Article number

6AG2214-1AG40-1XB0

SIPLUS S7-1200 CPU 1214C DC/DC/DC RAIL

General information

Product type designation

CPU 1214C DC/DC/DC

Supply voltage

Rated value (DC)

  • 24 V DC

Yes

permissible range, lower limit (DC)

20.4V

permissible range, upper limit (DC)

28.8V

Reverse polarity protection

Yes

Load voltage L+

  • Rated value (DC)

24V

  • permissible range, lower limit (DC)

20.4V

  • permissible range, upper limit (DC)

28.8V

Input current

Current consumption (rated value)

500mA; CPU only

Current consumption, max.

1500mA; CPU with all expansion modules

Inrush current, max.

12A; at 28.8 V DC

Output current

for backplane bus (5 V DC), max.

1600mA; Max. 5 V DC for SM and CM

Encoder supply

24 V encoder supply

  • 24 V

L+ minus 4 V DC min.

Power loss

Power loss, typ.

12W

Memory

Work memory

  • integrated

100kbyte

  • expandable

No

Load memory

  • integrated

4Mbyte

  • Plug-in (SIMATIC Memory Card), max.

with SIMATIC memory card

Backup

  • present

Yes; maintenance-free

  • without battery

Yes

CPU processing times

for bit operations, typ.

0.085s; / instruction

for word operations, typ.

1.7s; / instruction

for floating point arithmetic, typ.

2.3s; / instruction

CPU-blocks

Number of blocks (total)

DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used

OB

  • Number, max.

Limited only by RAM for code

Data areas and their retentivity

Retentive data area (incl. timers, counters, flags), max.

10kbyte

Flag

  • Number, max.

8kbyte; Size of bit memory address area

Local data

  • per priority class, max.

16kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB

Process image

  • Inputs, adjustable

1kbyte

  • Outputs, adjustable

1kbyte

Hardware configuration

Number of modules per system, max.

3 comm. modules, 1 signal board, 8 signal modules

Time of day

Clock

  • Hardware clock (real-time)

Yes

  • Backup time

480h; Typical

  • Deviation per day, max.

60 s/month at 25 C

Digital inputs

Number of digital inputs

14; Integrated

  • of which inputs usable for technological functions

6; HSC (High Speed Counting)

Source/sink input

Yes

Number of simultaneously controllable inputs

all mounting positions

  • up to 40 C, max.

14

Input voltage

  • Rated value (DC)

24V

  • for signal "0"

5 V DC at 1 mA

  • for signal "1"

15 V DC at 2.5 mA

Input delay (for rated value of input voltage)

for standard inputs

  • parameterizable

0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four

  • at "0" to "1", min.

0.2ms

  • at "0" to "1", max.

12.8ms

for interrupt inputs

  • parameterizable

Yes

for counter/technological functions

  • parameterizable

Single phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @ 80 kHz & 3 @ 30 kHz

Cable length

  • shielded, max.

500m; 50 m for technological functions

  • unshielded, max.

300m; For technological functions: No

Digital outputs

Number of digital outputs

10

  • of which high-speed outputs

4; 100 kHz Pulse Train Output

Limitation of inductive shutdown voltage to

L+ (-48 V)

Switching capacity of the outputs

  • with resistive load, max.

0.5A

  • on lamp load, max.

5W

Output voltage

  • for signal "0", max.

0.1V; with 10 kOhm load

  • for signal "1", min.

20 V

Output current

  • for signal "1" rated value

0.5A

  • for signal "0" residual current, max.

0.1mA

Output delay with resistive load

  • "0" to "1", max.

1s

  • "1" to "0", max.

5s

Switching frequency

  • of the pulse outputs, with resistive load, max.

100kHz

Cable length

  • shielded, max.

500m

  • unshielded, max.

150m

Analog inputs

Number of analog inputs

2

Input ranges

  • Voltage

Yes

Input ranges (rated values), voltages

  • 0 to +10 V

Yes

  • Input resistance (0 to 10 V)

≥100k ohms

Cable length

  • shielded, max.

100m; twisted and shielded

Analog outputs

Number of analog outputs

0

Analog value generation for the inputs

Integration and conversion time/resolution per channel

  • Resolution with overrange (bit including sign), max.

10bit

  • Integration time, parameterizable

Yes

  • Conversion time (per channel)

625s

Encoder

Connectable encoders

  • 2-wire sensor

Yes

1. Interface

Interface type

PROFINET

Physics

Ethernet

Isolated

Yes

automatic detection of transmission rate

Yes

Autonegotiation

Yes

Autocrossing

Yes

Functionality

  • PROFINET IO Controller

Yes

  • PROFINET IO Device

Yes

  • Open IE communication

Yes

  • Web server

Yes

PROFINET IO Controller

  • Transmission rate, max.

100Mbit/s

Services

  • Number of connectable IO Devices, max.

16

PROFINET IO Device

Services

  • Shared device

Yes

  • Number of IO Controllers with shared device, max.

2

Protocols

Supports protocol for PROFINET IO

Yes

PROFIBUS

Yes; CM 1243-5 required

AS-Interface

Yes

Protocols (Ethernet)

  • TCP/IP

Yes

Open IE communication

  • TCP/IP

Yes

  • ISO-on-TCP (RFC1006)

Yes

  • UDP

Yes

Web server

  • User-defined websites

Yes

Further protocols

  • MODBUS

Yes

Communication functions

S7 communication

  • supported

Yes

  • as server

Yes

  • as client

Yes

Web server

  • supported

Yes

Number of connections

  • overall

16; dynamically

Test commissioning functions

Status/control

  • Status/control variable

Yes

  • Variables

Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters

Forcing

  • Forcing

Yes

Diagnostic buffer

  • present

Yes

Traces

  • Number of configurable Traces

2; Up to 512 KB of data per trace are possible

Integrated Functions

Number of counters

6

Counting frequency (counter) max.

100kHz

Frequency measurement

Yes

controlled positioning

Yes

Number of position-controlled positioning axes, max.

8

Number of positioning axes via pulse-direction interface

4; With integrated DO

PID controller

Yes

Number of alarm inputs

4

Number of pulse outputs

4

Limit frequency (pulse)

100kHz

Potential separation

Potential separation digital inputs

  • Potential separation digital inputs

500V AC for 1 minute

  • between the channels, in groups of

1

Potential separation digital outputs

  • Potential separation digital outputs

Yes

  • between the channels

No

  • between the channels, in groups of

1

Isolation

Isolation tested with

According to EN 50155 (routine test)

EMC

Interference immunity against discharge of static electricity

  • Interference immunity against discharge of static electricity acc. to IEC 61000-4-2

Yes

  • Test voltage at air discharge

8kV

  • Test voltage at contact discharge

6kV

Interference immunity to cable-borne interference

  • Interference immunity on supply lines acc. to IEC 61000-4-4

Yes

  • Interference immunity on signal cables acc. to IEC 61000-4-4

Yes

Interference immunity against voltage surge

  • on the supply lines acc. to IEC 61000-4-5

Yes

Interference immunity against conducted variable disturbance induced by high-frequency fields

  • Interference immunity against high-frequency radiation acc. to IEC 61000-4-6

Yes

Emission of radio interference acc. to EN 55 011

  • Limit class A, for use in industrial areas

Yes; Group 1

  • Limit class B, for use in residential areas

Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011

Degree and class of protection

Degree of protection acc. to EN 60529

  • IP20

Yes

Standards, approvals, certificates

Railway application

  • EN 50121-3-2

Yes; EMC for rail vehicles

  • EN 50121-4

Yes; EMC for signal and telecommunications systems

  • EN 50124-1

Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC

  • EN 50125-1

Yes; Rail vehicles - see ambient conditions

  • EN 50125-2

Yes; Stationary electrical equipment - see ambient conditions

  • EN 50125-3

Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track)

  • EN 50155

Yes; Rail vehicles - temperature class T1, horizontal mounting position, salt spray Class ST2

  • EN 61373

Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B

  • Fire protection acc. to EN 45545-2

Yes; Rail vehicles - verification on request

Ambient conditions

Free fall

  • Fall height, max.

0.3m; five times, in product package

Ambient temperature during operation

  • horizontal installation, min.

-25C; = Tmin; Startup @ -25 C

  • horizontal installation, max.

60C; Number of simultaneously activated inputs or outputs: 7 or 5 (no adjacent points) at 60 C horizontal, 14 or 10 at 55 C horizontal; 70 C for 10 minutes (T1 acc. to EN 50155)

Ambient temperature during storage/transportation

  • min.

-40C

  • max.

70C

Altitude during operation relating to sea level

  • Ambient air temperature-barometric pressure-altitude

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)

Relative humidity

  • With condensation, tested in accordance with IEC 60068-2-38, max.

100%; RH incl. condensation/frost (no commissioning under condensation conditions)

Vibrations

  • Vibration resistance during operation acc. to IEC 60068-2-6

2 g (m/s) wall mounting, 1 g (m/s) DIN rail

  • Operation, tested according to IEC 60068-2-6

Yes

Shock testing

  • tested according to IEC 60068-2-27

Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms

Use in stationary industrial systems

  • to biologically active substances according to EN 60721-3-3

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

  • to chemically active substances according to EN 60721-3-3

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

  • to mechanically active substances according to EN 60721-3-3

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Use on land craft, rail vehicles and special-purpose vehicles

  • to biologically active substances according to EN 60721-3-5

Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request

  • to chemically active substances according to EN 60721-3-5

Yes; Class 5C3 (RH < 75%) including salt spray according to EN 50155 (ST2). The supplied plug covers must remain in place over the unused interfaces during operation!

  • to mechanically active substances according to EN 60721-3-5

Yes; Class 5S3 including sand and dust. The supplied plug covers must remain in place over the unused interfaces during operation!

Programming

Programming language

  • LAD

Yes

  • FBD

Yes

  • SCL

Yes

Cycle time monitoring

  • adjustable

Yes

Dimensions

Width

110mm

Height

100mm

Depth

75mm

Weights

Weight, approx.

415g

Other

Note:

For use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A Online Support article 109736776



















  © " " 2007-2022
  (4872) 700-366  skenergo@mail.ru
.