Standards | | IEC/EN 60947-5-1, EN ISO 14119 |
Rated insulation voltageUi | V | 250 |
Degree of pollution according to IEC 60664-1 | | Class 3 |
Rated impulse withstand voltage Uimp | kV | 4 |
Rated operational voltage Ue | | |
| V | 24 |
| V | 230 |
Conventional thermal current Ith | A | 6 |
Rated operational current Ie | | |
- With alternating current 50/60 Hz
| | Ie / AC-15 or B300 |
| A | 6 |
| A | 6 |
| A | 6 |
| | Ie / DC-13 or Q300 |
| A | 3 |
| A | 0.55 |
| A | 0.27 |
Magnet | | |
| N | 1300 | 2600 |
- Locking force according to EN ISO 14119
| N | 1000 | 2000 |
| CO | 3.5 |
Short-circuit protection1) | | |
- With DIAZED fuse links,
utilization category gG
| A | 6 |
- With circuit breaker, Char. C C
| A | 0.5 |
Mechanical endurance | | 1 Г— 106 operating cycles |
Electrical endurance | | |
- With 3RH.1, 3RT contactors in size S00, S0
| | 1 Г— 106 operating cycles |
- For utilization category AC-15 when interrupting Ie / AC-15 at 230 V
| | 100000 operating cycles |
- With utilization category DC-12/DC-13
| | For direct current depending on the loading of the switch |
Switching frequency with 3RH.1, 3RT contactors in size S00, S0 | | 6000 operating cycles/h |
Shock resistance acc. to IEC 60068-2-27 | g/ms | 30 / 11 |