Input | | | | |
Input | 1-phase AC or DC | 1-phase AC or DC | 1-phase AC or DC | 1-phase AC or DC |
Rated voltage value Vin rated | 100...240V | 100...240V | 100...240V | 100...240V |
Voltage range AC | 85...264V | 85...264V | 85...264V | 85...264V |
Input voltage | | | | |
| 110...300V | 110...300V | 110...300V | 110...300V |
Wide-range input | Yes | Yes | Yes | Yes |
Mains buffering at Iout rated, min. | 40ms; at Vin = 187 V | 40ms; at Vin = 187 V | 40ms; at Vin = 187 V | 40ms; at Vin = 187 V |
Rated line frequency 1 | 50Hz | 50Hz | 50Hz | 50Hz |
Rated line frequency 2 | 60Hz | 60Hz | 60Hz | 60Hz |
Rated line range | 47...63Hz | 47...63Hz | 47...63Hz | 47...63Hz |
Input current | | | | |
| 0.3A | 0.7A | 1.22A | 1.95A |
| 0.2A | 0.35A | 0.66A | 0.97A |
Switch-on current limiting (+25 C), max. | 20A | 25A | 52A | 31A |
It, max. | 0.8As | 0.8As | 3As | 2.5As |
Built-in incoming fuse | internal | internal | internal | internal |
Protection in the mains power input (IEC 898) | Recommended miniature circuit breaker: from 6 A characteristic B or from 2 A characteristic C | Recommended miniature circuit breaker: from 6 A characteristic B or from 2 A characteristic C | Recommended miniature circuit breaker: from 10 A characteristic B or from 6 A characteristic C | Recommended miniature circuit breaker: from 10 A characteristic B or from 6 A characteristic C |
Output | | | | |
Output | Controlled, isolated DC voltage | Controlled, isolated DC voltage | Controlled, isolated DC voltage | Controlled, isolated DC voltage |
Rated voltage Vout DC | 24V | 24V | 24V | 24V |
Total tolerance, static | 3% | 3% | 3% | 3% |
Static mains compensation, approx. | 0.1% | 0.1% | 0.1% | 0.1% |
Static load balancing, approx. | 0.1% | 0.1% | 0.1% | 0.1% |
Residual ripple peak-peak, max. | 200mV | 200mV | 200mV | 200mV |
Residual ripple peak-peak, typ. | 30mV | 30mV | 30mV | 30mV |
Spikes peak-peak, max. (bandwidth: 20 MHz) | 300mV | 300mV | 300mV | 300mV |
Spikes peak-peak, typ. (bandwidth: 20 MHz) | 50mV | 50mV | 50mV | 50mV |
Adjustment range | | 22.2...26.4V | 22.2...26.4V | 22.2...26.4V |
Product function Output voltage adjustable | No | Yes | Yes | Yes |
Output voltage setting | | via potentiometer | via potentiometer | via potentiometer |
Status display | Green LED for output voltage OK | Green LED for output voltage OK | Green LED for output voltage OK | Green LED for output voltage OK |
On/off behavior | No overshoot of Vout (soft start) | No overshoot of Vout (soft start) | No overshoot of Vout (soft start) | No overshoot of Vout (soft start) |
Startup delay, max. | 0.5s | 0.5s | 0.5s | 0.5s |
Voltage rise, typ. | 100ms | 100ms | 100ms | 100ms |
Rated current value Iout rated | 0.6A | 1.3A | 2.5A | 4A |
Current range | 0...0.6A | 0...1.3A | 0...2.5A | 0...4A |
| +55 ... +70 C: Derating 2%/K | +55 ... +70 C: Derating 2%/K | +55 ... +70 C: Derating 2%/K | +55 ... +70 C: Derating 2%/K |
Supplied active power typical | 14.4W | 31.2W | 60W | 96W |
Parallel switching for enhanced performance | No | Yes | Yes | Yes |
Numbers of parallel switchable units for enhanced performance | | 2 | 2 | 2 |
Efficiency | | | | |
Efficiency at Vout rated, Iout rated, approx. | 81% | 86% | 90% | 89% |
Power loss at Vout rated, Iout rated, approx. | 3W | 5W | 7W | 12W |
Power loss [W] during no-load operation maximum | 0.3W | 0.3W | 0.3W | 0.3W |
Closed-loop control | | | | |
Dynamic mains compensation (Vin rated 15 %), max. | 0.2% | 0.2% | 0.2% | 0.2% |
Dynamic load smoothing (Iout: 10/90/10 %), Uout typ. | 2% | 1% | 2% | 2% |
Load step setting time 10 to 90%, typ. | 1ms | 1ms | 1ms | 1ms |
Load step setting time 90 to 10%, typ. | 1ms | 1ms | 1ms | 1ms |
Protection and monitoring | | | | |
Output overvoltage protection | Yes, according to EN 60950-1 | Yes, according to EN 60950-1 | Yes, according to EN 60950-1 | Yes, according to EN 60950-1 |
Current limitation, typ. | 0.8A | 1.7A | 3.2A | 5A |
Property of the output Short-circuit proof | Yes | Yes | Yes | Yes |
Short-circuit protection | Constant current characteristic | Constant current characteristic | Constant current characteristic | Constant current characteristic |
Enduring short circuit current RMS value | | | | |
| 0.8A | 1.7A | 3.2A | 5A |
Overload/short-circuit indicator | - | - | - | - |
Safety | | | | |
Primary/secondary isolation | Yes | Yes | Yes | Yes |
Galvanic isolation | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 |
Protection class | Class II (without protective conductor) | Class II (without protective conductor) | Class II (without protective conductor) | Class II (without protective conductor) |
CE mark | Yes | Yes | Yes | Yes |
UL/cUL (CSA) approval | cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus-Recognized (UL 60950, CSA C22.2 No. 60950), File E151273, NEC class 2 (acc. to UL 1310) | cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus-Recognized (UL 60950, CSA C22.2 No. 60950), File E151273, NEC class 2 (acc. to UL 1310) | cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus-Recognized (UL 60950, CSA C22.2 No. 60950), File E151273, NEC class 2 (acc. to UL 1310) | cULus-listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus-recognized (UL 60950, CSA C22.2 No. 60950), File E151273 |
Explosion protection | ATEX (EX) II 3G Ex nA IIC T3; cCSAus (CSA C22.2 No. 213-M1987, ANSI/ISA-12.12.01-2007) Class I, Div. 2, Group ABCD, T4 | ATEX (EX) II 3G Ex nA IIC T3; cCSAus (CSA C22.2 No. 213-M1987, ANSI/ISA-12.12.01-2007) Class I, Div. 2, Group ABCD, T4 | ATEX (EX) II 3G Ex nA IIC T3; cCSAus (CSA C22.2 No. 213-M1987, ANSI/ISA-12.12.01-2007) Class I, Div. 2, Group ABCD, T4 | ATEX (EX) II 3G Ex nA IIC T3; cCSAus (CSA C22.2 No. 213-M1987, ANSI/ISA-12.12.01-2007) Class I, Div. 2, Group ABCD, T4 |
FM approval | Class I, Div. 2, Group ABCD, T4 | Class I, Div. 2, Group ABCD, T4 | Class I, Div. 2, Group ABCD, T4 | Class I, Div. 2, Group ABCD, T4 |
CB approval | Yes | Yes | Yes | Yes |
Marine approval | available soon | available soon | available soon | available soon |
Degree of protection (EN 60529) | IP20 | IP20 | IP20 | IP20 |
EMC | | | | |
Emitted interference | EN 55022 Class B | EN 55022 Class B | EN 55022 Class B | EN 55022 Class B |
Supply harmonics limitation | not applicable | not applicable | not applicable | EN 61000-3-2 |
Noise immunity | EN 61000-6-2 | EN 61000-6-2 | EN 61000-6-2 | EN 61000-6-2 |
Operating data | | | | |
Ambient temperature | | | | |
| -25...+70C | -25...+70C | -25...+70C | -25...+70C |
| with natural convection | with natural convection | with natural convection | with natural convection |
| -40...+85C | -40...+85C | -40...+85C | -40...+85C |
| -40...+85C | -40...+85C | -40...+85C | -40...+85C |
Humidity class according to EN 60721 | Climate class 3K3, no condensation | Climate class 3K3, no condensation | Climate class 3K3, no condensation | Climate class 3K3, no condensation |
Mechanics | | | | |
Connection technology | screw-type terminals | screw-type terminals | screw-type terminals | screw-type terminals |
Connections | | | | |
| L, N: 1 screw terminal each for 0.5 ... 2.5 mm2 single-core/finely stranded | L, N: 1 screw terminal each for 0.5 ... 2.5 mm2 single-core/finely stranded | L, N: 1 screw terminal each for 0.5 ... 2.5 mm2 single-core/finely stranded | L, N: 1 screw terminal each for 0.5 ... 2.5 mm2 single-core/finely stranded |
| +, -: 2 screw terminals each for 0.5 ... 2.5 mm | +, -: 2 screw terminals each for 0.5 ... 2.5 mm | +, -: 2 screw terminals each for 0.5 ... 2.5 mm | +, -: 2 screw terminals each for 0.5 ... 2.5 mm |
| - | - | - | - |
Width of the enclosure | 18mm | 36mm | 54mm | 72mm |
Height of the enclosure | 90mm | 90mm | 90mm | 90mm |
Depth of the enclosure | 53mm | 53mm | 53mm | 53mm |
Required spacing | | | | |
| 20mm | 20mm | 20mm | 20mm |
| 20mm | 20mm | 20mm | 20mm |
| 0mm | 0mm | 0mm | 0mm |
| 0mm | 0mm | 0mm | 0mm |
Weight, approx. | 0.07kg | 0.12kg | 0.2kg | 0.29kg |
Product feature of the enclosure housing for side-by-side mounting | Yes | Yes | Yes | Yes |
Installation | Snaps onto DIN rail EN 60715 35x15, various direct mounting positions | Snaps onto DIN rail EN 60715 35x15, various direct mounting positions | Snaps onto DIN rail EN 60715 35x15, various direct mounting positions | Snaps onto DIN rail EN 60715 35x15, various direct mounting positions |
MTBF at 40 C | 4415040h | 3094996h | 2864520h | 2391480h |
Other information | Specifications at rated input voltage and ambient temperature +25 C (unless otherwise specified) | Specifications at rated input voltage and ambient temperature +25 C (unless otherwise specified) | Specifications at rated input voltage and ambient temperature +25 C (unless otherwise specified) | Specifications at rated input voltage and ambient temperature +25 C (unless otherwise specified) |