General information | |
Product type designation | CB 1241 RS485 |
Input current | |
from backplane bus 5 V DC, typ. | 50 mA |
Power loss | |
Power loss, typ. | 1.5 W |
Interfaces | |
Point-to-point | |
| 1 000 m |
Integrated protocol driver | |
| Yes |
| Yes; Available as library function |
| Yes |
| Yes |
| Yes |
| Yes; Available as library function |
Protocols | |
Integrated protocols | |
Freeport | |
| 1 kbyte |
| 7 or 8 |
| 1 (Standard), 2 |
| No parity (standard); even, uneven, mark (parity bit always 1); space (parity bit always 0) |
3964 (R) | |
| 1 kbyte |
| 7 or 8 |
| 1 (Standard), 2 |
| No parity (standard); even, uneven, mark (parity bit always 1); space (parity bit always 0) |
Modbus RTU master | |
| 1 through 49 999 (Standard Modbus addressing) |
| 247; slave numbers 1 through 247, per MODBUS network segment maximum 32 devices, additional repeaters needed to expand the network to maximum configuration |
MODBUS RTU slave | |
| 1 through 49 999 (Standard Modbus addressing) |
Interrupts/diagnostics/status information | |
Diagnostic functions | Yes |
Isolation | |
Isolation tested with | 707 V DC (type test) and according to EN 50155 (routine test) |
Degree and class of protection | |
Degree of protection acc. to EN 60529 | |
| Yes |
Standards, approvals, certificates | |
CE mark | Yes |
Railway application | |
| Yes; EMC for rail vehicles |
| Yes; EMC for signal and telecommunications systems |
| Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC |
| Yes; Rail vehicles - see ambient conditions |
| Yes; Stationary electrical equipment - see ambient conditions |
| Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track) |
| Yes; Rail vehicles - temperature class T1, horizontal mounting position, salt spray Class ST2 |
| Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B |
| Yes; Rail vehicles - verification on request |
Ambient conditions | |
Free fall | |
| 0.3 m; five times, in product package |
Ambient temperature during operation | |
| -25 °C; = Tmin |
| 60 °C; = Tmax; +70 °C for 10 min (T1 acc. to EN 50155) |
Ambient temperature during storage/transportation | |
| -40 °C |
| 70 °C |
Altitude during operation relating to sea level | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) |
Relative humidity | |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Use in stationary industrial systems | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Use on land craft, rail vehicles and special-purpose vehicles | |
| Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request |
| Yes; Class 5C3 (RH < 75%) including salt spray according to EN 50155 (ST2). The supplied plug covers must remain in place over the unused interfaces during operation! |
| Yes; Class 5S3 including sand and dust. The supplied plug covers must remain in place over the unused interfaces during operation! |
Mechanics/material | |
Enclosure material (front) | |
| Yes |
Dimensions | |
Width | 38 mm |
Height | 62 mm |
Depth | 21 mm |
Weights | |
Weight, approx. | 40 g |
Other | |
Note: | For use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A Online Support article 109736776 |