Article number

6AG2511-1AK01-1AB0

6AG2511-1AK01-4AB0

SIPLUS S7-1500 CPU 1511-1 PN T1 RAIL

SIPLUS S7-1500 CPU 1511-1 PN TX RAIL

General information

 

 

Product type designation

CPU 1511-1 PN

CPU 1511-1 PN

Configuration control

 

 

via dataset

Yes

Yes

Supply voltage

 

 

Type of supply voltage

24 V DC

24 V DC

permissible range, lower limit (DC)

19.2 V

19.2 V

permissible range, upper limit (DC)

28.8 V

28.8 V

Reverse polarity protection

Yes

Yes

Mains buffering

 

 

  • в—Џ Mains/voltage failure stored energy time

5 ms

5 ms

Input current

 

 

Current consumption (rated value)

0.7 A

0.7 A

Inrush current, max.

1.9 A; Rated value

1.9 A; Rated value

IІt

0.02 AІ·s

0.02 AІ·s

Power

 

 

Infeed power to the backplane bus

10 W

10 W

Power consumption from the backplane bus (balanced)

5.5 W

5.5 W

Power loss

 

 

Power loss, typ.

5.7 W

5.7 W

Memory

 

 

Number of slots for SIMATIC memory card

1

1

SIMATIC memory card required

Yes

Yes

Work memory

 

 

  • в—Џ integrated (for program)

150 kbyte

150 kbyte

  • в—Џ integrated (for data)

1 Mbyte

1 Mbyte

Load memory

 

 

  • в—Џ Plug-in (SIMATIC Memory Card), max.

32 Gbyte

32 Gbyte

Backup

 

 

  • в—Џ maintenance-free

Yes

Yes

CPU processing times

 

 

for bit operations, typ.

60 ns

60 ns

for word operations, typ.

72 ns

72 ns

for fixed point arithmetic, typ.

96 ns

96 ns

for floating point arithmetic, typ.

384 ns

384 ns

CPU-blocks

 

 

Number of elements (total)

2 000; In addition to blocks such as DBs, FBs and FCs, UDTs, global constants, etc. are also regarded as elements

2 000; Blocks (OB, FB, FC, DB) and UDTs

DB

 

 

  • в—Џ Number range

1 ... 60 999; subdivided into: number range that can be used by the user: 1 ... 59 999, and number range of DBs created via SFC 86: 60 000 ... 60 999

1 ... 60 999; subdivided into: number range that can be used by the user: 1 ... 59 999, and number range of DBs created via SFC 86: 60 000 ... 60 999

  • в—Џ Size, max.

1 Mbyte; For non-optimized block accesses, the max. size of the DB is 64 KB

1 Mbyte; For non-optimized block accesses, the max. size of the DB is 64 KB

FB

 

 

  • в—Џ Number range

0 ... 65 535

0 ... 65 535

  • в—Џ Size, max.

150 kbyte

150 kbyte

FC

 

 

  • в—Џ Number range

0 ... 65 535

0 ... 65 535

  • в—Џ Size, max.

150 kbyte

150 kbyte

OB

 

 

  • в—Џ Size, max.

150 kbyte

150 kbyte

  • в—Џ Number of free cycle OBs

100

100

  • в—Џ Number of time alarm OBs

20

20

  • в—Џ Number of delay alarm OBs

20

20

  • в—Џ Number of cyclic interrupt OBs

20

20

  • в—Џ Number of process alarm OBs

50

50

  • в—Џ Number of DPV1 alarm OBs

3

3

  • в—Џ Number of isochronous mode OBs

1

1

  • в—Џ Number of technology synchronous alarm OBs

2

2

  • в—Џ Number of startup OBs

100

100

  • в—Џ Number of asynchronous error OBs

4

4

  • в—Џ Number of synchronous error OBs

2

2

  • в—Џ Number of diagnostic alarm OBs

1

1

Nesting depth

 

 

  • в—Џ per priority class

24

24

Counters, timers and their retentivity

 

 

S7 counter

 

 

  • в—Џ Number

2 048

2 048

Retentivity

 

 

  • — adjustable

Yes

Yes

IEC counter

 

 

  • в—Џ Number

Any (only limited by the main memory)

Any (only limited by the main memory)

Retentivity

 

 

  • — adjustable

Yes

Yes

S7 times

 

 

  • в—Џ Number

2 048

2 048

Retentivity

 

 

  • — adjustable

Yes

Yes

IEC timer

 

 

  • в—Џ Number

Any (only limited by the main memory)

Any (only limited by the main memory)

Retentivity

 

 

  • — adjustable

Yes

Yes

Data areas and their retentivity

 

 

Retentive data area (incl. timers, counters, flags), max.

128 kbyte; In total; available retentive memory for bit memories, timers, counters, DBs, and technology data (axes): 88 KB

128 kbyte; In total; available retentive memory for bit memories, timers, counters, DBs, and technology data (axes): 88 KB

Flag

 

 

  • в—Џ Number, max.

16 kbyte

16 kbyte

  • в—Џ Number of clock memories

8; 8 clock memory bits, grouped into one clock memory byte

8; 8 clock memory bits, grouped into one clock memory byte

Data blocks

 

 

  • в—Џ Retentivity adjustable

Yes

Yes

  • в—Џ Retentivity preset

No

No

Local data

 

 

  • в—Џ per priority class, max.

64 kbyte; max. 16 KB per block

64 kbyte; max. 16 KB per block

Address area

 

 

Number of IO modules

1 024; max. number of modules / submodules

1 024; max. number of modules / submodules

I/O address area

 

 

  • в—Џ Inputs

32 kbyte; All inputs are in the process image

32 kbyte; All inputs are in the process image

  • в—Џ Outputs

32 kbyte; All outputs are in the process image

32 kbyte; All outputs are in the process image

per integrated IO subsystem

 

 

  • — Inputs (volume)

8 kbyte

8 kbyte

  • — Outputs (volume)

8 kbyte

8 kbyte

per CM/CP

 

 

  • — Inputs (volume)

8 kbyte

8 kbyte

  • — Outputs (volume)

8 kbyte

8 kbyte

Subprocess images

 

 

  • в—Џ Number of subprocess images, max.

32

32

Hardware configuration

 

 

Number of distributed IO systems

32; A distributed I/O system is characterized not only by the integration of distributed I/O via PROFINET or PROFIBUS communication modules, but also by the connection of I/O via AS-i master modules or links (e.g. IE/PB-Link)

20

Number of DP masters

 

 

  • в—Џ Via CM

4; A maximum of 4 CMs/CPs (PROFIBUS, PROFINET, Ethernet) can be inserted in total

4; A maximum of 4 CMs/CPs (PROFIBUS, PROFINET, Ethernet) can be inserted in total

Number of IO Controllers

 

 

  • в—Џ integrated

1

1

  • в—Џ Via CM

4; A maximum of 4 CMs/CPs (PROFIBUS, PROFINET, Ethernet) can be inserted in total

4; A maximum of 4 CMs/CPs (PROFIBUS, PROFINET, Ethernet) can be inserted in total

Rack

 

 

  • в—Џ Modules per rack, max.

32; CPU + 31 modules

32; CPU + 31 modules

  • в—Џ Number of lines, max.

1

1

PtP CM

 

 

  • в—Џ Number of PtP CMs

the number of connectable PtP CMs is only limited by the number of available slots

the number of connectable PtP CMs is only limited by the number of available slots

Time of day

 

 

Clock

 

 

  • в—Џ Type

Hardware clock

Hardware clock

  • в—Џ Backup time

6 wk; At 40 °C ambient temperature, typically

6 wk; At 40 °C ambient temperature, typically

  • в—Џ Deviation per day, max.

10 s; Typ.: 2 s

10 s; Typ.: 2 s

Operating hours counter

 

 

  • в—Џ Number

16

16

Clock synchronization

 

 

  • в—Џ supported

Yes

Yes

  • в—Џ in AS, master

Yes

Yes

  • в—Џ in AS, slave

Yes

Yes

  • в—Џ on Ethernet via NTP

Yes

Yes

Interfaces

 

 

Number of PROFINET interfaces

1

1

1. Interface

 

 

Interface types

 

 

  • в—Џ Number of ports

2

2

  • в—Џ integrated switch

Yes

Yes

  • в—Џ RJ 45 (Ethernet)

Yes; X1

Yes; X1

Functionality

 

 

  • в—Џ PROFINET IO Controller

Yes

Yes

  • в—Џ PROFINET IO Device

Yes

Yes

  • в—Џ SIMATIC communication

Yes

Yes

  • в—Џ Open IE communication

Yes

Yes

  • в—Џ Web server

Yes

Yes

  • в—Џ Media redundancy

Yes

Yes

Interface types

 

 

RJ 45 (Ethernet)

 

 

  • в—Џ 100 Mbps

Yes

Yes

  • в—Џ Autonegotiation

Yes

Yes

  • в—Џ Autocrossing

Yes

Yes

  • в—Џ Industrial Ethernet status LED

Yes

Yes

Protocols

 

 

Number of connections

 

 

  • в—Џ Number of connections, max.

96; via integrated interfaces of the CPU and connected CPs / CMs

96; via integrated interfaces of the CPU and connected CPs / CMs

  • в—Џ Number of connections reserved for ES/HMI/web

10

10

  • в—Џ Number of connections via integrated interfaces

64

64

  • в—Џ Number of S7 routing paths

16

16

PROFINET IO Controller

 

 

Services

 

 

  • — PG/OP communication

Yes

Yes

  • — S7 routing

Yes

Yes

  • — Isochronous mode

Yes

Yes

  • — Open IE communication

Yes

Yes

  • — IRT

Yes

Yes

  • — MRP

Yes; As MRP redundancy manager and/or MRP client; max. number of devices in the ring: 50

Yes; As MRP redundancy manager and/or MRP client; max. number of devices in the ring: 50

  • — MRPD

Yes; Requirement: IRT

  • — PROFIenergy

Yes

Yes

  • — Prioritized startup

Yes; Max. 32 PROFINET devices

Yes; Max. 32 PROFINET devices

  • — Number of connectable IO Devices, max.

128; In total, up to 256 distributed I/O devices can be connected via AS-i, PROFIBUS or PROFINET

128; In total, up to 256 distributed I/O devices can be connected via PROFIBUS or PROFINET

  • — Of which IO devices with IRT, max.

64

64

  • — Number of connectable IO Devices for RT, max.

128

128

  • — of which in line, max.

128

128

  • — Number of IO Devices that can be simultaneously activated/deactivated, max.

8; in total across all interfaces

8

  • — Number of IO Devices per tool, max.

8

8

  • — Updating times

The minimum value of the update time also depends on communication share set for PROFINET IO, on the number of IO devices, and on the quantity of configured user data

The minimum value of the update time also depends on communication share set for PROFINET IO, on the number of IO devices, and on the quantity of configured user data

Update time for IRT

 

 

  • — for send cycle of 250 µs

250 Ојs to 4 ms; Note: In the case of IRT with isochronous mode, the minimum update time of 625 µs of the isochronous OB is decisive

250 Ојs to 4 ms; Note: In the case of IRT with isochronous mode, the minimum update time of 625 µs of the isochronous OB is decisive

  • — for send cycle of 500 µs

500 Ојs to 8 ms; Note: In the case of IRT with isochronous mode, the minimum update time of 625 µs of the isochronous OB is decisive

500 Ојs to 8 ms; Note: In the case of IRT with isochronous mode, the minimum update time of 625 µs of the isochronous OB is decisive

  • — for send cycle of 1 ms

1 ms to 16 ms

1 ms to 16 ms

  • — for send cycle of 2 ms

2 ms to 32 ms

2 ms to 32 ms

  • — for send cycle of 4 ms

4 ms to 64 ms

4 ms to 64 ms

  • — With IRT and parameterization of "odd" send cycles

Update time = set "odd" send clock (any multiple of 125 µs: 375 µs, 625 µs ... 3 875 µs)

Update time = set "odd" send clock (any multiple of 125 µs: 375 µs, 625 µs ... 3 875 µs)

Update time for RT

 

 

  • — for send cycle of 250 µs

250 µs to 128 ms

250 µs to 128 ms

  • — for send cycle of 500 µs

500 µs to 256 ms

500 µs to 256 ms

  • — for send cycle of 1 ms

1 ms to 512 ms

1 ms to 512 ms

  • — for send cycle of 2 ms

2 ms to 512 ms

2 ms to 512 ms

  • — for send cycle of 4 ms

4 ms to 512 ms

4 ms to 512 ms

PROFINET IO Device

 

 

Services

 

 

  • — PG/OP communication

Yes

Yes

  • — S7 routing

Yes

Yes

  • — Isochronous mode

No

No

  • — Open IE communication

Yes

Yes

  • — IRT

Yes

Yes

  • — MRP

Yes

Yes

  • — MRPD

Yes

  • — PROFIenergy

Yes

Yes

  • — Shared device

Yes

Yes

  • — Number of IO Controllers with shared device, max.

4

4

SIMATIC communication

 

 

  • в—Џ S7 communication, as server

Yes

Yes

  • в—Џ S7 communication, as client

Yes

Yes

  • в—Џ User data per job, max.

See online help (S7 communication, user data size)

See online help (S7 communication, user data size)

Open IE communication

 

 

  • в—Џ TCP/IP

Yes

Yes

  • — Data length, max.

64 kbyte

64 kbyte

  • — several passive connections per port, supported

Yes

Yes

  • в—Џ ISO-on-TCP (RFC1006)

Yes

Yes

  • — Data length, max.

64 kbyte

64 kbyte

  • в—Џ UDP

Yes

Yes

  • — Data length, max.

1 472 byte

1 472 byte

  • в—Џ DHCP

No

No

  • в—Џ SNMP

Yes

Yes

  • в—Џ DCP

Yes

Yes

  • в—Џ LLDP

Yes

Yes

Web server

 

 

  • в—Џ HTTP

Yes; Standard and user-defined pages

Yes; Standard and user-defined pages

  • в—Џ HTTPS

Yes; Standard and user-defined pages

Yes; Standard and user-defined pages

OPC UA

 

 

  • в—Џ OPC UA Client

No

  • в—Џ OPC UA Server

Yes; for data access

Further protocols

 

 

  • в—Џ MODBUS

Yes; MODBUS TCP

Yes; MODBUS TCP

Media redundancy

 

 

  • в—Џ Switchover time on line break, typ.

200 ms; For MRP, bumpless for MRPD

200 ms

  • в—Џ Number of stations in the ring, max.

50

50

Isochronous mode

 

 

Isochronous operation (application synchronized up to terminal)

Yes; With minimum OB 6x cycle of 625 µs

Yes; With minimum OB 6x cycle of 625 µs

Equidistance

Yes

Yes

S7 message functions

 

 

Number of login stations for message functions, max.

32

32

Program alarms

Yes

Yes

Number of configurable program alarms

5 000

5 000

Number of simultaneously active program alarms

  • в—Џ Number of program alarms

300

300

  • в—Џ Number of alarms for system diagnostics

100

100

  • в—Џ Number of alarms for motion technology objects

80

80

Test commissioning functions

 

 

Joint commission (Team Engineering)

Yes; Parallel online access possible for up to 5 engineering systems

Yes; Parallel online access possible for up to 5 engineering systems

Status block

Yes; Up to 8 simultaneously (in total across all ES clients)

Yes; Up to 8 simultaneously (in total across all ES clients)

Single step

No

No

Status/control

 

 

  • в—Џ Status/control variable

Yes

Yes

  • в—Џ Variables

Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters

Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters

  • в—Џ Number of variables, max.

  • — of which status variables, max.

200; per job

200; per job

  • — of which control variables, max.

200; per job

200; per job

Forcing

 

 

  • в—Џ Forcing, variables

Peripheral inputs/outputs

Peripheral inputs/outputs

  • в—Џ Number of variables, max.

200

200

Diagnostic buffer

 

 

  • в—Џ present

Yes

Yes

  • в—Џ Number of entries, max.

1 000

1 000

  • — of which powerfail-proof

500

500

Traces

 

 

  • в—Џ Number of configurable Traces

4; Up to 512 KB of data per trace are possible

4; Up to 512 KB of data per trace are possible

Interrupts/diagnostics/status information

 

 

Diagnostics indication LED

 

 

  • в—Џ RUN/STOP LED

Yes

Yes

  • в—Џ ERROR LED

Yes

Yes

  • в—Џ MAINT LED

Yes

Yes

  • в—Џ Connection display LINK TX/RX

Yes

Yes

Supported technology objects

 

 

Motion Control

Yes; Note: The number of axes affects the cycle time of the PLC program; selection guide via the TIA Selection Tool or SIZER

Yes

  • в—Џ Number of available Motion Control resources for technology objects (except cam disks)

1 600

  • в—Џ Required Motion Control resources

  • — per speed-controlled axis

80; per axis

  • — per positioning axis

160; per axis

  • — per synchronous axis

160; per axis

  • — per external encoder

80; per external encoder

  • — per output cam

20; per cam

  • — per cam track

160; per cam track

  • — per probe

40; per probe

  • в—Џ Speed-controlled axis

  • — Number of speed-controlled axes, max.

6; Requirement: There must be no other motion technology objects created; note: The number of axes affects the cycle time of the PLC program; selection guide via the TIA Selection Tool

  • в—Џ Positioning axis

  • — Number of positioning axes, max.

6; Requirement: There must be no other motion technology objects created; note: The number of axes affects the cycle time of the PLC program; selection guide via the TIA Selection Tool

  • — Number of positioning axes at motion control cycle of 4 ms (typical value)

3

  • — Number of positioning axes at motion control cycle of 8 ms (typical value)

8

  • в—Џ Synchronized axes (relative gear synchronization)

  • — Number of axes, max.

3; Requirement: There must be no other motion technology objects created; note: The number of axes affects the cycle time of the PLC program; selection guide via the TIA Selection Tool

  • в—Џ External encoders

  • — Number of external encoders, max.

6; Requirement: There must be no other motion technology objects created; note: The number of axes affects the cycle time of the PLC program; selection guide via the TIA Selection Tool

Controller

  • в—Џ PID_Compact

Yes; Universal PID controller with integrated optimization

Yes; Universal PID controller with integrated optimization

  • в—Џ PID_3Step

Yes; PID controller with integrated optimization for valves

Yes; PID controller with integrated optimization for valves

  • в—Џ PID-Temp

Yes; PID controller with integrated optimization for temperature

Yes; PID controller with integrated optimization for temperature

Counting and measuring

  • в—Џ High-speed counter

Yes

Yes

Isolation

 

 

Isolation tested with

707 V DC (type test) and according to EN 50155 (routine test)

707 V DC (type test) and according to EN 50155 (routine test)

Standards, approvals, certificates

 

 

Railway application

 

 

  • в—Џ EN 50121-3-2

Yes; EMC for rail vehicles

Yes; EMC for rail vehicles

  • в—Џ EN 50121-4

Yes; EMC for signal and telecommunications systems

Yes; EMC for signal and telecommunications systems

  • в—Џ EN 50124-1

Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC

Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC

  • в—Џ EN 50125-1

Yes; Rail vehicles - see ambient conditions

Yes; Rail vehicles - see ambient conditions

  • в—Џ EN 50125-2

Yes; Stationary electrical equipment - see ambient conditions

Yes; Stationary electrical equipment - see ambient conditions

  • в—Џ EN 50125-3

Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track)

Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track)

  • в—Џ EN 50155

Yes; Rail vehicles - temperature class T1, horizontal mounting position, salt spray Class ST2

Yes; Rail vehicles - temperature class Tx, horizontal mounting position, salt spray Class ST2

  • в—Џ EN 61373

Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B

Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B

  • в—Џ Fire protection acc. to EN 45545-2

Yes; Rail vehicles - verification on request

Yes; Rail vehicles - verification on request

Ambient conditions

 

 

Ambient temperature during operation

 

 

  • в—Џ horizontal installation, min.

-40 °C; = Tmin

-40 °C; = Tmin

  • в—Џ horizontal installation, max.

60 °C; = Tmax; +70 °C for 10 min (T1 acc. to EN 50155)

70 °C; = Tmax; +85 °C for 10 min (Tx acc. to EN 50155)

Ambient temperature during storage/transportation

 

 

  • в—Џ min.

-40 °C

-40 °C

  • в—Џ max.

70 °C

70 °C

Altitude during operation relating to sea level

 

 

  • в—Џ Ambient air temperature-barometric pressure-altitude

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)

Relative humidity

 

 

  • в—Џ With condensation, tested in accordance with IEC 60068-2-38, max.

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

Use in stationary industrial systems

 

 

  • — to biologically active substances according to EN 60721-3-3

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

  • — to chemically active substances according to EN 60721-3-3

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

  • — to mechanically active substances according to EN 60721-3-3

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Use on land craft, rail vehicles and special-purpose vehicles

 

 

  • — to biologically active substances according to EN 60721-3-5

Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request

Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request

  • — to chemically active substances according to EN 60721-3-5

Yes; Class 5C3 (RH < 75%) including salt spray according to EN 50155 (ST2). The supplied plug covers must remain in place over the unused interfaces during operation!

Yes; Class 5C3 (RH < 75%) including salt spray according to EN 50155 (ST2). The supplied plug covers must remain in place over the unused interfaces during operation!

  • — to mechanically active substances according to EN 60721-3-5

Yes; Class 5S3 including sand and dust. The supplied plug covers must remain in place over the unused interfaces during operation!

Yes; Class 5S3 including sand and dust. The supplied plug covers must remain in place over the unused interfaces during operation!

Configuration

 

 

Programming

 

 

Programming language

 

 

  • — LAD

Yes

Yes

  • — FBD

Yes

Yes

  • — STL

Yes

Yes

  • — SCL

Yes

Yes

  • — GRAPH

Yes

Yes

Know-how protection

 

 

  • в—Џ User program protection/password protection

Yes

Yes

  • в—Џ Copy protection

Yes

Yes

  • в—Џ Block protection

Yes

Yes

Access protection

 

 

  • в—Џ Password for display

Yes

Yes

  • в—Џ Protection level: Write protection

Yes

Yes

  • в—Џ Protection level: Read/write protection

Yes

Yes

  • в—Џ Protection level: Complete protection

Yes

Yes

Cycle time monitoring

 

 

  • в—Џ lower limit

adjustable minimum cycle time

adjustable minimum cycle time

  • в—Џ upper limit

adjustable maximum cycle time

adjustable maximum cycle time

Dimensions

 

 

Width

35 mm

35 mm

Height

147 mm

147 mm

Depth

129 mm

129 mm

Weights

 

 

Weight, approx.

430 g

430 g

Other

 

 

Note:

For use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A Online Support article 109736776

For use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A Online Support article 109736776


















skener.ru

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Арматура DENDOR

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Датчики и измерители

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Регуляторы и регистраторы

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Пневматическое оборудование

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Краны и Клапаны

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Измерительные приборы

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Системы беспроводного управления «умный дом»

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Бесконтактные выключатели Конечные выключатели Оптические датчики Энкодеры

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Установка умягчения

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Установка обезжелезивания

  © ООО "СК ЭНЕРГО" 2007-2022
  (4872) 700-366  skenergo@mail.ru
Яндекс.Метрика