Transmission rate | | | |
Transfer rate | 10 Mbit/s, 100 Mbit/s, 1 000 Mbit/s | 10 Mbit/s, 100 Mbit/s, 1 000 Mbit/s | 100 Mbit/s, 1 000 Mbit/s |
Interfaces for communication integrated | | | |
Number of electrical connections | | | |
| 8 | 8 | |
| | 8 | |
Number of 10/100/1000 Mbit/s RJ45 ports Integrated | | | |
| 8 | | |
| | 8 | |
Number of electrical connections | | | |
| | | 8 |
Interfaces for communication pluggable maximum | | | |
Number of electrical connections | | | |
| | | 8 |
Interfaces others | | | |
Type of electrical connection | | | |
| | 2-pole terminal block | |
Number of extender expansion interfaces | 2 | 2 | 2 |
Product feature hot-swappable interface modules | Yes | Yes | Yes |
Supply voltage, current consumption, power loss | | | |
Type of voltage of the supply voltage | | DC | |
Supply voltage | | | |
| | 54 V | |
| | 51.3 V | |
| | 56.7 V | |
Product component fusing at power supply input | | Yes | |
Fuse protection type at input for supply voltage | | F 4 A / 60 V | |
Consumed current maximum | 0.2 A | 0.2 A | 0.07 A |
Power loss [W] | | | |
| 4.8 W | 4.8 W | 1.7 W |
Supplied active power of PSE with PoE | | | |
| | 30 W | |
| | 180 W | |
Permitted ambient conditions | | | |
Ambient temperature | | | |
| -40 ... +70 °C | -40 ... +60 °C | -40 ... +60 °C |
| -40 ... +85 °C | -40 ... +85 °C | -40 ... +85 °C |
| -40 ... +85 °C | -40 ... +85 °C | -40 ... +85 °C |
Relative humidity | | | |
| 95 % | 95 % | 95 % |
Protection class IP | IP20 | IP20 | IP20 |
Design, dimensions and weight | | | |
Design | SIMATIC S7-1500 device design | SIMATIC S7-1500 device design | SIMATIC S7-1500 device design |
Number of modular height units relating to 19-inch cabinet | | | 1 |
Width | 70 mm | 70 mm | 70 mm |
Height | 147 mm | 147 mm | 147 mm |
Depth | 125 mm | 125 mm | 125 mm |
Net weight | 0.6 kg | 0.7 kg | 0.6 kg |
Mounting type | | | |
| No | No | No |
| Yes | Yes | Yes |
| No | No | No |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
Standards, specifications, approvals | | | |
Standard | | | |
| FM3611: Class 1, Divison 2, Group A, B, C, D / T4, Class 1, Zone 2, Group IIC, T4 | FM3611: Class 1, Divison 2, Group A, B, C, D / T4, Class 1, Zone 2, Group IIC, T4 | FM3611: Class 1, Divison 2, Group A, B, C, D / T4, Class 1, Zone 2, Group IIC, T4 |
| EN 60079-0: 2009, EN60079-15: 2010, II 3 G Ex nA IIC T4 Gc, KEMA 07 ATEX 0145 X, IECEx DEK 14.0025X | EN 60079-0: 2009, EN60079-15: 2010, II 3 G Ex nA IIC T4 Gc, KEMA 07 ATEX 0145 X, IECEx DEK 14.0025X | EN 60079-0: 2009, EN60079-15: 2010, II 3 G Ex nA IIC T4 Gc, KEMA 07 ATEX 0145 X, IECEx DEK 14.0025X |
| UL 508, UL 60950-1, CSA C22.2 Nr. 60950-1-03 | UL 508, UL 60950-1, CSA C22.2 Nr. 60950-1-03 | UL 508, UL 60950-1, CSA C22.2 Nr. 60950-1-03 |
| ISA 12.12.01-2012 (Hazardous Location), Class 1 / Division 2 / Group A, B, C, D / T4, Class 1 / Zone 2 / Group IIC / T4 | ISA 12.12.01-2012 (Hazardous Location), Class 1 / Division 2 / Group A, B, C, D / T4, Class 1 / Zone 2 / Group IIC / T4 | ISA 12.12.01-2012 (Hazardous Location), Class 1 / Division 2 / Group A, B, C, D / T4, Class 1 / Zone 2 / Group IIC / T4 |
| EN 61000-6-4 (Class A) | EN 61000-6-4 (Class A) | EN 61000-6-4 (Class A) |
| EN 61000-6-2 | EN 61000-6-2 | EN 61000-6-2 |
Standards, specifications, approvals CE | | | |
Certificate of suitability CE marking | Yes | Yes | Yes |
Standards, specifications, approvals miscellaneous | | | |
Certificate of suitability | EN 61000-6-2, EN 61000-6-4 | EN 61000-6-2, EN 61000-6-4 | EN 61000-6-2, EN 61000-6-4 |
| Yes | Yes | Yes |
| | Yes | |
| Yes | Yes | Yes |
Standards, specifications, approvals ship classification | | | |
Marine classification association | | | |
| No | No | No |
| No | No | No |
| Yes | Yes | Yes |
| No | No | No |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
Standards, specifications, approvals product conformity | | | |
MTBF at 40 °C | 58 y | | 63 y |