General information | | |
Product type designation | IM 155-5 PN ST | IM 155-5 PN HF |
Vendor identification (VendorID) | 0x002A | 002AH |
Device identifier (DeviceID) | 0X0312 | 0X0312 |
Product function | | |
| Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 |
Configuration control | | |
via user data | | No |
via dataset | | Yes |
Supply voltage | | |
Type of supply voltage | DC | DC |
Rated value (DC) | 24 V | 24 V |
permissible range, lower limit (DC) | 20.4 V | 20.4 V |
permissible range, upper limit (DC) | 28.8 V | 28.8 V |
Reverse polarity protection | Yes | Yes |
Short-circuit protection | Yes | Yes |
Mains buffering | | |
| 5 ms | 5 ms |
Input current | | |
Current consumption (rated value) | 0.2 A | 0.2 A |
Current consumption, max. | | 1.2 A |
Inrush current, max. | 9 A | 9 A |
IІt | 0.09 AІ·s | 0.09 AІ·s |
Power | | |
Infeed power to the backplane bus | 14 W | 14 W |
Power available from the backplane bus | 2.3 W | 2.3 W |
Power loss | | |
Power loss, typ. | 4.5 W | 4.5 W |
Address area | | |
Address space per module | | |
| 256 byte; per input / output | 256 byte; per input / output |
Address space per station | | |
| 512 byte; per input / output | 512 byte; per input / output |
Hardware configuration | | |
Integrated power supply | | Yes |
System power supply can be plugged in to left of IM | Yes | Yes |
Number of permissible power segments | 3 | 3 |
Rack | | |
| 30; I/O modules | 30; I/O modules |
Interfaces | | |
Number of PROFINET interfaces | 1 | 1 |
1. Interface | | |
Interface types | | |
| 2 | 2 |
| Yes | Yes |
| Yes | Yes |
Functionality | | |
| Yes | Yes |
| Yes | Yes; PROFINET MRP |
Interface types | | |
RJ 45 (Ethernet) | | |
| PROFINET with 100 Mbit/s full duplex (100BASE-TX) | PROFINET with 100 Mbit/s full duplex (100BASE-TX) |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
PROFINET IO Device | | |
Services | | |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
| | No |
| | Yes |
| | No |
| Yes | Yes |
| Yes | Yes |
| 2 | 4 |
Open IE communication | | |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
Isochronous mode | | |
Isochronous operation (application synchronized up to terminal) | Yes | Yes |
Equidistance | Yes | Yes |
shortest clock pulse | 250 µs | 250 µs |
max. cycle | 4 ms | 4 ms |
Interrupts/diagnostics/status information | | |
Status indicator | Yes | Yes |
Alarms | Yes | Yes |
Diagnostic functions | Yes | Yes |
Diagnostics indication LED | | |
| Yes; Green LED | Yes; Green LED |
| Yes; Red LED | Yes; Red LED |
| Yes; yellow LED | Yes; yellow LED |
| Yes; yellow LED | Yes; yellow LED |
Potential separation | | |
between backplane bus and electronics | No | No |
between PROFINET and all other circuits | Yes | Yes |
between supply and all other circuits | No | No |
Isolation | | |
Isolation tested with | 707 V DC (type test) and according to EN 50155 (routine test) | 707 V DC (type test) and according to EN 50155 (routine test) |
Standards, approvals, certificates | | |
Railway application | | |
| Yes; EMC for rail vehicles | Yes; EMC for rail vehicles |
| Yes; EMC for signal and telecommunications systems | Yes; EMC for signal and telecommunications systems |
| Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC | Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC |
| Yes; Rail vehicles - see ambient conditions | Yes; Rail vehicles - see ambient conditions |
| Yes; Stationary electrical equipment - see ambient conditions | Yes; Stationary electrical equipment - see ambient conditions |
| Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track) | Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track) |
| Yes; Rail vehicles - temperature class Tx, horizontal mounting position, salt spray Class ST2 | Yes; Rail vehicles - temperature class T1, horizontal mounting position, salt spray Class ST2 |
| Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B | Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B |
| Yes; Rail vehicles - verification on request | Yes; Rail vehicles - verification on request |
Ambient conditions | | |
Ambient temperature during operation | | |
| -40 °C; = Tmin | -40 °C; = Tmin; Startup @ -25 °C |
| 70 °C; = Tmax; from > +60 °C no module permissible left of the IM; +85 °C for 10 min. (Tx acc. to EN 50155) | 60 °C; = Tmax; +70 °C for 10 min (T1 acc. to EN 50155) |
Altitude during operation relating to sea level | | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) |
Relative humidity | | |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Use in stationary industrial systems | | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Use on land craft, rail vehicles and special-purpose vehicles | | |
| Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request | Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request |
| Yes; Class 5C3 (RH < 75%) including salt spray according to EN 50155 (ST2). The supplied plug covers must remain in place over the unused interfaces during operation! | Yes; Class 5C3 (RH < 75%) including salt spray according to EN 50155 (ST2). The supplied plug covers must remain in place over the unused interfaces during operation! |
| Yes; Class 5S3 including sand and dust. The supplied plug covers must remain in place over the unused interfaces during operation! | Yes; Class 5S3 including sand and dust. The supplied plug covers must remain in place over the unused interfaces during operation! |
Connection method | | |
ET-Connection | | |
| | No |
Dimensions | | |
Width | 35 mm | 35 mm |
Height | 147 mm | 147 mm |
Depth | 129 mm | 129 mm |
Weights | | |
Weight, approx. | 310 g | 350 g |
Other | | |
Note: | For use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A Online Support article 109736776 | For use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A Online Support article 109736776 |