Installation type/mounting | |
Mounting | Mounting rail 7.5 mm and 15 mm |
Supply voltage | |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes |
Mains buffering | |
| 20 ms |
Input current | |
from supply voltage 1L+, max. | 400 mA |
Power loss | |
Power loss, typ. | 6 W |
Interfaces | |
PROFINET IO | |
| Yes |
| 100 Mbit/s |
| Yes; 4 RJ45 female connectors, 2 for each side |
| 4; 2 for each side |
Protocols | |
Supports protocol for PROFINET IO | Yes |
Protocols (Ethernet) | |
| Yes |
| Yes |
| Yes |
Isochronous mode | |
Isochronous operation (application synchronized up to terminal) | No; For operation on isochronous bus |
Interrupts/diagnostics/status information | |
Status indicator | Yes |
Alarms | Yes |
Diagnostic functions | Yes |
Diagnostics indication LED | |
| Yes; for each side |
| Yes; for each side |
| Yes; for each side |
| Yes; for each port |
Potential separation | |
between supply voltage and electronics | Yes; to power input 2 |
between Ethernet and electronics | Yes |
Permissible potential difference | |
between different circuits | 500 V DC |
Isolation | |
Isolation tested with | 707 V DC (type test) and according to EN 50155 (routine test) |
Standards, approvals, certificates | |
Railway application | |
| Yes; EMC for rail vehicles |
| Yes; EMC for signal and telecommunications systems |
| Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC |
| Yes; Rail vehicles - see ambient conditions |
| Yes; Stationary electrical equipment - see ambient conditions |
| Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track) |
| Yes; Rail vehicles - temperature class Tx, horizontal mounting position, salt spray Class ST2 |
| Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B |
| Yes; Rail vehicles - verification on request |
Ambient conditions | |
Ambient temperature during operation | |
| -40 °C; = Tmin; Startup @ -25 °C |
| 60 °C; = Tmax; +70 °C for 10 min (T1 acc. to EN 50155) |
Altitude during operation relating to sea level | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) |
Relative humidity | |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Use in stationary industrial systems | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Use on land craft, rail vehicles and special-purpose vehicles | |
| Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request |
| Yes; Class 5C3 (RH < 75%) including salt spray according to EN 50155 (ST2). The supplied plug covers must remain in place over the unused interfaces during operation! |
| Yes; Class 5S3 including sand and dust. The supplied plug covers must remain in place over the unused interfaces during operation! |
Dimensions | |
Width | 120 mm; Minimized with good handling |
Height | 119.5 mm |
Depth | 75 mm; with mounting rail |
Weights | |
Weight, approx. | 283 g |
Other | |
Note: | For use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A Online Support article 109736776 |