General information | |
Product type designation | KP300 Basic mono PN |
Display | |
Design of display | FSTN |
Screen diagonal | 3.6 in |
Display width | 87 mm |
Display height | 31 mm |
Number of colors | 4; Backlit display only (white, red, green, yellow) |
Resolution (pixels) | |
| 240 Pixel |
| 80 Pixel |
Backlighting | |
| 50 000 h |
| No |
Keyboard fonts | |
| |
| 10 |
| No |
| Yes |
| Yes; Keyboard |
| Yes; Keyboard |
Touch operation | |
| No |
Installation type/mounting | |
Mounting position | vertical |
Mounting in portrait format possible | No |
Mounting in landscape format possible | Yes |
maximum permissible angle of inclination without external ventilation | 35° |
Supply voltage | |
Type of supply voltage | DC |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 19.2 V |
permissible range, upper limit (DC) | 28.8 V |
Input current | |
Current consumption (rated value) | 0.1 A |
Starting current inrush IІt | 0.5 AІ·s |
Power | |
Active power input, typ. | 3 W |
Memory | |
Flash | Yes |
RAM | Yes |
Memory available for user data | 1 Mbyte |
Type of output | |
Acoustics | |
| No |
| No |
Time of day | |
Clock | |
| No |
| Yes |
| No |
| Yes |
Interfaces | |
Number of industrial Ethernet interfaces | 1 |
Number of RS 485 interfaces | 0 |
Number of RS 422 interfaces | 0 |
Number of RS 232 interfaces | 0 |
Number of USB interfaces | 0 |
Number of 20 mA interfaces (TTY) | 0 |
Number of parallel interfaces | 0 |
Number of other interfaces | 0 |
Number of SD card slots | 0 |
With software interfaces | No |
Industrial Ethernet | |
| 2 |
Protocols | |
PROFINET | Yes |
Supports protocol for PROFINET IO | No |
IRT | No |
PROFIBUS | No |
MPI | No |
Protocols (Ethernet) | |
| Yes |
| Yes |
| Yes |
| Yes |
| Yes |
WEB characteristics | |
| No |
| No |
Further protocols | |
| No |
| Yes |
| Yes; Modicon (MODBUS TCP/IP) |
Interrupts/diagnostics/status information | |
Diagnostic messages | |
| No |
Isolation | |
Isolation tested with | 707 V DC (type test) and according to EN 50155 (routine test) |
Degree and class of protection | |
IP (at the front) | IP65 |
Enclosure Type 4 at the front | Yes |
Enclosure Type 4x at the front | Yes |
IP (rear) | IP20 |
Standards, approvals, certificates | |
Railway application | |
| Yes; EMC for rail vehicles |
| Yes; EMC for signal and telecommunications systems |
| Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC |
| Yes; Rail vehicles - see ambient conditions |
| Yes; Stationary electrical equipment - see ambient conditions |
| Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track) |
| Yes; Rail vehicles - temperature class T1, horizontal mounting position, salt spray Class ST2 |
| Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B |
| Yes; Rail vehicles - verification on request |
Ambient temperature during storage/transportation | |
| -20 °C |
| 60 °C |
Altitude during operation relating to sea level | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) |
Relative humidity | |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Use in stationary industrial systems | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Use on land craft, rail vehicles and special-purpose vehicles | |
| Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request |
| Yes; Class 5C3 (RH < 75%) including salt spray according to EN 50155 (ST2). The supplied plug covers must remain in place over the unused interfaces during operation! |
| Yes; Class 5S3 including sand and dust. The supplied plug covers must remain in place over the unused interfaces during operation! |
Operating systems | |
proprietary | Yes |
pre-installed operating system | |
| No |
Configuration | |
Message indicator | Yes |
Alarm system (incl. buffer and acknowledgment) | Yes |
Process value display (output) | Yes |
Process value default (input) possible | Yes |
Recipe management | Yes |
Configuration software | |
| Yes; via integrated WinCC Basic (TIA Portal) |
| Yes; via integrated WinCC Basic (TIA Portal) |
| No |
| No |
| No |
| Yes |
| Yes |
| Yes |
| Yes |
Languages | |
Online languages | |
| 5 |
Project languages | |
| 32 |
Functionality under WinCC (TIA Portal) | |
Libraries | Yes |
Task planner | |
| No |
| Yes |
Help system | Yes |
| 320 |
Message system | |
| 32 |
| |
| 200 |
| |
| 15 |
| Yes |
| 80 |
| 8 |
| Yes |
| |
| 256 |
| Yes |
| Yes |
| Yes |
Recipe management | |
| 5 |
| 20 |
| 20 |
| 40 kbyte |
| No |
Variables | |
| 250 |
| 30 |
| Yes |
| Yes |
| No |
| Yes |
Images | |
| 50 |
| Yes |
| Yes |
| Yes |
| Yes |
Image objects | |
| 30 |
| Yes |
| Yes |
| Yes |
| Yes |
| Yes |
| Yes |
| Yes |
| Yes |
| Yes |
| Yes |
Complex image objects | |
| 5 |
| Yes |
| Yes |
| Yes |
| No |
| No |
| Yes |
| No |
| No |
| No |
| Yes |
| No |
| No |
| No |
Lists | |
| 150 |
| 30 |
| 100 |
| 30 |
Archiving | |
| 0 |
Security | |
| 50 |
| 32 |
| 50 |
| No |
| No |
Character sets | |
| |
| Yes |
Transfer (upload/download) | |
| No |
| No |
| Yes |
| No |
Process coupling | |
| Yes |
| Yes |
| Yes |
| Yes |
| Yes |
| Yes |
| No |
| No |
| Yes |
| No |
| Yes |
| No |
| No |
| No |
| Yes |
| No |
Service tools/configuration aids | |
| Yes |
| No |
| Yes |
| Yes |
Peripherals/Options | |
Peripherals | |
| No |
| No |
| No |
| No |
Mechanics/material | |
Enclosure material (front) | |
| Yes |
| No |
| No |
Dimensions | |
Width of the housing front | 165 mm |
Height of housing front | 97 mm |
Mounting cutout, width | 149 mm |
Mounting cutout, height | 82 mm |
Overall depth | 30 mm |
Weights | |
Weight without packaging | 0.25 kg |
Weight incl. packaging | 0.38 kg |
Other | |
Note: | For use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A Online Support article 109736776 |