General information | | | | |
Product type designation | Type A0 | Type A0 | Type A0 | Type A0 |
Supply voltage | | | | |
Rated value (DC) | 24 V | 24 V | 24 V | 24 V |
external protection for power supply lines | Yes; 24 V DC/10 A miniature circuit breaker with type B or C tripping characteristic | Yes; 24 V DC/10 A miniature circuit breaker with type B or C tripping characteristic | Yes; 24 V DC/10 A miniature circuit breaker with type B or C tripping characteristic | Yes; 24 V DC/10 A miniature circuit breaker with type B or C tripping characteristic |
Current carrying capacity | | | | |
up to 60 °C, max. | 10 A | 10 A | 10 A | 10 A |
Potential separation | | | | |
between backplane bus and supply voltage | Yes | Yes | Yes | Yes |
between the potential groups | | Yes | | Yes |
Isolation | | | | |
Isolation tested with | 707 V DC (type test) and according to EN 50155 (routine test) | 707 V DC (type test) and according to EN 50155 (routine test) | 707 V DC (type test) and according to EN 50155 (routine test) | 707 V DC (type test) and according to EN 50155 (routine test) |
Standards, approvals, certificates | | | | |
Railway application | | | | |
| Yes; EMC for rail vehicles | Yes; EMC for rail vehicles | Yes; EMC for rail vehicles | Yes; EMC for rail vehicles |
| Yes; EMC for signal and telecommunications systems | Yes; EMC for signal and telecommunications systems | Yes; EMC for signal and telecommunications systems | Yes; EMC for signal and telecommunications systems |
| Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC | Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC | Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC | Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC |
| Yes; Rail vehicles - see ambient conditions | Yes; Rail vehicles - see ambient conditions | Yes; Rail vehicles - see ambient conditions | Yes; Rail vehicles - see ambient conditions |
| Yes; Stationary electrical equipment - see ambient conditions | Yes; Stationary electrical equipment - see ambient conditions | Yes; Stationary electrical equipment - see ambient conditions | Yes; Stationary electrical equipment - see ambient conditions |
| Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track) | Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track) | Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track) | Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track) |
| Yes; Rail vehicles - temperature class Tx, horizontal mounting position, salt spray Class ST2 | Yes; Rail vehicles - temperature class Tx, horizontal mounting position, salt spray Class ST2 | Yes; Rail vehicles - temperature class Tx, horizontal mounting position, salt spray Class ST2 | Yes; Rail vehicles - temperature class Tx, horizontal mounting position, salt spray Class ST2 |
| Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B | Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B | Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B | Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B |
| Yes; Rail vehicles - verification on request | Yes; Rail vehicles - verification on request | Yes; Rail vehicles - verification on request | Yes; Rail vehicles - verification on request |
Ambient conditions | | | | |
Ambient temperature during operation | | | | |
| -40 °C; = Tmin | -40 °C; = Tmin | -40 °C; = Tmin | -40 °C; = Tmin |
| 70 °C; = Tmax; +85 °C for 10 min (Tx acc. to EN 50155) | 70 °C; = Tmax; +85 °C for 10 min (Tx acc. to EN 50155) | 70 °C; = Tmax; +85 °C for 10 min (Tx acc. to EN 50155) | 70 °C; = Tmax; +85 °C for 10 min (Tx acc. to EN 50155) |
Altitude during operation relating to sea level | | | | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) |
Relative humidity | | | | |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Use in stationary industrial systems | | | | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Use on land craft, rail vehicles and special-purpose vehicles | | | | |
| Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request | Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request | Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request | Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request |
| Yes; Class 5C3 (RH < 75%) including salt spray according to EN 50155 (ST2). The supplied plug covers must remain in place over the unused interfaces during operation! | Yes; Class 5C3 (RH < 75%) including salt spray according to EN 50155 (ST2). The supplied plug covers must remain in place over the unused interfaces during operation! | Yes; Class 5C3 (RH < 75%) including salt spray according to EN 50155 (ST2). The supplied plug covers must remain in place over the unused interfaces during operation! | Yes; Class 5C3 (RH < 75%) including salt spray according to EN 50155 (ST2). The supplied plug covers must remain in place over the unused interfaces during operation! |
| Yes; Class 5S3 including sand and dust. The supplied plug covers must remain in place over the unused interfaces during operation! | Yes; Class 5S3 including sand and dust. The supplied plug covers must remain in place over the unused interfaces during operation! | Yes; Class 5S3 including sand and dust. The supplied plug covers must remain in place over the unused interfaces during operation! | Yes; Class 5S3 including sand and dust. The supplied plug covers must remain in place over the unused interfaces during operation! |
Dimensions | | | | |
Width | 15 mm | 15 mm | 15 mm | 15 mm |
Height | 117 mm | 117 mm | 141 mm | 141 mm |
Weights | | | | |
Weight, approx. | 40 g | 40 g | 50 g | 50 g |
Other | | | | |
Note: | For use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A Online Support article 109736776 | For use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A Online Support article 109736776 | For use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A Online Support article 109736776 | For use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A Online Support article 109736776 |