Both CPUs feature: - High-performance processor:
The CPUs achieve instruction execution times as low as 0.03 µs per binary instruction. - CPU 416F-2: 8 MB main memory (of which 4 MB each for program or data);
CPU 416F-3 PN/DP: 11.2 MB main memory (of which 5.6 MB each for program or data); fast main memory for parts of the user program that are significant for execution. - Flexible expansion possibilities:
Max. 262144 digital, 16384 analog inputs/outputs - MPI multi-point interface:
With the MPI it is possible to establish simple networking of max. 32 stations at a data transmission rate of up to 12 Mbps. The CPUs can establish up to 44 connections to stations of the communication bus (C bus) and the MPI. - Mode selector:
Toggle switch design - Diagnostics buffer:
The last 120 error and interrupt events are stored in a ring buffer for diagnostic purposes. The number of entries can be parameterized. - Real-time clock:
Diagnostic alarms of the CPU are tagged with the date and time. - Memory card:
To expand the integrated load memory. RAM and FEPROM cards (FEPROM for saving even at zero voltage). - Combined MPI/DP interface and integrated PROFIBUS DP interface (with CPU 416F-2):
The PROFIBUS DP master interface allows a distributed automation configuration offering high speed and ease of use. The distributed I/O is treated like a central I/O from the point of view of the user (same configuring, addressing and programming). Mixed installation: SIMATIC S5 and SIMATIC S7 as PROFIBUS master acc. to EN 50170.
CPU 416F-3 PN/DP also features: - Submodule socket:
Using the IF 964-DP interface module, an additional PROFIBUS DP master system can be connected. - PROFINET interface with 2 ports (switch):
- PROFINET IO, 256 IO devices can be connected
- PROFINET CBA
Failsafe I/O modules can be connected to all integrated interfaces, to IF 964-DP and/or via communication modules (CP443-5 Ext. and CP443-1 Advanced). Safety-related communication is performed over PROFIBUS DP with the PROFIsafe profile.
|
|