of axes for integrated drive control (servo / vector / V/f) | 6 / 4 / 8 (alternative) (Drive control based on SINAMICS S120 CU320, firmware version V2.x) | 6 / 4 / 8 (alternative) (Drive control based on SINAMICS S120 CU320, firmware version V2.x) | 6 / 4 / 8 (alternative) (Drive control based on SINAMICS S120 CU320, firmware version V2.x) |
Memory |
RAM (Random Access Memory) (+ 20 MB for Java applications) | 48 MB | 48 MB | 96 MB |
RAM disk (load memory) | 23 MB | 23 MB | 47 MB |
Retentive memory | 364 KB | 364 KB | 364 KB |
Persistent memory (user data on CF) | 300 MB | 300 MB | 300 MB |
Communication |
DRIVE-CLiQ interfaces | 4 | 4 | 6 |
USB interfaces | 2 | 2 | 2 |
Ethernet interfaces | 2 | 2 | 2 |
PROFIBUS interfaces | 2 - Equidistant and isochronous
- Can be configured as master or slave
| 2 - Equidistant and isochronous
- Can be configured as master or slave
| 2 - Equidistant and isochronous
- Can be configured as master or slave
|
PROFINET interfaces | Optionally over CBE30: - 1 interface with 4 ports
- Supports PROFINET IO with IRT and RT
- Can be configured as PROFINET IO controller and/or device
| Optionally over CBE30: - 1 interface with 4 ports
- Supports PROFINET IO with IRT and RT
- Can be configured as PROFINET IO controller and/or device
| Optionally over CBE30: - 1 interface with 4 ports
- Supports PROFINET IO with IRT and RT
- Can be configured as PROFINET IO controller and/or device
|
General technical specifications |
Fan | Optional fan/battery module (single fan) | Optional fan/battery module (single fan) | Double fan/battery module included in scope of delivery |
Supply voltage | | | |
| 24 V DC | 24 V DC | 24 V DC |
| 20.4 ... 28.8 V | 20.4 ... 28.8 V | 20.4 ... 28.8 V |
Current consumption, typ. (Without load on inputs/outputs, without 24 V supply via DRIVE-CLiQ and PROFIBUS interfaces) | 600 mA | 600 mA | 1 A |
Starting current, typ. | 6 A | 6 A | 5 A |
Power loss, typ. | 15 W | 15 W | 24 W |
Permissible ambient temperature | | | |
| -40 ... +70 °C (-40 … +158 °F) | -40 ... +70 °C (-40 … +158 °F) | -40 ... +70 °C (-40 … +158 °F) |
| 0 ... 55 °C (32 … 131 °F) Maximum installation altitude 5000 m (16405 ft) above sea level. As of an altitude of 2000 m (6562 ft), the max. ambient temperature decreases by 7 °C (44.6 °F) every 1000 m (3281 ft). | 0 ... 55 °C (32 … 131 °F) Maximum installation altitude 5000 m (16405 ft) above sea level. As of an altitude of 2000 m (6562 ft), the max. ambient temperature decreases by 7 °C (44.6 °F) every 1000 m (3281 ft). | 0 ... 55 °C (32 … 131 °F) Maximum installation altitude 5000 m (16405 ft) above sea level. As of an altitude of 2000 m (6562 ft), the max. ambient temperature decreases by 7 °C (44.6 °F) every 1000 m (3281 ft). |
Permissible relative humidity (without condensation) | 5 ... 95% | 5 ... 95% | 5 ... 95% |
Permissible air pressure | 700 ... 1060 hPa | 700 ... 1060 hPa | 700 ... 1060 hPa |
Degree of protection acc. to EN 60529 (IEC 60529) | IP20 | IP20 | IP20 |
Dimensions (W x H x D) | 50 x 380 x 270 mm (1.97 x 14.96 x 10.63 in) 230 mm (9.06 in) depth with disassembled spacer; all dimensions without fan/battery module | 50 x 380 x 270 mm (1.97 x 14.96 x 10.63 in) 230 mm (9.06 in) depth with disassembled spacer; all dimensions without fan/battery module | 50 x 380 x 270 mm (1.97 x 14.96 x 10.63 in) 230 mm (9.06 in) depth with disassembled spacer; all dimensions without double fan/battery module |
Weight | | | |
| 2600 g (5.73lb) | 2600 g (5.73lb) | 3100 g (6.84 lb) |
| 10 g (0.35 oz) | 10 g (0.35 oz) | 10 g (0.35 oz) |
Digital inputs | 8 | 8 | 8 |
| | | |
| 24 V DC | 24 V DC | 24 V DC |
| 15 ... 30 V | 15 ... 30 V | 15 ... 30 V |
| -3 ... +5 V | -3 ... +5 V | -3 ... +5 V |
| Yes, in groups of 4 | Yes, in groups of 4 | Yes, in groups of 4 |
- Current consumption typ. at signal level 1
| 10 mA at 24 V | 10 mA at 24 V | 10 mA at 24 V |
- Input delay, typ. (hardware)
| L → H: 50 µs H → L: 150 µs | L → H: 50 µs H → L: 150 µs | L → H: 50 µs H → L: 150 µs |
Digital inputs/outputs (parameterizable) | 8 (max. 6 as high-speed measuring inputs, max. 8 as high-speed cam outputs) | 8 (max. 6 as high-speed measuring inputs, max. 8 as high-speed cam outputs) | 8 (max. 6 as high-speed measuring inputs, max. 8 as high-speed cam outputs) |
If used as an input |
| | | |
| 24 V DC | 24 V DC | 24 V DC |
| 15 ... 30 V | 15 ... 30 V | 15 ... 30 V |
| -3 ... +5 V | -3 ... +5 V | -3 ... +5 V |
| No | No | No |
- Current consumption typ. at signal level 1
| 10 mA at 24 V | 10 mA at 24 V | 10 mA at 24 V |
- Input delay, typ. (hardware)
| L → H: 5 µs H → L: 50 µs | L → H: 5 µs H → L: 50 µs | L → H: 5 µs H → L: 50 µs |
- Measuring input, reproducibility
| 5 µs | 5 µs | 5 µs |
If used as an output |
| 24 V DC | 24 V DC | 24 V DC |
| 20.4 ... 28.8 V | 20.4 ... 28.8 V | 20.4 ... 28.8 V |
| No | No | No |
| 500 mA per output | 500 mA per output | 500 mA per output |
| 2 mA | 2 mA | 2 mA |
- Output delay time, typ./max. (hardware, with 48 Ω load)
| L → H: 150 µs / 400 µs H → L: 75 µs / 100 µs | L → H: 150 µs / 400 µs H → L: 75 µs / 100 µs | L → H: 150 µs / 400 µs H → L: 75 µs / 100 µs |
- Cam output, reproducibility
| 125 µs | 125 µs | 125 µs |
- Switching frequency of the outputs, max.
| | | |
| 100 Hz | 100 Hz | 100 Hz |
| 2 Hz | 2 Hz | 2 Hz |
| 11 Hz | 11 Hz | 11 Hz |
| Yes | Yes | Yes |
Additional technical specifications |
Non-volatile data backup 1) | | | |
| 5 days (real-time clock/SRAM backup) | 5 days (real-time clock/SRAM backup) | 5 days (real-time clock/SRAM backup) |
| Only a few minutes | Only a few minutes | Only a few minutes |
Approvals, according to | cULus and C-Tick | cULus and C-Tick | cULus and C-Tick |