Input | |
Measurement | Flow by measuring the transit time difference of ultrasonic signals through ultrasonic transducers in DN 100 (4") … 3000 (120") 2-path sensor pipes (depending on selected size, 1-path or 4-path special solutions are possible). |
Nominal diameters and number of paths | 2-path DN 100 (4") ... DN 3000 (120") (depending on size, optionally also 1-path and 4-path) |
Max. cable length | 120 m (395 ft) (shielded coaxial cable). For Ex version the transducer cable length is restricted to 3 m (9.84 ft) in order to meet requirements for electrical immunity. For systems with sizes ≥ DN 1500 (60") cable length is recommended to be max. 30 m (98.4 ft). |
Output | |
Function | Current output programmable for flow, sound velocity or amplitude level. |
Analog output | Active current output (13.2 V < open loop voltage < 15.8 V) |
| 4 … 20 mA |
| 20 … 22.5 mA, adjustable |
| 3.6 mA, 22 mA, or 24 mA |
| Max. 600 Ω; for non Ex version ≤ 230 Ω for HART communication ≤ 330 Ω for Ex-version |
- Only PROFIBUS PA version:
| Analog output omitted, is replaced by digital PROFIBUS PA interface |
Digital output 1 | |
Function | Pulse, frequency or status output - programmable for pulses, frequency, alarm, limit or status. |
- Active or passive signal, can be configured with positive or negative logic
| Active: 24 V DC, ≤ 24 mA, Ri = 300 Ω Passive: open collector, 30 V DC, ≤ 200 mA |
- For explosion protection (ATEX version) and PROFIBUS PA version
| Only passive: open collector 30 V DC, ≤ 100 mA |
- Output function, configurable
| Pulse output - Adjustable pulse significance ≤ 5 000 pulses/s
- Adjustable pulse width ≥ 0.1 ms
Frequency response - fEND selectable up to 10 kHz
Limit for flow, totalizers, ultrasonic velocity or ultrasonic amplitude device status, flow direction |
Digital output 2 | |
Function | Relay output - programmable for alarm, limit or status indication. |
| Switching capacity max. 5 W Max. 50 V DC, max. 200 mA DC Self-resetting fuse, Ri = 9 Ω |
- For explosion protection (ATEX version)
| Max. 30 V DC, max. 100 mA DC, 50 mA AC (cf. EC-Type Examination certificate) |
- Output function, configurable
| Limit for flow, ultrasonic velocity or ultrasonic amplitude flow direction device status |
- Only PROFIBUS PA version:
| Digital output 2 omitted |
Communication via analog output 4 … 20 mA | |
- PC/laptop or HART communicator with SITRANS F flowmeter
| |
- Load with connection of coupling module
| min. 230 Ω (max. 330 Ω for Ex-version) |
- Load with connection of HART communicator
| min. 230 Ω |
| 2-wire shielded ≤ 3 km (≤ 1.86 miles) Multi-core shielded ≤ 1.5 km (≤ 0.93 miles) |
| HART, version 5.1 |
Communication via PROFIBUS PA interface | Layers 1 + 2 according to PROFIBUS PA Communication system according to IEC 61158/EN 50170 |
| Separate supply, four-wire device Permissible bus voltage 9 … 32 V See certificates and approvals |
- Current consumption from bus
| 10 mA; ≤ 15 mA in event of error with electronic current limiting |
Electrical isolation | Outputs electrically isolated from power supply and from another |
Accuracy | |
Error in measurement (at reference conditions) | |
| ≤ ± 0,5 % of measured value at 0,5 … 10 m/s or |
| ≤ ± 0,25/V[m/s]% of measured value at flow < 0,5 m/s |
| As pulse output plus ± 0.1 % of measured value, ± 20 µA |
| ≤ ± 0,25 % of measured value at 0.5 … 10 m/s |
Reference conditions (water) | |
- Process temperature in the connected sensor
| 25 °C ± 5 °C (77 °F ± 9 °F) |
- Ambient temperature at the transmitter
| 25 °C ± 5 °C (77 °F ± 9 °F) |
- Transmitter warming-up time
| 30 min. |
Rated operation conditions | |
Ambient conditions | |
Ambient temperature | |
| -20 … +50 °C (-4 … +122 °F) |
- In potentially explosive atmospheres
| Observe temperature classes |
| -25 … +80 °C (-13 … +176 °F) |
Enclosure rating | IP65 (NEMA 4) |
Electromagnetic compatibility | For use in industrial environments |
| To EN 55011 / CISPR-11 |
| To EN/IEC 61326-1 (Industry) |
Medium conditions | The measuring media must be ultrasonic signal compatible. It must be homogeneous and not two-phased to transfer the acoustic ultrasonic signals. |
| -200 … +250 °C (-328 … +482 °F) (not directly influenced by medium temperature) |
| Influence accuracy of measurement (approx. max. 3 % gases or solids) |
Design | |
Separate version | Transmitter is connected to the transducers via 3 … 120 m (9.8 ft … 395 ft) long specially shielded cables (coaxial cable) |
| For ATEX versions mounted in the Ex area only with 3 m (9.8 ft) long cables. |
Enclosure material | Die-cast aluminium, painted |
Wall mounting bracket (standard and special) | Stainless steel (standard: always incl.) |
Weigth of transmitter | 4.4 kg (9.7 lb) |
Electrical connection | Cable glands (always incl.) |
| - Power supply and outputs
- 2 x M20 (HART)/M25 (PROFIBUS) or
2 x ½“-NPT (HART)
|
| |
Display and controls | |
Display | LCD, two lines with 16 characters each |
- Multi-display:
2 freely-selectable values are displayed simultaneously in two lines
| Flow, volume, mass flow, mass, flow velocity, speed of sound, ultrasonic signal information, current, frequency, alarm information |
Operation | 4 infrared keys, hierarchical menu shown with codes |
Power supply | |
Supply voltage | |
| 120 … 230 V AC ± 15 % (50/60 Hz) or 19 … 30 V DC/21 ... 26 V AC |
| 19 … 30 V DC/21 … 26 V AC |
Power failure | No effect for at least 1 period (> 20 ms) |
Power consumption | Approx. 10 VA/10 W |
Certificates and approvals | |
Explosion protection | ATEX II 2 G Ex dem [ia/ib] IIC T6/T4/T3 Gb |
| T6 for media < 85 °C (185 °F) T5 for media < 100 °C (212 °F) T4 for media < 135 °C (275 °F) T3 for media < 200 °C (392 °F) |