General information | |
Product type designation | CPU 1507S F |
Software version | V2.1 |
Engineering with | |
| V14 SP1 |
Configuration control | |
via dataset | Yes |
Memory | |
SIMATIC memory card required | No; Use of the PC mass storage |
Work memory | |
| 7.5 Mbyte |
| 20 Mbyte |
| 20 Mbyte |
Load memory | |
| 320 Mbyte |
Backup | |
| Yes; all memory areas declared retentive |
| Yes; Depending on PC hardware |
CPU processing times | |
for bit operations, typ. | 1 ns; on SIMATIC IPC427D, Intel Core i7 processor, 1.7 GHz |
for word operations, typ. | 2 ns; on SIMATIC IPC427D, Intel Core i7 processor, 1.7 GHz |
for fixed point arithmetic, typ. | 2 ns; on SIMATIC IPC427D, Intel Core i7 processor, 1.7 GHz |
for floating point arithmetic, typ. | 2 ns; on SIMATIC IPC427D, Intel Core i7 processor, 1.7 GHz |
CPU-blocks | |
Number of elements (total) | 6 000; In addition to blocks such as DBs, FBs and FCs, UDTs, global constants, etc. are also regarded as elements |
DB | |
| 5 999; Number range: 1 to 65535 |
| 16 Mbyte |
FB | |
| 5 998; Number range: 1 to 65535 |
| 512 kbyte |
FC | |
| 5 999; Number range: 1 to 65535 |
| 512 kbyte |
OB | |
| 512 kbyte |
| 100 |
| 20 |
| 20 |
| 20 |
| 50 |
| 3 |
| 0 |
| 2 |
| 100 |
| 4 |
| 2 |
| 1 |
Nesting depth | |
| 24; Up to 8 possible for F-blocks |
Counters, timers and their retentivity | |
S7 counter | |
| 2 048 |
Retentivity | |
| Yes |
IEC counter | |
| Any (only limited by the main memory) |
Retentivity | |
| Yes |
S7 times | |
| 2 048 |
Retentivity | |
| Yes |
IEC timer | |
| Any (only limited by the main memory) |
Retentivity | |
| Yes |
Data areas and their retentivity | |
Retentive data area (incl. timers, counters, flags), max. | 135 kbyte; On SIMATIC IPC227E, IPC277E, IPC427D, IPC477D and IPC427E, IPC477E; 35 KB on SIMATIC IPC627D, IPC677D and IPC827D |
Flag | |
| 16 kbyte |
| 8; 8 clock memory bits, grouped into one clock memory byte |
Data blocks | |
| Yes |
| No |
Local data | |
| 64 kbyte; max. 16 KB per block |
Address area | |
Number of IO modules | 8 192 |
I/O address area | |
| 32 kbyte |
| 32 kbyte |
Subprocess images | |
| 32 |
Hardware configuration | |
Number of distributed IO systems | 20 |
Number of DP masters | |
| 1 |
Number of IO Controllers | |
| 1 |
Time of day | |
Clock | |
| Software clock, synchronizable, no battery backup |
| Depending on PC hardware |
Clock synchronization | |
| Yes |
| No |
| Yes |
| Yes |
Interfaces | |
Number of interfaces | 3 |
Number of PROFINET interfaces | 2; In case of I-Device configuration, only one PROFINET interface is supported |
Number of PROFIBUS interfaces | 1 |
1. Interface | |
Interface type | Onboard PROFINET / IE interfaces of SIMATIC IPC (X2, IPC4x7E: X3), Intel Springville i210T |
Interface types | |
| 1 |
| No |
| Yes |
| 100 Mbit/s |
| Yes |
Functionality | |
| 128 |
| Yes |
| Yes |
| Yes |
| Yes |
| Yes |
PROFINET IO Controller | |
Services | |
| No |
| No |
| No |
| No |
| Yes |
| Yes; Max. 32 PROFINET devices; if you want to use the "Prioritized startup" functionality in STEP 7 for the PROFINET interface of the CPU, the CPU and the device must be separated by means of a switch (e.g. SCALANCE X205) |
| 128 |
| 8 |
| Yes; The CPU and changing IO devices must be separated by a switch (e.g. SCALANCE X205) |
| 8 |
| The minimum value of the update time also depends on communication share set for PROFINET IO, on the number of IO devices, and on the quantity of configured user data |
Update time for RT | |
| 1 ms to 512 ms |
Address area | |
| 8 kbyte |
| 8 kbyte |
PROFINET IO Device | |
Services | |
| No |
| No |
| No |
| Yes |
| Yes; If you want to use the "Prioritized startup" functionality in STEP 7 for the PROFINET interface of the CPU, the CPU and the device must be separated by means of a switch (e.g. SCALANCE X205) |
| Yes |
| 4 |
2. Interface | |
Interface type | PROFIBUS with CP 5622, CP 5622 onboard |
Interface types | |
| Yes |
Functionality | |
| 44 |
| Yes |
| No |
| Yes; no PG/STEP 7 connection possible |
DP master | |
| 64 |
Services | |
| No |
| No |
Address area | |
| 8 kbyte |
| 8 kbyte |
3. Interface | |
Interface type | PROFIBUS with CP 5623 |
Interface types | |
| Yes |
Functionality | |
| 44 |
| Yes |
| No |
| Yes; no PG/STEP 7 connection possible |
DP master | |
| 125 |
Services | |
| No |
| No |
Address area | |
| 8 kbyte |
| 8 kbyte |
Protocols | |
Number of connections | |
| 128 |
| 10 |
| 16 |
SIMATIC communication | |
| Yes |
| Yes |
| Yes |
| Yes |
| 64 kbyte; BSEND/BRCV: 64 KB; PUT/GET: 960 bytes |
Open IE communication | |
| Yes |
| 64 kbyte |
| Yes |
| 64 kbyte |
| Yes |
| 1 472 byte |
| No |
| Yes |
| Yes |
| Yes |
Web server | |
| Yes; Via Windows and PROFINET interface |
| Yes; Via Windows and PROFINET interface |
OPC UA | |
| Yes; Accessible via PROFINET interfaces; functionality: data access (read, write, subscribe), runtime license required |
| Yes; Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256 |
| Yes; Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256 |
| Yes; "anonymous" or by user name & password |
Further protocols | |
| Yes; MODBUS TCP |
S7 message functions | |
Number of login stations for message functions, max. | 32 |
Program alarms | Yes |
Number of configurable program alarms | 10 000 |
Number of simultaneously active program alarms | 1 000 |
| 1 000 |
| 200 |
| 160 |
Test commissioning functions | |
Joint commission (Team Engineering) | Yes; Parallel online access possible for up to 8 engineering systems |
Status block | Yes; up to 8 simultaneously |
Single step | No |
Status/control | |
| Yes |
| Inputs, outputs, memory bits, DB, times, counters |
| |
| 200 |
| 200 |
Forcing | |
| Yes |
| Inputs, outputs |
| 200 |
Diagnostic buffer | |
| Yes |
| 1 000 |
| 300 |
Traces | |
| 4 |
| 512 kbyte |
Interrupts/diagnostics/status information | |
Diagnostics indication LED | |
| Yes; HW LED of SIMATIC IPC227E, IPC427D/E and IPC627D/677D |
| Yes; HW LED of SIMATIC IPC227E, IPC427D/E and IPC627D/677D |
| Yes; HW LED of SIMATIC IPC227E, IPC427D/E and IPC627D/677D |
Supported technology objects | |
Motion Control | Yes; Note: The number of technology objects affects the cycle time of the PLC program; selection guide via the TIA Selection Tool or SIZER |
| 4 800 |
| |
| 40; per axis |
| 80; per axis |
| 160; per axis |
| 80; per external encoder |
| 20; per cam |
| 160; per cam track |
| 40; per probe |
| |
| 15; on SIMATIC IPC427D, Intel Core i7 processor, 1.7 GHz |
| 30; on SIMATIC IPC427D, Intel Core i7 processor, 1.7 GHz |
Controller | |
| Yes; Universal PID controller with integrated optimization |
| Yes; PID controller with integrated optimization for valves |
| Yes; PID controller with integrated optimization for temperature |
Counting and measuring | |
| Yes |
Standards, approvals, certificates | |
Highest safety class achievable in safety mode | |
Probability of failure (for service life of 20 years and repair time of 100 hours) | |
| < 2.00E-05 |
| < 1.00E-09 1/h |
Hardware requirement | |
Hardware required | SIMATIC IPC2x7E, IPC4x7D/E, IPC627D, IPC677D, IPC827D |
Processor | |
| No |
| No |
| Yes |
| Yes |
| 1; For multicore processors with activated Hyper-Threading, one complete physical core is reserved for the CPU 1507S |
Lifetime of module | |
| 4 Gbyte |
| 720 Mbyte |
| 230 Mbyte |
| 400 Mbyte |
Operating systems | |
pre-installed operating system | |
| No |
| Yes; Professional, Enterprise, Ultimate (32 bit and 64 bit); Windows installation in Legacy mode (MBR volume) required |
| Yes; With the delivery image of the SIMATIC PC |
| No |
| No |
| No |
Configuration | |
Programming | |
Programming language | |
| Yes; incl. failsafe |
| Yes; incl. failsafe |
| Yes |
| Yes |
| No |
| Yes |
Know-how protection | |
| Yes |
| Yes |
| Yes |
Access protection | |
| Yes |
| Yes |
| Yes |
Cycle time monitoring | |
| adjustable minimum cycle time |
| adjustable maximum cycle time |
Open Development interfaces | |
| 5.8 Mbyte |
Dimensions | |
Width | 18.2 cm; Packaging |
Height | 26.5 cm |
Depth | 3 cm |
Weights | |
Weight, approx. | 200 g |