Article number

6AG1677-2AA31-4EB0

6AG1677-2AA40-4AA0

SIPLUS ET 200SP CPU 1515SP PC 4GB

SIPLUS ET 200SP CPU 1515SP PC SPARE 4GB

General information

Product type designation

CPU 1515SP PC

CPU 1515SP PC

HW functional status

FS05

FS03

Firmware version

V2.0

Installed software

  • Visualization

No

No

  • Control

S7-1500 Software Controller CPU 1505SP V2.0

No

Configuration control

via dataset

Yes

Control elements

Mode selector switch

1

1

Supply voltage

Type of supply voltage

24 V DC

24 V DC

permissible range, lower limit (DC)

19.2V

19.2V

permissible range, upper limit (DC)

28.8V

28.8V

Reverse polarity protection

Yes

Yes

Mains buffering

  • Mains/voltage failure stored energy time

5ms

5ms

Input current

Current consumption (rated value)

1.5A; Full processor load, incl. ET 200SP modules and using USB

1.5A; Full processor load, incl. ET 200SP modules and using USB

Current consumption (in no-load operation), typ.

0.6A

0.6A

Inrush current, max.

4.7A; Rated value

4.7A; Rated value

Power

Active power input, max.

36W; incl. ET 200SP modules and using USB

36W; incl. ET 200SP modules and using USB

Infeed power to the backplane bus

8.75W

8.75W

Power loss

Power loss, typ.

15W; without ET 200SP modules and without using USB

15W; without ET 200SP modules and without using USB

Processor

Processor type

Dual-Core 1 GHz, AMD G Series APU T40E

Dual-Core 1 GHz, AMD G Series APU T40E

Memory

Type of memory

DDR3-SDRAM

DDR3-SDRAM

Main memory

4 GB RAM

4 GB RAM

Flash Disk

8 GB

CFast memory card

Yes; 8 GB flash memory

No

SIMATIC memory card required

No

Work memory

  • integrated (for program)

1Mbyte

  • integrated (for data)

5Mbyte

  • integrated (for CPU function library of CPU Runtime)

10Mbyte

Load memory

  • integrated (on PC mass storage)

320Mbyte

Backup

  • with UPS

Yes; all memory areas declared retentive

  • with non-volatile memory

Yes

CPU processing times

for bit operations, typ.

10ns

for word operations, typ.

12ns

for fixed point arithmetic, typ.

16ns

for floating point arithmetic, typ.

64ns

CPU-blocks

Number of elements (total)

6000; In addition to blocks such as DBs, FBs and FCs, UDTs, global constants, etc. are also regarded as elements

DB

  • Number, max.

5999; Number range: 1 to 65535

  • Size, max.

5Mbyte

FB

  • Number, max.

5998; Number range: 1 to 65535

  • Size, max.

512kbyte

FC

  • Number, max.

5999; Number range: 1 to 65535

  • Size, max.

512kbyte

OB

  • Size, max.

1048kbyte

  • Number of free cycle OBs

100

  • Number of time alarm OBs

20

  • Number of delay alarm OBs

20

  • Number of cyclic interrupt OBs

20

  • Number of process alarm OBs

50

  • Number of DPV1 alarm OBs

3

  • Number of isochronous mode OBs

1

  • Number of technology synchronous alarm OBs

2

  • Number of startup OBs

100

  • Number of asynchronous error OBs

4

  • Number of synchronous error OBs

2

  • Number of diagnostic alarm OBs

1

Nesting depth

  • per priority class

24

Counters, timers and their retentivity

S7 counter

  • Number

2048

Retentivity

  • adjustable

Yes

IEC counter

  • Number

Any (only limited by the main memory)

Retentivity

  • adjustable

Yes

S7 times

  • Number

2048

Retentivity

  • adjustable

Yes

IEC timer

  • Number

Any (only limited by the main memory)

Retentivity

  • adjustable

Yes

Data areas and their retentivity

Retentive data area (incl. timers, counters, flags), max.

410kbyte; For storage in NVRAM; for storage in mass storage 5 242 020 bytes

Flag

  • Number, max.

16kbyte

  • Number of clock memories

8; 8 clock memory bits, grouped into one clock memory byte

Data blocks

  • Retentivity adjustable

Yes

  • Retentivity preset

No

Local data

  • per priority class, max.

64kbyte; max. 16 KB per block

Address area

Number of IO modules

8192

I/O address area

  • Inputs

32kbyte; All inputs are in the process image

  • Outputs

32kbyte; All outputs are in the process image

of which per assigned PC interface

  • Inputs (volume)

8kbyte

  • Outputs (volume)

8kbyte

Subprocess images

  • Number of subprocess images, max.

32

Hardware configuration

Integrated power supply

Yes

Yes

Number of distributed IO systems

20

Number of DP masters

  • Via CM

1

Rack

  • Modules per rack, max.

64; CPU 1515SP PC + 64 modules + server module

64; CPU + 64 modules + server module (mounting width max. 1 m)

  • Number of lines, max.

1

1

PtP CM

  • Number of PtP CMs

the number of connectable PtP CMs is only limited by the number of available slots

Time of day

Clock

  • Type

Hardware clock

Hardware clock

  • Hardware clock (real-time)

Yes; Resolution: 1 s

Yes; Resolution: 1 s

  • Backup time

6wk; At 40 C ambient temperature, typically

6wk; At 40 C ambient temperature, typically

  • Deviation per day, max.

10s; Typ.: 2 s

10s; Typ.: 2 s

Clock synchronization

  • supported

Yes

  • to DP, master

No

  • on Ethernet via NTP

Yes

  • on Windows clock, slave

Yes

Interfaces

Number of industrial Ethernet interfaces

2

1

Number of PROFINET interfaces

1

1

Number of PROFIBUS interfaces

1

Number of RS 485 interfaces

1; Via CM DP module

Number of USB interfaces

3; 3x USB 2.0 on the front, 500 mA each of which 2x 500 mA and 1x 100 mA simultaneously

3; 3x USB 2.0 on the front, 500 mA each of which 2x 500 mA and 1x 100 mA simultaneously

Number of SD card slots

1

1

Video interfaces

  • Graphics interface

1x DVI-I

1x DVI-I

1. Interface

Interface type

PROFINET

PROFINET

automatic detection of transmission rate

Yes

Yes

Autonegotiation

Yes

Yes

Autocrossing

Yes

Yes

Interface types

  • Number of ports

2

2

  • integrated switch

Yes

Yes

  • RJ 45 (Ethernet)

Yes; Via BusAdapter BA 2x RJ45

Yes; Via BusAdapter BA 2x RJ45

  • Transmission rate, max.

100Mbit/s

100Mbit/s

  • Industrial Ethernet status LED

Yes

Yes

  • BusAdapter (PROFINET)

Yes; Applicable BusAdapter: BA 2x RJ45, BA 2x FC

Functionality

  • Number of connections via this interface

88

  • PROFINET IO Controller

Yes

  • PROFINET IO Device

Yes

  • SIMATIC communication

Yes

  • Open IE communication

Yes

  • Web server

Yes

PROFINET IO Controller

Services

  • Isochronous mode

Yes

  • shortest clock pulse

500s

  • IRT

Yes

  • MRP

Yes

  • MRPD

Yes

  • Prioritized startup

Yes; Max. 32 PROFINET devices

  • Number of connectable IO Devices, max.

128

  • Of which IO devices with IRT, max.

64

  • of which in line, max.

64

  • Number of connectable IO Devices for RT, max.

128

  • of which in line, max.

128

  • Number of IO Devices that can be simultaneously activated/deactivated, max.

8

  • IO Devices changing during operation (partner ports), supported

Yes

  • Number of IO Devices per tool, max.

8

  • Updating times

The minimum value of the update time also depends on communication share set for PROFINET IO, on the number of IO devices, and on the quantity of configured user data

Update time for IRT

  • for send cycle of 500 s

500 s to 8 ms

  • for send cycle of 1 ms

1 ms to 16 ms

  • for send cycle of 2 ms

2 ms to 32 ms

  • for send cycle of 4 ms

4 ms to 64 ms

  • With IRT and parameterization of "odd" send cycles

Update time = set "odd" send clock (any multiple of 125 s: 375 s, 625 s ... 3 875 s)

Update time for RT

  • for send cycle of 500 s

500 s to 256 ms

  • for send cycle of 1 ms

1 ms to 512 ms

  • for send cycle of 2 ms

2 ms to 512 ms

  • for send cycle of 4 ms

4 ms to 512 ms

PROFINET IO Device

Services

  • Isochronous mode

No

  • IRT

Yes

  • MRP

Yes

  • MRPD

Yes

  • Prioritized startup

Yes

  • Shared device

Yes

  • Number of IO Controllers with shared device, max.

4

2. Interface

Interface type

Integrated Ethernet interface

Integrated Ethernet interface

Physics

RJ45

automatic detection of transmission rate

Yes

Yes

Autonegotiation

Yes

Yes

Autocrossing

Yes

Yes

Interface types

  • Number of ports

1

1

  • RJ 45 (Ethernet)

Yes; Integrated

Yes; Integrated

  • Transmission rate, max.

1000Mbit/s

1000Mbit/s

  • Industrial Ethernet status LED

No

No

3. Interface

Interface type

PROFIBUS with CM DP

Interface types

  • RS 485

Yes

Functionality

  • Number of connections via this interface

44

  • PROFIBUS DP master

Yes

  • PROFIBUS DP slave

Yes

  • SIMATIC communication

Yes

DP master

  • Number of DP slaves, max.

125

Services

  • Equidistance

No

  • Isochronous mode

No

DP slave

Services

  • Equidistance

No

  • Isochronous mode

No

RS 485

  • Transmission rate, max.

12Mbit/s

12Mbit/s

Protocols

Number of connections

  • Number of connections, max.

88

  • Number of connections reserved for ES/HMI/web

10

  • Number of S7 routing paths

16

SIMATIC communication

  • PG/OP communication

Yes

  • S7 routing

Yes

  • S7 communication, as server

Yes

  • S7 communication, as client

Yes

  • User data per job, max.

64kbyte

Open IE communication

  • TCP/IP

Yes

  • Data length, max.

64kbyte

  • ISO-on-TCP (RFC1006)

Yes

  • Data length, max.

64kbyte

  • UDP

Yes

  • Data length, max.

1472kbyte

  • SNMP

Yes

  • DCP

Yes

  • LLDP

Yes

Web server

  • HTTP

Yes; Via Windows and PROFINET interface

  • HTTPS

Yes; Only via PROFINET interface

OPC UA

  • OPC UA Server

Data access (read, write, subscribe), runtime license required

  • Application authentication

Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256

  • Security policies

Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256

  • User authentication

"anonymous" or by user name & password

Further protocols

  • MODBUS

Yes; MODBUS TCP

Media redundancy

  • Switchover time on line break, typ.

200ms

  • Number of stations in the ring, max.

50

S7 message functions

Number of login stations for message functions, max.

32

Program alarms

Yes

Number of configurable program alarms

10000

Number of simultaneously active program alarms

  • Number of program alarms

1000

  • Number of alarms for system diagnostics

200

  • Number of alarms for motion technology objects

160

Test commissioning functions

Joint commission (Team Engineering)

Yes; Parallel online access possible for up to 8 engineering systems

Status block

Yes; up to 8 simultaneously

Single step

No

Status/control

  • Status/control variable

Yes

  • Variables

Inputs, outputs, memory bits, DB, times, counters

  • Number of variables, max.

  • of which status variables, max.

200

  • of which control variables, max.

200

Forcing

  • Forcing

Yes

  • Forcing, variables

Inputs, outputs

  • Number of variables, max.

200

Diagnostic buffer

  • present

Yes

  • Number of entries, max.

1000

  • of which powerfail-proof

300

Traces

  • Number of configurable Traces

4

  • Memory size per trace, max.

512kbyte

Interrupts/diagnostics/status information

Diagnostics indication LED

  • RUN/STOP LED

Yes

  • ERROR LED

Yes

  • MAINT LED

Yes

Supported technology objects

Motion Control

Yes

  • Number of available Motion Control resources for technology objects (except cam disks)

2400

  • Required Motion Control resources

  • per speed-controlled axis

40; per axis

  • per positioning axis

80; per axis

  • per synchronous axis

160; per axis

  • per external encoder

80; per external encoder

  • per output cam

20; per cam

  • per cam track

160; per cam track

  • per probe

40; per probe

  • Positioning axis

  • Number of positioning axes at motion control cycle of 4 ms (typical value)

5

  • Number of positioning axes at motion control cycle of 8 ms (typical value)

12

Controller

  • PID_Compact

Yes; Universal PID controller with integrated optimization

  • PID_3Step

Yes; PID controller with integrated optimization for valves

  • PID-Temp

Yes; PID controller with integrated optimization for temperature

Counting and measuring

  • High-speed counter

Yes

EMC

Emission of radio interference acc. to EN 55 011

  • Limit class A, for use in industrial areas

Yes

Yes

Standards, approvals, certificates

CE mark

Yes

Yes

Ambient conditions

Ambient temperature during operation

  • min.

0C

0C

  • max.

60C; Up to 60 C with max. 32 ET 200SP modules and 3x 100 mA USB load; up to 55 C with max. 64 ET 200SP modules and 2x max. 500 mA and 1x max. 100 mA USB load

60C; Up to 60 C with max. 32 ET 200SP modules and 3x 100 mA USB load; up to 55 C with max. 64 ET 200SP modules and 2x max. 500 mA and 1x max. 100 mA USB load

  • horizontal installation, min.

0C; = Tmin

0C; = Tmin

  • horizontal installation, max.

60C; = Tmax; up to 60 C with max. 32 ET 200SP modules and 3x 100 mA USB load; up to 55 C with max. 64 ET 200SP modules and 2x max. 500 mA and 1x max. 100 mA USB load

60C; = Tmax; up to 60 C with max. 32 ET 200SP modules and 3x 100 mA USB load; up to 55 C with max. 64 ET 200SP modules and 2x max. 500 mA and 1x max. 100 mA USB load

  • vertical installation, min.

0C; = Tmin

0C; = Tmin

  • vertical installation, max.

50C; = Tmax; at max. 32 ET 200SP modules and 3x 100 mA USB load

50C; = Tmax; at max. 32 ET 200SP modules and 3x 100 mA USB load

Ambient temperature during storage/transportation

  • min.

-40C

-40C

  • max.

70C

70C

Altitude during operation relating to sea level

  • Ambient air temperature-barometric pressure-altitude

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Relative humidity

  • With condensation, tested in accordance with IEC 60068-2-38, max.

100%; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation

100%; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation

Vibrations

  • Operation, tested according to IEC 60068-2-6

Yes

Yes

  • Transport, tested acc. to IEC 60068-2-6

Yes

Yes

Shock testing

  • tested according to IEC 60068-2-6

Yes

Yes

  • tested according to IEC 60068-2-27

Yes

Yes

  • tested according to IEC 60068-2-29

Yes

Yes

  • Storage/transport, tested acc. to IEC 60068-2-27

Yes

Yes

Use in stationary industrial systems

  • to biologically active substances according to EN 60721-3-3

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

  • to chemically active substances according to EN 60721-3-3

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

  • to mechanically active substances according to EN 60721-3-3

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Operating systems

Operating systems

Windows Embedded Standard 7 E 32-bit

Configuration

Programming

Programming language

  • LAD

Yes

  • FBD

Yes

  • STL

Yes

  • SCL

Yes

  • CFC

No

  • GRAPH

Yes

Know-how protection

  • User program protection/password protection

Yes

  • Copy protection

Yes

  • Block protection

Yes

Access protection

  • Protection level: Write protection

Yes

  • Protection level: Read/write protection

Yes

  • Protection level: Complete protection

Yes

Cycle time monitoring

  • lower limit

adjustable minimum cycle time

  • upper limit

adjustable maximum cycle time

Open Development interfaces

  • Size of ODK SO file, max.

3.8Mbyte

Peripherals/Options

Peripherals

  • SD card

Optionally for additional mass storage

Optionally for additional mass storage

Dimensions

Width

160mm

160mm

Height

117mm

117mm

Depth

75mm

75mm

Weights

Weight, approx.

0.83kg

0.83kg