Supply voltage | |
Rated value (DC) | |
| Yes |
Input current | |
Current consumption, typ. | 5 mA |
from backplane bus 5 V DC, typ. | 20 mA |
Power loss | |
Power loss, typ. | 0.5 W |
Analog inputs | |
Number of analog inputs | 1; Resistance thermometer |
permissible input voltage for current input (destruction limit), max. | ± 35 V |
Technical unit for temperature measurement adjustable | Degrees Celsius/degrees Fahrenheit |
Input ranges | |
| Yes |
| No |
| No |
| Yes; Platinum (Pt) |
| Yes; 150 О©, 300 О©, 600 О© |
Input ranges (rated values), voltages | |
| >= 10 MOhm |
Input ranges (rated values), resistance thermometer | |
| Yes |
| 100 Ω |
| Yes |
| 1 000 Ω |
| Yes |
| 200 Ω |
| Yes |
| 500 Ω |
Input ranges (rated values), resistors | |
| Yes |
| Yes |
| Yes |
Thermocouple (TC) | |
Temperature compensation | |
| No |
Analog outputs | |
Number of analog outputs | 0 |
Analog value generation for the inputs | |
Measurement principle | integrating |
Integration and conversion time/resolution per channel | |
| 15 bit; + sign |
| No |
| 85 dB at 10 / 50 / 60 / 400 Hz |
Errors/accuracies | |
Temperature error (relative to input range), (+/-) | 25 °C ±0.1%, up to 55 °C ±0.25% total measurement range |
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) | 0.05 % |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency | |
| 120 dB |
Interrupts/diagnostics/status information | |
Alarms | Yes |
Diagnostic functions | Yes; Can be read out |
Alarms | |
| Yes |
Diagnostic messages | |
| Yes |
Diagnostics indication LED | |
| Yes |
| Yes |
Degree and class of protection | |
Degree of protection acc. to EN 60529 | |
| Yes |
Standards, approvals, certificates | |
CE mark | Yes |
Ambient conditions | |
Free fall | |
| 0.3 m; five times, in product package |
Ambient temperature during operation | |
| -40 °C; = Tmin; Startup @ -25 °C |
| 60 °C; = Tmax |
| -40 °C; = Tmin; Startup @ -25 °C |
| 50 °C; = Tmax |
Ambient temperature during storage/transportation | |
| -40 °C |
| 70 °C |
Altitude during operation relating to sea level | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Relative humidity | |
| 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation |
Use in stationary industrial systems | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Connection method | |
required front connector | Yes |
Mechanics/material | |
Enclosure material (front) | |
| Yes |
Dimensions | |
Width | 38 mm |
Height | 62 mm |
Depth | 21 mm |
Weights | |
Weight, approx. | 35 g |