Supply voltage | |
Rated value (DC) | |
| Yes |
Input current | |
Current consumption, typ. | 45 mA |
from backplane bus 5 V DC, typ. | 80 mA |
Power loss | |
Power loss, typ. | 1.5 W |
Analog outputs | |
Number of analog outputs | 4; Current or voltage |
Output ranges, voltage | |
| Yes |
Output ranges, current | |
| Yes |
Load impedance (in rated range of output) | |
| 1 000 Ω |
| 600 Ω |
Analog value generation for the outputs | |
Integration and conversion time/resolution per channel | |
| Voltage: 14 bits; Current : 13 bits |
Errors/accuracies | |
Temperature error (relative to output range), (+/-) | 25 °C ±0.3%, to 55 °C ±0.6% total measurement range |
Basic error limit (operational limit at 25 °C) | |
| 0.3 % |
| 0.3 % |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency | |
| 12 V |
Interrupts/diagnostics/status information | |
Alarms | Yes |
Diagnostic functions | Yes |
Alarms | |
| Yes |
Diagnostic messages | |
| Yes |
| Yes |
| Yes |
Diagnostics indication LED | |
| Yes |
| Yes |
Degree and class of protection | |
Degree of protection acc. to EN 60529 | |
| Yes |
Standards, approvals, certificates | |
CE mark | Yes |
Railway application | |
| Yes; EMC for rail vehicles |
| Yes; EMC for signal and telecommunications systems |
| Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC |
| Yes; Rail vehicles - see ambient conditions |
| Yes; Stationary electrical equipment - see ambient conditions |
| Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track) |
| Yes; Rail vehicles - temperature class T1, horizontal mounting position, salt spray Class ST2 |
| Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B |
| Yes; Rail vehicles - verification on request |
Ambient conditions | |
Free fall | |
| 0.3 m; five times, in product package |
Ambient temperature during operation | |
| -25 °C |
| 60 °C; = Tmax; +70 °C for 10 minutes (T1 acc. to EN 50155) for horizontal mounting position |
Ambient temperature during storage/transportation | |
| -40 °C |
| 70 °C |
Air pressure acc. to IEC 60068-2-13 | |
| 660 hPa |
| 1 080 hPa |
Altitude during operation relating to sea level | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) |
Relative humidity | |
| 95 % |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Use in stationary industrial systems | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Use on land craft, rail vehicles and special-purpose vehicles | |
| Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request |
| Yes; Class 5C3 (RH < 75%) including salt spray according to EN 50155 (ST2). The supplied plug covers must remain in place over the unused interfaces during operation! |
| Yes; Class 5S3 including sand and dust. The supplied plug covers must remain in place over the unused interfaces during operation! |
Connection method | |
required front connector | Yes |
Mechanics/material | |
Enclosure material (front) | |
| Yes |
Dimensions | |
Width | 45 mm |
Height | 100 mm |
Depth | 75 mm |
Weights | |
Weight, approx. | 180 g |
Other | |
Note: | For use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A Online Support article 109736776 |