Article number

6ES7655-5PX11-0XX0

SIMATIC CFU PA

General information

Product type designation

Compact Field Unit

HW functional status

E01

Firmware version

V1.0

  • FW update possible

Yes

Vendor identification (VendorID)

002AH

Device identifier (DeviceID)

060DH

Number of channels

16

Product function

  • I&M data

Yes; I&M0 to I&M4

  • The user can configure digital channels as input/output as required

Yes

  • Digital channels can be parameterized

Yes

Engineering with

  • STEP 7 TIA Portal configurable/integrated as of version

- / -

  • STEP 7 configurable/integrated as of version

From STEP 7 V5.6 HF1 and higher

  • PCS 7 configurable/integrated as of version

V9.0

  • PROFIBUS as of GSD version/GSD revision

- / -

Installation type/mounting

Mounting

on 35 mm DIN rail, 2 spacing units wide

Mounting position

Horizontal, vertical

Supply voltage

Type of supply voltage

24 V DC

Rated value (DC)

24V

permissible range, lower limit (DC)

19.2V

permissible range, upper limit (DC)

28.8V

Reverse polarity protection

Yes

Short-circuit protection

Yes

Redundant power supply

Yes

Mains buffering

  • Mains/voltage failure stored energy time

5ms; Bridging for field devices and communication

Input current

Current consumption (rated value)

2.5A

Current consumption, max.

2.55A

Inrush current, max.

8A

It

0.3As

Encoder supply

Number of outputs

8

Output voltage encoder supply, min.

18.2V

Short-circuit protection

Yes; Electronic

Output current

  • up to 60 C, max.

2A

  • up to 70 C, max.

1A

Power loss

Power loss, typ.

8.2W; Depending on the type of BusAdapter used (typ. RJ45)

Address space per station

  • Address space per station, max.

1440byte; Dependent on configuration

Digital inputs

Number of digital inputs

8

Source/sink input

Yes; P-reading

Input characteristic curve in accordance with IEC 61131, type 1

Yes

Input characteristic curve in accordance with IEC 61131, type 2

No

Input characteristic curve in accordance with IEC 61131, type 3

Yes

Pulse extension

No

Number of simultaneously controllable inputs

horizontal installation

  • up to 60 C, max.

8; Total current must be observed, see DQ

  • up to 70 C, max.

8; Total current must be observed, see DQ

vertical installation

  • up to 60 C, max.

8; Total current must be observed, see DQ

Input voltage

  • Rated value (DC)

24V

  • for signal "0"

-30 to +5V

  • for signal "1"

+11 to +30V

Input current

  • for signal "1", typ.

2.5mA; Typical

Input delay (for rated value of input voltage)

for standard inputs

  • parameterizable

No

  • at "0" to "1", max.

3.2ms

  • at "1" to "0", max.

3.2ms

Cable length

  • shielded, max.

1000m

  • unshielded, max.

600m

Digital outputs

Type of digital output

Transistor

Number of digital outputs

8

Current-sinking

No

Current-sourcing

Yes

Short-circuit protection

Yes

  • Response threshold, typ.

0.7 to 1.3 A

Limitation of inductive shutdown voltage to

Typ. L+ (-50 V)

Controlling a digital input

Yes

Switching capacity of the outputs

  • on lamp load, max.

5W

Load resistance range

  • lower limit

48Ω

  • upper limit

12kΩ

Output voltage

  • Type of output voltage

DC

  • for signal "1", min.

Ue minus 1 V

Output current

  • for signal "1" rated value

0.5A

  • for signal "0" residual current, max.

0.1mA

Output delay with resistive load

  • "0" to "1", max.

50s

  • "1" to "0", max.

100s

Parallel switching of two outputs

  • for uprating

No

  • for redundant control of a load

No

Switching frequency

  • with resistive load, max.

100Hz

  • with inductive load, max.

2Hz

  • on lamp load, max.

10Hz

Total current of the outputs

  • Current per channel, max.

0.5A

horizontal installation

  • up to 70 C, max.

1A

vertical installation

  • up to 60 C, max.

2A

Cable length

  • shielded, max.

1000m

  • unshielded, max.

600m

Encoder

Connectable encoders

  • 2-wire sensor

Yes

  • permissible quiescent current (2-wire sensor), max.

1.5mA

Interfaces

Number of PROFINET interfaces

1

Number of PROFIBUS interfaces

0

PROFIBUS PA

  • Transmission rate, max.

31.25kbit/s

  • Number of connectable PA field devices

8; Electrically isolated from other interfaces, isolation tested at 2 500 V DC

  • Current output to PA field devices, max.

320mA

  • permissible current per spur line

40mA

  • Automatic addressing

Yes

  • System-supported integration of field devices via PA profiles

Yes

  • Extended fieldbus diagnostics

Yes

1. Interface

Interface type

PROFINET

Isolated

Yes

Interface types

  • Number of ports

2

  • integrated switch

Yes

  • BusAdapter (PROFINET)

Yes

Functionality

  • PROFINET IO Device

Yes

  • PROFIBUS DP slave

No

Interface types

RJ 45 (Ethernet)

  • 100 Mbps

Yes

  • Autonegotiation

Yes

  • Autocrossing

Yes

Protocols

Supports protocol for PROFINET IO

Yes

PROFINET IO Device

Services

  • MRP

Yes

  • PROFINET system redundancy

Yes; Type S2

Open IE communication

  • LLDP

Yes

Isochronous mode

Isochronous operation (application synchronized up to terminal)

No

Interrupts/diagnostics/status information

Status indicator

Yes

Alarms

Yes

Diagnostic functions

Yes

Diagnostic messages

  • Monitoring of encoder power supply

Yes

  • Wire-break

Yes

  • Short-circuit

Yes

Diagnostics indication LED

  • RUN LED

Yes; Green LED

  • ERROR LED

Yes; Red LED

  • MAINT LED

Yes; yellow LED

  • Monitoring of the supply voltage (PWR-LED)

Yes

  • Digital input status indicator

Yes

  • Digital output status indicator

Yes

  • Spur line status/fault

Yes

Potential separation

between the channels and PROFINET

Yes

Potential separation digital inputs

  • between the channels

No

  • between the channels and the power supply of the electronics

No

Potential separation digital outputs

  • between the channels

No

  • between the channels and the power supply of the electronics

No

Isolation

Isolation tested with

1 500 V AC between PROFINET and electronics

Degree and class of protection

Degree of protection acc. to EN 60529

IP20

Ambient conditions

Ambient temperature during operation

  • min.

-40C

  • max.

70C

  • horizontal installation, min.

-40C

  • horizontal installation, max.

70C; Observe derating

  • vertical installation, min.

-40C

  • vertical installation, max.

60C; Observe derating

Ambient temperature during storage/transportation

  • min.

-40C

  • max.

85C

Relative humidity

  • Operation, max.

95%

Connection method

Design of electrical connection

Connection plug

Spur line

  • Number of spur lines

8

  • Type of cable

Type A

  • Cable diameter, min.

6mm

  • Cable diameter, max.

12mm

  • Conductor cross-section, min.

0.2mm

  • Conductor cross-section, max.

2.5mm

  • Cable length, max.

120m

  • total current output to field devices, max.

320mA

  • Number of connectable field devices

8

  • Current limitation per field device, max.

40mA

  • No-load voltage, max.

15.3V

  • short-circuit proof

Yes

  • Short-circuit current (test current); max.

8mA

  • intrinsically safe according to FISCO model

Yes

  • Debounce logic

Yes

Dimensions

Width

300mm; 329 mm

Height

115mm; 123 mm

Depth

40mm; 74 mm

Weights

Weight, approx.

580g