General information | |
Product family | ET 200SP |
Product category | Analog module input |
Product type designation | ET 200SP, AI 2xSG 4/6-wire HS |
Firmware version | V1.0.0 |
| Yes |
Suitable BaseUnits | BU type A0 |
Color code for module-specific color-coded label | CC00 |
Product function | |
| Yes, I&M0 to I&M3 |
| No |
| No |
- Measuring range adaptation
| Yes, +/- 0.5 mV/V to 320 mV/Volt |
Engineering with | |
- STEP 7 TIA Portal can be configured/integrated as of version
| V14 SP1 |
- STEP 7 can be configured/integrated as of version
| V5.5 SP4 or higher |
- PROFIBUS as of GSD version/GSD revision
| GSD revision 5 |
- PROFINET as of GSD version/GSD revision
| GSDML V2.32 |
Operating mode | |
| Yes, 2 channels per module |
| No |
CiR – Configuration in RUN | |
Parameter reassignment possible in RUN | Yes |
Calibration possible in RUN | No |
Installation type/mounting | |
Rack mounting | Yes |
Front mounting | Yes |
Rail mounting | Yes |
Wall/direct mounting | No |
Supply voltage | |
Type of supply voltage | DC |
Rated value (DC) | 24 V |
Valid range, lower limit (DC) | 19.2 V |
Valid range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes |
Input current | |
Current consumption (rated value) | 70 mA |
Power loss | |
Typical power loss | 1.2 W, without sensor supply |
Address range | |
Address range per module, max. | 32 bytes |
Hardware configuration | |
BaseUnits for connection variants | |
| BU type A0 |
| BU type A0 |
Analog inputs | |
No. of analog inputs | 2 differential inputs |
Cycle time (all channels), min. | 100 Ојs |
Analog input with oversampling | Yes |
| 14 |
| 100 Ојs |
Standardization of measured values | |
Input ranges | |
| Yes |
Input ranges (rated values), voltages | |
| 16/28 bits |
Cable length | |
| 500 m (1 640.42 ft) |
Generation of analog input values | |
Measuring principle | Sigma delta |
Integration and conversion time/resolution per channel | |
- Resolution with overrange (bits including sign), max.
| 28 bits, 16 bits with oversampling |
- Interference voltage suppression for interference frequency f1 in Hz
| 60 / 50 / off |
- Conversion time (per channel)
| 100 Ојs |
Measured value smoothing | |
- IIR low-pass filter ordinal
| 0.1 ... 6 553.5 Hz, adjustable |
- Moving average value filter
| 0.1 ... 655.35 Hz, adjustable |
| 0.1 ... 1 000.0 Hz, adjustable |
Encoders | |
Connection of sensors | |
| Yes |
| 4.85 V DC, +/- 3% |
- Resistance of full bridge strain gauge min.
| 80 ohms |
- Resistance of full bridge strain gauge max.
| 5 000 ohms |
Errors/accuracies | |
Linearity error (in relation to input range), (+/-) | ≤ 0.025% |
Temperature error (in relation to input range), (+/-) 6-wire connection | ≤ 5 ppm/contactor relay |
Temperature error (in relation to input range), (+/-) 4-wire connection | ≤ 10 ppm/contactor relay |
Temperature error zero point (+/-) | ≤ 0.25 µV/contactor relay |
Error limit according to DIN 1319-1 at 20 °C +/-10 K | |
- Voltage, related to input range, (+/-)
| ≤ 0.05 % |
Isochronous mode | |
Isochronous mode (application synchronized up to terminal) | Yes |
Filter and processing (TWE), min. | 87 Ојs |
Bus cycle time (TDP), min. | 125 Ојs |
Interrupts/diagnostics/status information | |
Interrupts | |
| Yes |
| Yes, two high and two low limits |
Diagnostic messages | |
- Monitoring of supply voltage
| Yes |
| Yes |
| Yes |
| Yes |
| Yes |
Diagnostics LED | |
- Monitoring of supply voltage (PWR LED)
| Yes, green PWR LED |
| Yes, green LED |
| Yes, red LED |
| Yes, green/red DIAG LED |
Galvanic isolation | |
Galvanic isolation of channels | |
| No |
- Between channels and backplane bus
| Yes |
- Between channels and electronics power supply
| Yes |
Insulation | |
Insulation tested with | 707 V DC (type test) |
Degree of protection and protection class | |
Degree of protection | IP20 |
Standards, approvals and certificates | |
Suitable for safety functions | No |
Equipment designation according to DIN EN 81346-2 | K |
Use in hazardous areas | |
- Explosion protection category for gas
| No |
- Explosion protection category for dust
| No |
Ambient conditions | |
Ambient temperature in operation | |
- Horizontal mounting, min.
| -25 °C |
- Horizontal mounting, max.
| -60 °C |
| -25 °C |
| -50 °C |
Connections | |
Design of electrical connection | Push-in terminals |
Dimensions | |
Width | 15 mm |
Height | 73 mm |
Depth | 58 mm |
Weight | |
Weight, approx. | 45 g |