Siemens
01 2018
(4872) 700-366
skenergo@mail.ru
 01 2017  

Article number

6BK1943-2AA00-0AA0

6BK1943-2AA00-0AA2

6BK1943-2BA00-0AA0

6BK1943-2BA00-0AA2

6BK1943-2CA00-0AA0

6BK1943-2CA00-0AA2

6BK1943-2DA00-0AA0

6BK1943-2DA00-0AA2

HCS POM4320 BUSBAR MOUNTING (IEC)

HCS POM4320 busbar mounting (IEC)

HCS POM4320 BUSBAR MOUNTING (UL)

HCS POM4320 busbar mounting (UL)

HCS POM4320 PANEL MOUNTING (IEC)

HCS POM4320 panel mounting (IEC)

HCS POM4320 PANEL MOUNTING (UL)

HCS POM4320 panel mounting (UL)

General information

Product brand name

SIPLUS

Type of control of heat emitters

Half-wave control and soft start

Installation type/mounting

Mounting type

Busbar mounting

Backplane mounting

Mounting position

vertical

Type of ventilation

Self-ventilation

Supply voltage

Type of supply voltage

AC

Rated value (AC)

400V

Relative negative tolerance

10%

Relative positive tolerance

30%

Line frequency

  • Rated value 1

50Hz

  • Rated value 2

60Hz

  • Relative symmetrical tolerance

5%

Mains buffering

  • Recovery time after power failure, typ.

1s

Resistance thermometer (RTD)

  • Design of electrical connection for supply voltage

Busbar adapter, 3-pole + PE

Terminal, 3-pin

  • Connectable conductor cross-sections, solid

1x (1.5 ... 50 mm)

  • Connectable conductor cross-sections, finely stranded with wire end processing

1x (1.5 ... 35 mm)

  • Connectable conductor cross-sections for AWG cables

1x (16 ... 1)

Power supply for the electronics

Design of the power supply

Power supply via CIM

Power

Active power input, max.

8W

Power electronics

Type of load

Ohmic load

Power capacity, max.

69.1kW

51.8kW

64.8kW

69.1kW

51.8kW

64.8kW

  • for delta connection with fan at 40 C, max.

69.1kW

51.8kW

64.8kW

69.1kW

51.8kW

64.8kW

Switching capacity current per phase, max.

83A

63A

80A

83A

63A

80A

Short-time withstand current (SCCR) acc. to UL 508A

50kA

100kA

50kA

100kA

Heating power

  • Number of digital outputs

9

  • Number of heat emitters per output, max.

1

  • Output voltage for heating power

400V

  • Power carrying capacity per output, min.

200W

  • Power carrying capacity per output, max.

7680W

5760W

7200W

7680W

5760W

7200W

  • for heating elements with high inrush current, max.

4000W

3000W

4000W

3000W

4000W

  • Output current for heating power

16A

12A

15A

16A

12A

15A

  • Peak current

150A

100A

150A

100A

150A

  • Melting I2t value

250As

225As

400As

250As

225As

400As

  • Design of short-circuit protection per output

Fuse 16 A

Fuse 15 A

Melting fuse 20 A

Fuse 16 A

Fuse 15 A

Melting fuse 20 A

  • Design of overvoltage protection

Transil Diode

Integration and conversion time/resolution per channel

  • Design of electrical connection at output for heating and fan

Connector, 3-pole with spring-loaded connection

  • Connectable conductor cross-sections, solid

1x (0.2 ... 10 mm)

  • Connectable conductor cross-sections, finely stranded with wire end processing

1x (0.25 ... 6 mm)

  • Connectable conductor cross-sections for AWG cables, stranded

1x (24 ... 8)

Interfaces

Interfaces/bus type

system interface

Interrupts/diagnostics/status information

Number of status displays

12

LED status display

LED green = ready, LED yellow = heating on/off, LED red = error display, LED red = error for each channel

Diagnostics function

Voltage diagnostics

Diagnostic messages

  • Wire-break

Yes

  • Fuse blown

Yes

  • Heat emitter defect

Yes

Integrated Functions

Monitoring functions

  • Temperature monitoring

Yes

  • Type of temperature monitoring

NTC thermistor

Measuring functions

  • Voltage measurement

Yes

Potential separation

Design of electrical isolation

Optocoupler and/or protective impedance between main circuit and PELV

between the outputs

No

Isolation

Overvoltage category

III

Degree of pollution

2

EMC

EMC interference emission

Limit value in accordance with IEC 61000-6-4:2007 + A1:2011

Electrostatic discharge acc. to IEC 61000-4-2

4 kV contact discharge / 8 kV air discharge

Field-related interference acc. to IEC 61000-4-3

10 V/m (80 ... 1 000 MHz), 3 V/m (1.4 ... 2.0 GHz), 1 V/m (2.0 ... 2.7 GHz)

Conducted interference due to burst acc. to IEC 61000-4-4

2 kV power supply lines, 2 kV load lines

Conducted interference due to surge acc. to IEC 61000-4-5

on supply and load lines: 1 kV symmetric, 2 kV unsymmetric

Conducted interference due to high-frequency radiation acc. to IEC 61000-4-6

10 V (0.15 ... 80 MHz)

Degree and class of protection

IP degree of protection

IP20

Standards, approvals, certificates

CE mark

Yes

UL approval

Yes

RCM (formerly C-TICK)

Yes

KC approval

Yes

EAC (formerly Gost-R)

Yes

China RoHS compliance

Yes

Device tag according to DIN EN 81346-2

Q

Ambient conditions

Ambient temperature during operation

  • min.

0C

  • max.

55C

Ambient temperature during storage/transportation

  • Storage, min.

-25C

  • Storage, max.

70C

  • Transportation, min.

-25C

  • Transportation, max.

70C

Air pressure acc. to IEC 60068-2-13

  • Operation, min.

860hPa

  • Operation, max.

1080hPa

  • Storage, min.

660hPa

  • Storage, max.

1080hPa

  • Installation altitude above sea level, max.

2000m

Relative humidity

  • Operation at 25 ℃, max.

95%

  • Operation at 50 ℃, max.

50%; 95 % at 25 C, decreasing linearly to 50 % at 50 C

Vibrations

  • Vibration resistance during operation acc. to IEC 60068-2-6

10 ... 58 Hz / 0.075 mm, 58 ... 150 Hz / 1 g

  • Vibration resistance during storage acc. to IEC 60068-2-6

5 ... 8.5 Hz / 3.5 mm, 8.5 ... 500 Hz / 1 g

Shock testing

  • Shock resistance during operation acc. to IEC 60068-2-27

15 g / 11 ms / 3 shocks/axis

  • Shock resistance during storage acc. to IEC 60068-2-29

25 g / 6 ms / 1 000 shocks/axis

Dimensions

Width

104mm

Height

340mm

344mm

Depth

250mm

217mm



















  © " " 2007-2022