Input | | | | |
Input | 1-phase and 2-phase AC | 1-phase and 2-phase AC | 1-phase and 2-phase AC | 1-phase and 2-phase AC |
Supply voltage | | | | |
| 120...230V | 120...230V | 120...230V | 120...230V |
| 230...500V | 230...500V | 230...500V | 230...500V |
| Set by means of selector switch on the device; starting from Vin > 90/180 V | Set by means of selector switch on the device; starting from Vin > 90/180 V | Set by means of selector switch on the device | Set by means of selector switch on the device |
Input voltage | | | | |
| 85...264V | 85...264V | 85...264V | 85...264V |
| 176...550V | 176...550V | 176...550V | 176...550V |
Wide-range input | Yes | Yes | Yes | Yes |
Overvoltage resistance | 1300 Vpeak, 1.3 ms | 1300 Vpeak, 1.3 ms | 1300 Vpeak, 1.3 ms | 1300 Vpeak, 1.3 ms |
Mains buffering at Iout rated, min. | 25ms; at Vin = 120/230 V, typ. 150 ms at Vin = 400 V | 25ms; at Vin = 120/230 V, typ. 150 ms at Vin = 400 V | 25ms; at Vin = 120/230 V, typ. 150 ms at Vin = 400 V | 25ms; at Vin = 120/230 V, typ. 150 ms at Vin = 400 V |
Rated line frequency 1 | 50Hz | 50Hz | 50Hz | 50Hz |
Rated line frequency 2 | 60Hz | 60Hz | 60Hz | 60Hz |
Rated line range | 47...63Hz | 47...63Hz | 47...63Hz | 47...63Hz |
Input current | | | | |
| 2.2A | 2.2A | 4.4A | 4.4A |
| 1.2A | 1.2A | 2.4A | 2.4A |
| 0.61A | 0.61A | 1.1A | 1.1A |
Switch-on current limiting (+25 C), max. | 35A | 35A | 35A | 35A |
It, max. | 1.7As | 1.7As | 4As | 4As |
Built-in incoming fuse | T 3.15 A (not accessible) | T 3.15 A (not accessible) | T 6.3 A (not accessible) | T 6.3 A (not accessible) |
Protection in the mains power input (IEC 898) | Recommended miniature circuit breaker at 1-phase operation: from 6 A (10 A) characteristic C (B); required at 2-phase operation: circuit breaker 2-pole connected or circuit breaker 3RV2011-1EA10 (setting 3.8 A) or 3RV2711-1ED10 (UL 489) at 230 V; 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489) at 400/500 V | Recommended miniature circuit breaker at 1-phase operation: from 6 A (10 A) characteristic C (B); required at 2-phase operation: circuit breaker 2-pole connected or circuit breaker 3RV2011-1EA10 (setting 3.8 A) or 3RV2711-1ED10 (UL 489) at 230 V; 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489) at 400/500 V | Recommended miniature circuit breaker at 1-phase operation: from 6 A (10 A) characteristic C (B); required at 2-phase operation: circuit breaker 2-pole connected or circuit breaker 3RV2011-1EA10 (setting 3.8 A) or 3RV2711-1ED10 (UL 489) at 230 V; 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489) at 400/500 V | Recommended miniature circuit breaker at 1-phase operation: from 6 A (10 A) characteristic C (B); required at 2-phase operation: circuit breaker 2-pole connected or circuit breaker 3RV2011-1EA10 (setting 3.8 A) or 3RV2711-1ED10 (UL 489) at 230 V; 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489) at 400/500 V |
Output | | | | |
Output | Controlled, isolated DC voltage | Controlled, isolated DC voltage | Controlled, isolated DC voltage | Controlled, isolated DC voltage |
Rated voltage Vout DC | 24V | 24V | 24V | 24V |
Total tolerance, static | 3% | 3% | 3% | 3% |
Static mains compensation, approx. | 0.1% | 0.1% | 0.1% | 0.1% |
Static load balancing, approx. | 0.1% | 0.1% | 0.1% | 0.1% |
Residual ripple peak-peak, max. | 50mV | 50mV | 50mV | 50mV |
Spikes peak-peak, max. (bandwidth: 20 MHz) | 200mV | 200mV | 200mV | 200mV |
Adjustment range | 24...28.8V | 24...28.8V | 24...28.8V | 24...28.8V |
Product function Output voltage adjustable | Yes | Yes | Yes | Yes |
Output voltage setting | via potentiometer | via potentiometer | via potentiometer | via potentiometer |
Status display | Green LED for 24 V OK | Green LED for 24 V OK | Green LED for 24 V OK | Green LED for 24 V OK |
Signaling | Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK" | Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK" | Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK" | Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK" |
On/off behavior | Overshoot of Vout approx. 3 % | Overshoot of Vout approx. 3 % | Overshoot of Vout approx. 3 % | Overshoot of Vout approx. 3 % |
Startup delay, max. | 1s | 1s | 1s | 1s |
Voltage rise, typ. | 50ms | 50ms | 50ms | 50ms |
Rated current value Iout rated | 5A | 5A | 10A | 10A |
Current range | 0...5A | 0...5A | 0...10A | 0...10A |
| | | +60 ... +70 C: Derating 2%/K (at 120 V, 230 V) or 3.5%/K (at 400 V) | +60 ... +70 C: Derating 2%/K (at 120 V, 230 V) or 3.5%/K (at 400 V) |
Supplied active power typical | 120W | 120W | 240W | 240W |
Short-term overload current | | | | |
| 15A | 15A | 30A | 30A |
Duration of overloading capability for excess current | | | | |
| 25ms | 25ms | 25ms | 25ms |
Constant overload current | | | | |
| 6A | 6A | 12A | 12A |
Parallel switching for enhanced performance | Yes; switchable characteristic | Yes; switchable characteristic | Yes; switchable characteristic | Yes; switchable characteristic |
Numbers of parallel switchable units for enhanced performance | 2 | 2 | 2 | 2 |
Efficiency | | | | |
Efficiency at Vout rated, Iout rated, approx. | 88% | 88% | 91% | 91% |
Power loss at Vout rated, Iout rated, approx. | 17W | 17W | 24W | 24W |
Power loss [W] during no-load operation maximum | 4W | 4W | 6W | 6W |
Closed-loop control | | | | |
Dynamic mains compensation (Vin rated 15 %), max. | 0.1% | 0.1% | 0.1% | 0.1% |
Dynamic load smoothing (Iout: 50/100/50 %), Uout typ. | 3% | 3% | 3% | 3% |
Load step setting time 50 to 100%, typ. | 2ms | 2ms | 2ms | 2ms |
Load step setting time 100 to 50%, typ. | 2ms | 2ms | 2ms | 2ms |
Setting time maximum | 5ms | 5ms | 5ms | 5ms |
Protection and monitoring | | | | |
Output overvoltage protection | < 35 V | < 35 V | < 35 V | < 35 V |
Current limitation, typ. | 6A | 6A | 12A | 12A |
Property of the output Short-circuit proof | Yes | Yes | Yes | Yes |
Short-circuit protection | Alternatively, constant current characteristic approx. 5.5 A or latching shutdown | Alternatively, constant current characteristic approx. 5.5 A or latching shutdown | Alternatively, constant current characteristic approx. 12 A or latching shutdown | Alternatively, constant current characteristic approx. 12 A or latching shutdown |
Enduring short circuit current RMS value | | | | |
| 6A | 6A | 12A | 12A |
Overload/short-circuit indicator | LED yellow for "overload", LED red for "latching shutdown" | LED yellow for "overload", LED red for "latching shutdown" | LED yellow for "overload", LED red for "latching shutdown" | LED yellow for "overload", LED red for "latching shutdown" |
Safety | | | | |
Primary/secondary isolation | Yes | Yes | Yes | Yes |
Galvanic isolation | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 |
Protection class | Class I | Class I | Class I | Class I |
Leakage current | | | | |
| 3.5mA | 3.5mA | 3.5mA | 3.5mA |
| 0.25mA | 0.25mA | 0.32mA | 0.32mA |
CE mark | Yes | Yes | Yes | Yes |
UL/cUL (CSA) approval | cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259 | cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259 | cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259 | cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259 |
Explosion protection | IECEx Ex nA nC IIC T4 Gc; ATEX (EX) II 3G Ex nA nC IIC T4 Gc (für AC 120-230/230-400 V); cCSAus (CSA C22.2 No. 213, ANSI/ISA-12.12.01) Class I, Div. 2, Group ABCD, T3 | IECEx Ex nA nC IIC T4 Gc; ATEX (EX) II 3G Ex nA nC IIC T4 Gc (für AC 120-230/230-400 V); cCSAus (CSA C22.2 No. 213, ANSI/ISA-12.12.01) Class I, Div. 2, Group ABCD, T3 | IECEx Ex nA nC IIC T4 Gc; ATEX (EX) II 3G Ex nA nC IIC T4 Gc (für AC 120-230/230-400 V); cCSAus (CSA C22.2 No. 213, ANSI/ISA-12.12.01) Class I, Div. 2, Group ABCD, T3 | IECEx Ex nA nC IIC T4 Gc; ATEX (EX) II 3G Ex nA nC IIC T4 Gc (für AC 120-230/230-400 V); cCSAus (CSA C22.2 No. 213, ANSI/ISA-12.12.01) Class I, Div. 2, Group ABCD, T3 |
CB approval | Yes | Yes | Yes | Yes |
Marine approval | GL, ABS | GL | GL, ABS | GL, ABS |
Degree of protection (EN 60529) | IP20 | IP20 | IP20 | IP20 |
EMC | | | | |
Emitted interference | EN 55022 Class B | EN 55022 Class B | EN 55022 Class B | EN 55022 Class B |
Supply harmonics limitation | EN 61000-3-2 | EN 61000-3-2 | EN 61000-3-2 | EN 61000-3-2 |
Noise immunity | EN 61000-6-2 | EN 61000-6-2 | EN 61000-6-2 | EN 61000-6-2 |
Operating data | | | | |
Ambient temperature | | | | |
| -25...+70C | -25...+70C | -25...+70C | -25...+70C |
| With natural convection; startup tested starting from -40 C nominal voltage | with natural convection | With natural convection; startup tested starting from -40 C nominal voltage | with natural convection |
| -40...+85C | -40...+85C | -40...+85C | -40...+85C |
| -40...+85C | -40...+85C | -40...+85C | -40...+85C |
Humidity class according to EN 60721 | Climate class 3K3, no condensation | Climate class 3K3, no condensation | Climate class 3K3, no condensation | Climate class 3K3, no condensation |
Mechanics | | | | |
Connection technology | screw-type terminals | screw-type terminals | screw-type terminals | screw-type terminals |
Connections | | | | |
| L, N, PE: 1 screw terminal each for 0.2 ... 2.5 mm single-core/finely stranded | L, N, PE: 1 screw terminal each for 0.2 ... 2.5 mm single-core/finely stranded | L, N, PE: 1 screw terminal each for 0.2 ... 2.5 mm single-core/finely stranded | L, N, PE: 1 screw terminal each for 0.2 ... 2.5 mm single-core/finely stranded |
| +, -: 2 screw terminals each for 0.2 ... 2.5 mm | +, -: 2 screw terminals each for 0.2 ... 2.5 mm | +, -: 2 screw terminals each for 0.2 ... 2.5 mm | +, -: 2 screw terminals each for 0.2 ... 2.5 mm |
| 13, 14 (alarm signal): 1 screw terminal each for 0.14 ... 1.5 mm | 13, 14 (alarm signal): 1 screw terminal each for 0.14 ... 1.5 mm | 13, 14 (alarm signal): 1 screw terminal each for 0.14 ... 1.5 mm | 13, 14 (alarm signal): 1 screw terminal each for 0.14 ... 1.5 mm |
Width of the enclosure | 70mm | 70mm | 70mm | 70mm |
Height of the enclosure | 125mm | 125mm | 125mm | 125mm |
Depth of the enclosure | 121mm | 121mm | 121mm | 121mm |
Required spacing | | | | |
| 50mm | 50mm | 50mm | 50mm |
| 50mm | 50mm | 50mm | 50mm |
| 0mm | 0mm | 0mm | 0mm |
| 0mm | 0mm | 0mm | 0mm |
Weight, approx. | 0.6kg | 0.6kg | 0.8kg | 0.8kg |
Product feature of the enclosure housing for side-by-side mounting | Yes | Yes | Yes | Yes |
Installation | Snaps onto DIN rail EN 60715 35x7.5/15 | Snaps onto DIN rail EN 60715 35x7.5/15 | Snaps onto DIN rail EN 60715 35x7.5/15 | Snaps onto DIN rail EN 60715 35x7.5/15 |
Electrical accessories | Buffer module | Buffer module | Buffer module | Buffer module |
MTBF at 40 C | 1123973h | 1123973h | 1055408h | 1055408h |
Other information | Specifications at rated input voltage and ambient temperature +25 C (unless otherwise specified) | Specifications at rated input voltage and ambient temperature +25 C (unless otherwise specified) | Specifications at rated input voltage and ambient temperature +25 C (unless otherwise specified) | Specifications at rated input voltage and ambient temperature +25 C (unless otherwise specified) |