General information | |
Product type designation | TM Timer DIDQ 10x24V |
usable BaseUnits | BU type A0 |
Product function | |
| Yes; I&M 0 |
Supply voltage | |
Load voltage L+ | |
| 24 V |
| 19.2 V |
| 28.8 V |
| Yes; against destruction |
Input current | |
Current consumption, max. | 50 mA; without load |
Encoder supply | |
Number of outputs | 1 |
24 V encoder supply | |
| Yes; L+ (-0.8 V) |
| Yes |
| 500 mA; Observe derating |
Power loss | |
Power loss, typ. | 1.5 W |
Address area | |
Occupied address area | |
| 26 byte |
| 32 byte |
Digital inputs | |
Number of digital inputs | 4 |
Digital inputs, parameterizable | Yes |
Input characteristic curve in accordance with IEC 61131, type 3 | Yes |
Digital input functions, parameterizable | |
| Yes |
| 4 |
| Yes |
| 3 |
| Yes |
| 1 |
| Yes |
| 4 |
| Yes |
| 1 |
| Yes |
| 3 |
Input voltage | |
| DC |
| 24 V |
| -30 to +5V |
| +11 to +30V |
| -30 V |
| 30 V |
Input current | |
| 2.5 mA |
Input delay (for rated value of input voltage) | |
| 3 µs for parameterization "none" |
for standard inputs | |
| Yes; none / 0.05 / 0.1 / 0.4 / 0.8 ms |
| 4 µs |
| 4 µs |
Cable length | |
| 1 000 m; Depending on sensor, cable quality and rate of change |
| 600 m; Depending on sensor, cable quality and rate of change |
Digital outputs | |
Type of digital output | Transistor |
Number of digital outputs | 6 |
Current-sinking | Yes; With High Speed output |
Current-sourcing | Yes |
Digital outputs, parameterizable | Yes |
Short-circuit protection | Yes; electronic/thermal |
| 1.7 A with Standard output, 0.5 A with High Speed output |
Limitation of inductive shutdown voltage to | -0.8 V |
Digital output functions, parameterizable | |
| Yes |
| 6 |
| Yes |
| 6 |
| Yes |
| 6 |
Switching capacity of the outputs | |
| 0.5 A; 0.1 A with High Speed output |
| 5 W; 1 W with High Speed output |
Load resistance range | |
| 48 Ω; 240 ohm with High Speed output |
| 12 kΩ |
Output voltage | |
| DC |
| 1 V; With High Speed output |
| 23.2 V; L+ (-0.8 V) |
Output current | |
| 0.5 A; 0.1 A with High Speed output, observe derating |
| 0.6 A; 0.12 A with High Speed output, observe derating |
| 2 mA |
| 0.5 mA |
Output delay with resistive load | |
| 1 µs; With High Speed output, 5 µs with Standard output |
| 1 µs; With High Speed output, 6 µs with Standard output |
Switching frequency | |
| 10 kHz |
| 10 Hz |
Total current of the outputs | |
| 3.5 A; Observe derating |
Cable length | |
| 1 000 m; Depending on load and cable quality |
| 600 m; Depending on load and cable quality |
Encoder | |
Connectable encoders | |
| Yes |
| Yes |
| Yes |
| 1.5 mA |
Encoder signals, incremental encoder (asymmetrical) | |
| 24 V |
| 50 kHz |
| 200 kHz; with quadruple evaluation |
| 600 m; Depending on input frequency, encoder and cable quality; max. 200 m at 50 kHz |
| Yes |
| Yes |
Encoder signal 24 V | |
| -30 V |
| 30 V |
Interface types | |
| Yes |
Isochronous mode | |
Isochronous operation (application synchronized up to terminal) | Yes |
Bus cycle time (TDP), min. | 375 µs |
Jitter, max. | 1 µs |
Interrupts/diagnostics/status information | |
Diagnostics function | Yes |
Substitute values connectable | Yes |
Alarms | |
| Yes |
Diagnostic messages | |
| Yes |
| Yes |
Diagnostics indication LED | |
| Yes; green PWR LED |
| Yes |
| Yes; green/red DIAG LED |
Integrated Functions | |
Number of counters | 3 |
Counting frequency (counter) max. | 200 kHz; with quadruple evaluation |
Counting functions | |
| Yes |
Potential separation | |
Potential separation channels | |
| Yes |
Ambient conditions | |
Ambient temperature during operation | |
| -40 °C |
| 60 °C; = Tmax; see Derating BasedOn (e.g. manual) |
| 0 °C |
| 50 °C; = Tmax; see Derating BasedOn (e.g. manual) |
Altitude during operation relating to sea level | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Relative humidity | |
| 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation |
Use in stationary industrial systems | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Decentralized operation | |
to SIMATIC S7-1500 | Yes |
Dimensions | |
Width | 15 mm |
Height | 73 mm |
Depth | 58 mm |
Weights | |
Weight, approx. | 45 g |